Duty Cycle Input
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Features
|
|
![]()
|
Description
Exceptional Accuracy and Stability
|
![]()
Specifications
Laureate 4-20 mA Transmitter
Duty Cycle Input
| Duty Cycle Mode | |
| Item Displayed Display Units Frequency Range Input Accuracy |
ON
or OFF duty cycle of periodic pulse waveshape |
| Update Rate | |
|
Conversion Interval Gate Time Time Before Zero Output |
Gate
time + 30 ms + 0-2 signal periods |
| Pulse Input | |
| Types Grounding Minimum Signal Maximum Signal Noise Filter Contact Debounce |
AC,
pulses from NPN, PNP transistors, contact closures, magnetic pickups. |
| Analog Output | |
|
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Update Rate Output Isolation |
4-20 mA and 0-10 Vdc (selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load ) 12 bits (4,096 steps) ±0.05% of output span 25/sec max 250V rms working, 2.3 kV rms per 1 minute test |
| Transducer Excitation Output (standard) | |
|
Jumper Selection 1 Jumper Selection 2 Jumper Selection 3 |
10V @ 60 mA, isolated to 50V from signal ground 5V @ 50 mA, isolated to 50V from signal ground 15V @ 60 mA, non-isolated |
| Dual Relay Output (optional) | |
|
Relay Type Load rating |
Two solid state relays, SPST, normally open,
Form A 120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance. |
| Power Input | |
|
Standard power Low power option Frequency Power Isolation |
95-240V AC ±10% or 90-300V DC 12-30V AC or 10-48V DC DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test. |
| Mechanical | |
|
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
| Environmental | |
|
Operating Temperature Storage Temperature Relative Humidity |
0°C to
70°C -40°C to 85°C 95% at 40°C, non-condensing |
![]()
| Application Example |
Duty Cycle and Elapsed Time of a Laser |
|
![]() |
Duty cycle can be used to indicate the ON time of a pulsed laser in relation to total time. Laureate counters and transmitters can also measure elapsed time, the number of pulses, average width in µs, the number of pulses, and total energy applied. |
![]()
Pinout
Laureate 4-20 mA Transmitter,
Duty Cycle Input
(shown with optional dual relay
output)
|
|
|
|
Transmitter
Powering a Single Sensor |
|
|
|
![]() |
| Transmitter Powering Two Sensors | Transmitter with Active or Passive Sensors |
![]()
Ordering
Guide
Laureate 4-20 mA Transmitter,
Duty Cycle Input
| Create a model
number in this format: TA802FR. This is for a 4-20 mA transmitter,
Extended main board, 95-240 Vac power, isolated dual
solid state relays, and dual channel pulse input
signal conditioner. Includes detachable screw clamp
connectors. |
|
Transmitter Type |
TA Laureate 4-20 mA Transmitter. | $235 |
| Main Board | 8 Extended Main Board (required for duty cycle). | $40 |
| Power |
0 Isolated 95-240 Vac & 90-300 Vdc. 1 Isolated 12-30 Vac & 10-48 Vdc. |
NC $30 |
|
Setpoint Output |
0 None. 2 Isolated Dual Solid State Relays. |
NC $30 |
| Input Type | FR Dual-Channel Pulse Input. | NC |
| Accessories |
CBL03 RS-232 cable, TA to computer. CBL02 USB to RS-232 cable adapter. |
$19 $39 |
|
Resource Pages |
|
3183-G Airway Avenue Costa Mesa, CA 92626, USA |
||
|---|---|---|---|
|
|
|