4-20 mA Thermocouple Transmitter
Exceptional linearity & accuracy at high update rates.
DIN Rail mounted, digitally
programmable.

Standard Features
- Factory calibrated for thermocouple types J, K, T, E, N, R, S
- User selectable
4-20 mA, 0-20 mA or 0-10 Vdc linearized analog
output
- User selectable input span from entire
thermocouple range down to 15.0°
- Highly accurate and repeatable
- Upscale or downscale open sensor
indication
- Output update rate to 60/sec
- Output resolution: 0.0015% of span (16 bits)
- Universal AC switching power supply for 85-264 Vac
- DIN rail mount housing only 22.5 mm wide
- Detachable screw-clamp connectors
- Dual solid state relays for alarm or control, isolated
- RS232 or RS485 serial communications, isolated
- Universal AC power, 85-264 Vac
- Easy setup with PC-based
Instrument Setup Software
- Priced at only $235
(basic temperature transmitter)
Options:
- Low voltage power,
10-48 Vdc or 12-32 Vac
|

Description
The Laureate 4-20 mA
thermocouple transmitter provides
a linearized, highly accurate, stable
and repeatable transmitter output for thermocouple types J, K, T, E, N, R
or S. The
thermocouple or RTD type and temperature range, specified in °C or °F, are
user-selectable. The temperature range can be as wide as the entire span of
the thermocouple type, or as narrow as 150 counts (such as
15.0°), limited only by considerations of electrical noise and digital
filtering time constants.
Digital
calibration of all
thermocouple ranges is performed the factory, with calibration data stored
in EEPROM on the signal conditioner board. This allows signal
conditioner boards and ranges to be changed in the field with no need for
recalibration. Cold junction compensation automatically
corrects for temperature variations at the thermocouple reference junction at the
transmitter.
Open sensor indication is standard and may be set up to indicate either upscale or
downscale.
Fast update rates at up to 50
or 60 conversions per second while integrating the signal over a
full power line cycle are provided by Concurrent Slope (Pat 5,262,780)
analog-to-digital conversion. High read
rate is ideal for peak or valley capture and for real-time computer interface and control.
Three analog transmitter
settings are
jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All
selections provide 16-bit (0.0015%) resolution of output span and
0.02% output accuracy. The output tracks the reading
from
-99,999 to +99,999 counts that would be transmitted digitally. For DC signals, this
reading has a rated accuracy of ±0.01% of full scale input and can be
scaled in software. Output isolation from signal and power grounds
eliminates potential ground loop problems. The supply can drive 20 mA into a
500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher)
load for 2 mA compliance.
Standard features of Laureate
thermocouple transmitters include:
-
Analog transmitter output, 16-bit, user scalable and isolated. User selectable 4-20 mA,
0-20 mA or 0-10V levels.
- Serial communications, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or
Laurel ASCII protocol.
- Dual solid state relays for control or alarm, isolated.
Rated 120 mA at 130 Vac or 170 Vdc.
- Universal AC power supply for 85-264 Vac.
Low voltage power of
10-48 Vdc or 12-32 Vac is optional.
Easy Transmitter programming is via
Laurel's Instrument Setup Software,
which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from
Laurel (P/N CBL04).
|

Specifications
Laureate 4-20 mA Thermocouple Temperature Transmitter
|
TC Types |
Range |
Conformity Error |
| J |
-210°C to
+760°C (-347°F to +1400°F) |
±0.09°C
(±0.16°F) |
| K |
-244°C to
+1372°C (-408°F to +2501°F) |
±0.1°C
(±0.17°F) |
| T |
0°C to
+400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F) |
±0.03°C
(±0.05°F)
±0.2°C (±0.36°F) |
| E |
-240°C to
+1000°C (-400°F to +1830°F) |
±0.18°C
(±0.32°F) |
| N |
-245°C to
+1300°C (-410°F to +2370°F) |
±0.10°C
(±0.17°F) |
| R |
-45°C to
+1768°C (-49°F to +3214°F) |
±0.17°C
(±0.31°F) |
| S |
-46°C to
+1768°C (-51°F to +3213°F) |
±0.12°C
(±0.22°F) |
|
Thermocouple
Input |
|
Calibration
Input resistance
Input current
Max lead resistance
Overall accuracy
Span tempco
Reference junction tempco
Span tempco
Over-voltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication |
NIST
Monograph 125 (IPTS-68)
1 Gohm
100 pA
1 kohm max for rated accuracy
±0.01 of full scale ±2 counts
±0.003% of reading/ºC
±0.02 deg/deg
±0.003% of reading/ºC
125 Vac
80 dB plus selectable filter from 80 ms
to 9.6 s time constant
120 dB with 500 W imbalance
250 Vac from power and earth grounds
0 mA or > 20mA output, selectable |
|
Analog Output (standard) |
|
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test |
|
Dual Relay Output (standard) |
|
Relay Type
Load Rating |
Two solid state relays, SPST, normally open,
Form A
130 mA at 140 Vac or 180 Vdc |
|
Serial Communications (standard) |
|
Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing |
RS232 (default) or RS485, 2 or 4-wire (user
selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line without repeater |
|
Power Input |
|
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL
approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical |
|
Mechanical |
|
Dimensions
Mounting
Electrical Connections |
128 x 103 x 22.5 mm
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors |
|
Environmental |
|
Operating
Temperature
Storage Temperature
Relative Humidity
Cooling Required |
0°C
to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan. |

Pinouts
Laureate 4-20 mA
Thermocouple Temperature Transmitter


Operation as a
Fast ON/OFF Controller
or Supervisory Monitor
With the optional dual solid state relay output
option, which has a typical response
time of only 17 ms, Laureate temperature meters
and transmitters can
serve as extremely fast and accurate ON/OFF controllers
for closed-loop temperature control.
They can also serve as
supervisory process monitors and provide alarms or shutoffs when processes exceed normal
limits.
Multiple setpoint operating modes are
individually selectable for each relay, as explained in the
dual-setpoint controller page. Relay duty cycles and chatter can be minimized with programmable hysteresis and
time delays. A band deviation operating mode can be
selected for each relay, where an alarm is generated whenever the reading is a selected
number of counts above or below the setpoint. The relay modes have to be
non-latching, since 4-20 mA temperature transmitters do not offer external
reset.
|

Ordering
Guide
Laureate 4-20 mA Thermocouple Transmitter
Click on the radio buttons to build a model number with pricing (shown below the Ordering Guide).
|