True AC RMS Voltage or Current
Modbus or Laurel ASCII Protocol Serial I/O Transmitter

4-20 mA Current Transmitters for AC RMS Voltage or Current

CE Mark      RoHS Mark

DIN Rail mounted, digitally programmable.
Exceptional accuracy at high update rates.

Features

  • Selectable Modbus or Laurel ASCII protocol.
  • Modbus RTU or ASCII modes, 2-wire connection, up to 247 digital addresses.
  • 0.2, 2, 20, 200, 200V & 600V AC input ranges.
  • 2, 20, 200 mA and 5A AC input ranges.
  • All ranges factory calibrated.
  • AC coupled, frequencies from 10 Hz to 10 kHz.
  • Crest factor of 2.4 at full scale input.
  • Output accuracy: ±0.1% of full span.
  • DIN rail mount package only 22.5 mm thick.
  • Detachable screw clamp connectors.
  • Easy setup using PC-based Instrument Setup Software.
  • Optional isolated scalable analog output (4-20 mA or 0-10V).
  • Optional dual solid state relays for alarm or control.
  • Optional custom curve linearization (Extended main board).

Description

AC Ranges.  The Laureate Serial I/O, AC RMS input transmitter provides six voltage ranges and four current ranges, all factory calibrated and jumper selectable. The 200.00 mV and 2.0000 V ranges provide a high input impedance of 22 Mohm to minimize the load on the voltage signal. A special 5.000A range allows the output of 5A current transformers to be applied directly to the transmitter, with no need for a stepdown transformer. The current readings can easily be scaled digitally as needed.

True RMS. Precision circuitry is used to determine the root-mean-square of complex waveforms from 10 Hz to 10 kHz. Spikes up to 2.4 times the maximum of each range are accurately measured. This provides a crest factor (Vp / Vrms) of 240 for a signal amplitude of 1% of full scale, decreasing to 2.4 at 100% of full scale. Laureate AC RMS input transmitters duplicate the performance and programmable features of their Laureate AC RMS digital panel meter counterparts.

Frequency and amplitude operating range of Laureate AC RMS Voltage or Current Input Transmitter

Maximum error as a function of frequency
and signal amplitude

Serial Data Output. Laureate TM Series transmitters send data as a serial digital signal. RS485 or RS232 signal levels are jumper selectable and can each be associated with either the Modbus protocol or Laurel’s simpler Custom ASCII protocol.

  • Modbus protocol operation is fully compliant with the Modbus Over Serial Line Specification V1.0 (2002) for 2-wire, half-duplex connection. This includes RTU or ASCII modes, addressing of up to 32 devices per RS485 line without a repeater, and up to 247 digital addresses. Modbus operation allows devices by different manufacturers to be connected in parallel and be addressed using the same protocol.
     
  • Laurel’s Laurel ASCII protocol allows up to 31 Laureate devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Laureates. It also allows use of Laurel’s datalogging software.

Transmitter programming is via the unit's three-terminal serial port using Laurel's PC-based Instrument Setup Software. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL03). Laurel's serial output transmitters and meters can also be part of PC-based data logging systems using Laurel's Datalogging Software, which operates under the Laurel ASCII Protocol. A single software command switches between the Modbus and Laurel ASCII Protocols.

Transmitter options include dual solid state relays for local alarm or control and an isolated 4-20 mA or 10V (selectable) analog output, effectively providing a linearized analog transmitter output that tracks the reading that would be transmitted digitally. The analog output provides 12-bit (4096 step) resolution of the output span and is ultra-linear to within one bit. Its accuracy is ±0.05% of span for all signal types, except for AC rms, where accuracy is ±0.1%. Output isolation from signal and power grounds is provided by a separate on-board power supply, which can drive 20 mA into a 500 ohm load for 10V compliance. Output isolation eliminates problems caused by ground loops.

DIN Rail Mounting.  Laureate transmitters are housed in a 35 mm DIN rail case that is only 22.5 mm (0.89") thick. Signal connections are via detachable screw clamp plug connectors.

