4-20 mA Thermocouple Transmitter
 Exceptional linearity & accuracy at high update rates.
DIN Rail mounted, digitally programmable.

4-20 mA Current Transmitter for Thermocouples

  RoHS Mark
Made in California

Standard Features

  • Factory calibrated for thermocouple types J, K, T, E, N, R, S
  • User selectable 4-20 mA, 0-20 mA or 0-10 Vdc linearized analog output
  • User selectable input span from entire thermocouple range down to 15.0°
  • Highly accurate and repeatable
  • Upscale or downscale open sensor indication
  • Output update rate to 60/sec
  • Output resolution: 0.0015% of span (16 bits)
  • Universal AC switching power supply for 85-264 Vac
  • DIN rail mount housing only 22.5 mm wide
  • Detachable screw-clamp connectors
  • Dual solid state relays for alarm or control, isolated
  • RS232 or RS485 serial communications, isolated
  • Universal AC power, 85-264 Vac
  • Easy setup with PC-based Instrument Setup Software
  • Priced at only $235 (basic temperature transmitter)
    Options:
  • Low voltage power, 10-48 Vdc or 12-32 Vac

Description

The Laureate 4-20 mA thermocouple transmitter provides a linearized, highly accurate, stable and repeatable transmitter output for thermocouple types J, K, T, E, N, R or S. The thermocouple or RTD type and temperature range, specified in °C or °F, are user-selectable. The temperature range can be as wide as the entire span of the thermocouple type, or as narrow as 150 counts (such as 15.0°), limited only by considerations of electrical noise and digital filtering time constants.

Thermocouple signal conditioner boardDigital calibration of all thermocouple ranges is performed the factory, with calibration data stored in EEPROM on the signal conditioner board. This allows signal conditioner boards and ranges to be changed in the field with no need for recalibration. Cold junction compensation automatically corrects for temperature variations at the thermocouple reference junction at the transmitter. Open sensor indication is standard and may be set up to indicate either upscale or downscale.

Fast update rates at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle are provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control.

Three analog transmitter settings are jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy. The output tracks the reading from -99,999 to +99,999 counts that would be transmitted digitally. For DC signals, this reading has a rated accuracy of ±0.01% of full scale input and can be scaled in software. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.

Standard features of Laureate thermocouple transmitters include:

  • Analog transmitter output, 16-bit, user scalable and isolated. User selectable 4-20 mA, 0-20 mA or 0-10V levels.
  • Serial communications, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or Laurel ASCII protocol.
  • Dual solid state relays for control or alarm, isolated. Rated 120 mA at 130 Vac or 170 Vdc.
  • Universal AC power supply for 85-264 Vac. Low voltage power of 10-48 Vdc or 12-32 Vac is optional.

Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04).

Specifications
Laureate 4-20 mA Thermocouple Temperature Transmitter

TC Types Range Conformity Error
J -210°C to +760°C (-347°F to +1400°F) ±0.09°C (±0.16°F)
K -244°C to +1372°C (-408°F to +2501°F) ±0.1°C (±0.17°F)
T 0°C to +400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F)
±0.03°C (±0.05°F)
±0.2°C (±0.36°F)
E -240°C to +1000°C (-400°F to +1830°F) ±0.18°C (±0.32°F)
N -245°C to +1300°C (-410°F to +2370°F) ±0.10°C (±0.17°F)
R -45°C to +1768°C (-49°F to +3214°F) ±0.17°C (±0.31°F)
S -46°C to +1768°C (-51°F to +3213°F) ±0.12°C (±0.22°F)
 

Thermocouple Input

Calibration
Input resistance
Input current
Max lead resistance
Overall accuracy
Span tempco
Reference junction tempco
Span tempco
Over-voltage protection

NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication

NIST Monograph 125 (IPTS-68)
1 Gohm
100 pA
1 kohm max for rated accuracy
±0.01 of full scale ±2 counts
±0.003% of reading/ºC
±0.02 deg/deg
±0.003% of reading/ºC
125 Vac
80 dB plus selectable filter from 80 ms to 9.6 s time constant
120 dB with 500 W imbalance
250 Vac from power and earth grounds
0 mA or > 20mA output, selectable

Analog Output (standard)

Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation

4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test

Dual Relay Output (standard)

Relay Type
Load Rating

Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc

Serial Communications (standard)

Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing

RS232 (default) or RS485, 2 or 4-wire (user selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line without repeater

Power Input

Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption

85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical

Mechanical

Dimensions
Mounting
Electrical Connections

120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors

Environmental

Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required

0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.

Pinouts
Laureate 4-20 mA Thermocouple Temperature Transmitter

Pinout of thermocouple temperature transmitter

Operation as a Fast ON/OFF Controller or Supervisory Monitor

Temperature controller operation of Laureate temperature meters and transmittersWith the optional dual solid state relay output option, which has a typical response time of only 17 ms, Laureate temperature meters and transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. They can also serve as supervisory process monitors and provide alarms or shutoffs when processes exceed normal limits.

Multiple setpoint operating modes are individually selectable for each relay, as explained in the dual-setpoint controller page. Relay duty cycles and chatter can be minimized with programmable hysteresis and time delays. A band deviation operating mode can be selected for each relay, where an alarm is generated whenever the reading is a selected number of counts above or below the setpoint. The relay modes have to be non-latching, since 4-20 mA temperature transmitters do not offer external reset.

Ordering Guide
Laureate 4-20 mA Thermocouple Transmitter
 Click on the radio buttons to build a model number with pricing (shown below the Ordering Guide).

Quantity
Transmitter
Type
LTA  Laureate 4-20 mA Transmitter $235
Main Board Standard Main Board NC
Power Isolated 85-264 Vac
Isolated 10-48 Vdc or 12-32 Vac
NC
$30
Relay
Output
None.
Isolated Dual Solid State Relays
NC
NC
Thermcouple
Input
JC  Thermocouple Type J, -210°C to 760°C
JF  Thermocouple Type J, -347°F to 1400°F
KC  Thermocouple Type K, -347°C to 1372°C
KF  Thermocouple Type K, -408°F to 2501°F
TC  Thermocouple Type T, -257°C to 400°C
TF  Thermocouple Type T, -430°F to 752°F
EC  Thermocouple Type E, -240°C to 1000°C
EF  Thermocouple Type E, -400°F to 1830°F
NC  Thermocouple Type N, -240°C to 1000°C
NF  Thermocouple Type N, -410°F to 2370°F
SC  Thermocouple Type S, -46°C to 1768°C
SF  Thermocouple Type S, -51°F to 3214°F
R Thermocouple Type R, -45°C to 1768°C
RF  Thermocouple Type R, -49°F to 3213°F
 NC

Note: The same signal conditioner board can be user configured for all thermocouple types listed and °C or °F.

Accessories CBL04  RS-232 cable, LTA to computer or USB adapter
CBL02
  USB to RS-232 cable adapter
$19
$39
 

Configured model number

LTA200JC

Configured price per model

$235

Quantity

1

Extended price

$235

 

 

  