Totalizer for 0-1 mA, 4-20 mA
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Features Standard Main Board
Extended Main Board
|
![]()
|
![]()
Description Laureate 4-20 mA output, process signal input totalizing transmitters accept 0-1 mA, 4-20 mA or 0-10V signals from flow meters and other transducers, such as watt meters, to track rate or totalized rate.
The process transmitters convert the full-scale 0-1 mA, 4-20 mA or 0-10 V analog input signal to a frequency of 10-110 kHz, which is converted internally to a 6-digit rate reading rate using inverse period timing, and from there to the analog transmitter output. The analog output is accurate to ±0.05% of output span, as determined by an ultra-linear 12-bit (4096 step) digital-to-analog converter (DAC). The output update rate is a fast 25/sec. Output isolation from signal and power grounds is provided by a separate on-board power supply, which can drive 20 mA into a 500 ohm load for 10V compliance. Output isolation eliminates problems caused by ground loops. In addition to the 4-20 mA output that would typically be used for signal transmission in an industrial environment, a 0-10V analog output is selectable. Transmitter programming is via a three-terminal RS-232 port using Laurel's PC-based Instrument Setup Software. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL03). The transmitters are housed in a DIN rail case that is only 22.5 mm (0.89") thick. Signal connections are via detachable screw clamp plug connectors. |
![]()
Specifications
Laureate 4-20 mA Transmitters
Analog Input Rate Transmitter &
Totalizer
| Analog Input | 0-1 mA | 4-20 mA | 0-10 V |
|
Input resistance Max current or voltage |
182 ohms 37 mA |
9 ohms 160 mA |
1 Mohm 600 V |
|
Input Resolution Span Tempco Zero Tempco Accuracy at 25°C Read Rate |
6 digits |
||
| Analog Output | |||
|
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Update Rate Output Isolation |
4-20 mA and 0-10 Vdc (selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load ) 12 bits (4,096 steps) ±0.05% of output span 25/sec 250V rms working, 2.3 kV rms per 1 minute test |
||
| Transducer Excitation Output (standard) | |||
|
Jumper Selection 1 Jumper Selection 2 Jumper Selection 3 |
10V @ 60 mA, isolated to 50V from signal ground 5V @ 50 mA, isolated to 50V from signal ground 15V @ 60 mA, non-isolated |
||
| Dual Relay Output (optional) | |||
|
Relay Type Load rating |
Two solid state relays, SPST, normally open,
Form A 120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance. |
||
| Power Input | |||
|
Standard power Low power option Frequency Power Isolation |
95-240V AC ±10% or 90-300V DC 12-30V AC or 10-48V DC DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test. |
||
| Mechanical | |||
|
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
||
| Environmental | |||
|
Operating Temperature Storage Temperature Relative Humidity |
0°C to
70°C -40°C to 85°C 95% at 40°C, non-condensing |
||
![]()
Pinout
Laureate 4-20 mA Transmitters
Analog Input Rate Transmitter &
Totalizer
(shown with optional dual relay
output)
|
|
|
DC
& Externally Powered Process Transmitter |
|
|
| Transmitter Powering Two Sensors |
![]()
Ordering
Guide
Laureate 4-20 mA Transmitters
Analog Input Rate Transmitter &
Totalizer
|
Create a model
number in this format: TA202VF3. This is for a 4-20 mA transmitter,
Standard main board, 95-240 Vac power, isolated dual
solid state relays, and 0-10V process signal conditioner. Includes detachable screw clamp
connectors. |
|
Transmitter Type |
TA Laureate 4-20 mA Transmitter. | $235 |
| Main Board |
6 Standard Main Board. 8 Extended Main Board With Standard Main Board: Rate, square root of rate, or totalized rate from differential pressure flow transducers with a DC output. With Extended Main Board: Above plus linearization of nonlinear inputs, batch operation, 1/rate (time). |
NC $40 |
| Power |
0 Isolated 95-240 Vac & 90-300 Vdc 1 Isolated 12-30 Vac & 10-48 Vdc. |
NC $30 |
|
Setpoint Output |
0 None. 2 Isolated Dual Solid State Relays. |
NC $30 |
| Input Type |
Voltage-to-Frequency
Converter VF1 V-to-F Converter, 4-20 mA. VF2 V-to-F Converter, 0-1 mA. VF3 V-to-F Converter, 0-10V. In the write-in field of your invoice, specify min input, min reading; max input, max reading. |
NC |
| Accessories |
CBL03 RS-232 cable, TA to computer. BL02 USB to RS-232 cable adapter. |
$19 $39 |
|
Resource Pages |
|