Specifications
Laureate Serial Output Transmitters, AC RMS Voltage or Current Input

AC RMS Input

Range

Resolution Input Ohms
Voltage Ranges
& Input Resistance
(1% to 100% of full scale)

  200.00 mV  
2.0000 V
20.000 V
200.00 V
600.0 V

10 µV
100 µV
1 mV
10 mV
100 mV

22 Mohm
22 Mohm
1 Mohm
1 Mohm
1 Mohm

Current Ranges
& Input Resistance
(1% to 100% of full scale)

2.0000 mA
20.000 mA
200.00 mA
5.000 A

0.1 µA
1 µA
10 µA
1 mA

100 ohms
10 ohms
1 ohm
0.01 ohm

Input Resolution
Input Accuracy
Output Update Rate
Converter Settling Time
Max applied voltage
Over-current protection
16 bits (65,536 steps)
±0.1% of full scale input (determined by ADC).
50 or 60 per second
1 sec (RMS converter)
600 Vac for 20, 200 & 600 V ranges, 125 Vac other ranges.
25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, 1x for 5A.
Serial I/O (standard)
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance
RS485 (default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002).
Transducer Excitation Output (standard)
Jumper Selection 1
Jumper Selection 2
Jumper Selection 3
10V @ 60 mA, isolated to 50V from signal ground
5V @ 50 mA, isolated to 50V from signal ground
15V @ 60 mA, non-isolated
Dual Relay Output (optional)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance.
Analog Output (optional)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
0-20 mA, 4-20 mA or  0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test
Power Input
Standard power
Low power option
Frequency
Power Isolation
95-240V AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test.
Mechanical
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw clamp plug connectors.
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
0°C to 70°C
-40°C to 85°C
95% at 40°C, non-condensing

Pinout
Laureate Serial Output Transmitter, AC RMS Voltage or Current Input
(shown with optional analog output and dual relay output)

Pinout, Serial ASCII or Modbus Transmitter, AC RMS Voltage or Current Input

Ordering Guide
Laureate Serial Output Transmitter, AC RMS Voltage or Current Input

Create a model number in this format: TA2020RMV1. This example calls out a Modbus I/O transmitter, standard main board, 95-240 Vac power, isolated dual solid state relays, no analog output, and a 200.00 mV AC input signal. Includes plug-in screw clamp connectors.
  
Transmitter
Type
TM   Laureate Transmitter, Modbus or Laurel ASCII Protocol. $210
Main Board Standard Main Board.
Extended Main Board.
NC
$40
Note: Extended allows custom curve linearization and rate from successive readings. Not applicable to temperature.  
Power 95-240 Vac & 90-300 Vdc
12-30 Vac & 10-48 Vdc.
NC
$30
Setpoint
Output
None.
Isolated Dual Solid State Relays.
NC
$30
Analog Output None.
4-20 mA, 0-10V.
NC
$25
Signal Input True AC RMS Volts
RMV1  200.00 mV.
RMV2  2.0000 V.
RMV3  20.000 V.
RMV4  200.00 V.
RMV5  600.0 V (range not UL approved).
RMV6  300.0 V.
 $35
True AC RMS Amps
RMA1  2.0000 mA.
RMA2  20.000 mA.
RMA3  200.00 mA.
RMA4  5.000 A.
 $35
Note: The same AC RMS signal conditioner can be user configured for AC Volts or AC Amps. It is precalibrated in EEPROM for all AC Volt and AC Amp ranges listed.  
Accessories CBL03  RS-232 cable, TM to computer.
CBL02  USB to RS-232 cable adapter.
$19
$39
 
Laurel Electronics domestic orders Order from distributors for shipment to USA or Canada.
Laurel Electronics international orders Order online for international shipment.
 

Price List  |  Distributors  |  Search  |  Inquiry  |  Privacy  |  Home

  
Laurel Electronics, Inc.
Industrial Instrumentation & Displays
3183-G Airway Avenue
Costa Mesa, CA 92626, USA
Phone: (714) 434-6131
Fax:
     (714) 434-3766

  
© 1996-2008 Laurel Electronics, Inc.