Stopwatch for Single Events
or Accumulated Events

4-20 mA Current Transmitter
Modbus or Laurel ASCII Protocol Serial I/O Transmitter
 Resolution to 0.2 µs.  Duration to 999,999 hrs.
DIN Rail mounted, digitally programmable.

Features

  • Selectable Modbus or Laurel ASCII protocol.
  • Modbus RTU or ASCII modes, 2-wire connection, up to 247 digital addresses.
  • Times single event time or accumulated time of all events.
  • Timing resolution to 0.2 µs.
  • Timing duration to 999,999 hrs.
  • Selectable H, M or S decimal format. 
  • Selectable HH.MM.SS clock format. 
  • Inputs from NPN or PNP proximity switches, contact closures, digital logic, or magnetic pickups down to 12 mV.
  • Triggers on positive or negative pulse edges.
  • Isolated 5V, 10V or 15V dc excitation output to power transducers.
  • DIN rail mount package only 22.5 mm thick.
  • Detachable screw clamp plug connectors.
  • Easy setup using PC-based Instrument Setup Software.
  • Optional dual solid state relays for alarm or control.

Serial ASCII or Modbus Transmitter, Stopwatch Input
CE Mark      
RoHS Mark

Description

Stopwatch mode of Laureate TransmitterStopwatch Operation

The Laureate TM Series serial output stopwatch transmitter performs all of the functions of the Laureate panel mount stopwatch, except for the display. The data retrieved via serial commands can be the time of individual events (Item #1) which produce start and stop pulses, or accumulated time of multiple events (Item #2). The highest resolution is 0.2 µs, making the transmitter ideal for fast events. The longest timing interval is 999,999 hrs. For long events, the output is updated continuously during timing. There are two primary timing modes:

  • A-A Stopwatch Mode. Time is measured between a start pulse and a stop pulse, both on Channel A, from either the positive or negative edges.
      
  • A-B Stopwatch Mode. Time is measured between a start pulse on Channel A (positive or negative edge) and a stop pulse on Channel B (positive or negative edge). This mode allows inputs from different sources. In addition, the A and B inputs can be tied together to start the stopwatch with one polarity and stop it with the other polarity.

Event time (Item #1) is measured by counting 5.5 MHz clock pulses from a calibrated quartz crystal. The stopwatch output is updated during timing at a rate controlled by a gate time, up to 25/sec. Time is reset to zero when the next start pulse occurs. Accumulated time from multiple events up to 999,999 hours (Item #2) can also be tracked.

Signal Conditioner Board for Stopwatch TransmitterUniversal Signal Conditioner

The dual-channel signal conditioner used for pulse detection accepts inputs from proximity switches with PNP or NPN output, TTL or CMOS logic, magnetic pickups, contact closures, and other signals from 12 mV to 250 Vac. Jumper selections provide optimum operation for different sensor types and noise conditions. A built-in isolated 5V, 10V or 15V dc excitation supply can power proximity switches and other sensors, and eliminate the need for an external power supply.

Serial Data I/O & Programming

Laureate TM Series transmitters send data as a serial digital signal. RS485 or RS232 signal levels are jumper selectable and can each be associated with either the Modbus protocol or Laurel’s simpler Laurel ASCII protocol.

  • Modbus protocol operation is fully compliant with the Modbus Over Serial Line Specification V1.0 (2002) for 2-wire, half-duplex connection. This includes RTU or ASCII modes, addressing of up to 32 devices per RS485 line without a repeater, and up to 247 digital addresses. Modbus operation allows devices by different manufacturers to be connected in parallel and be addressed using the same protocol.
     
  • Laurel’s Laurel ASCII protocol allows up to 31 Laureate devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Laureates. It also allows use of Laurel’s datalogging software.

Transmitter programming is via the unit's three-terminal serial port using Laurel's PC-based Instrument Setup Software. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL03). Laurel's serial output transmitters and meters can also be part of PC-based data logging systems using Laurel's Datalogging Software, which operates under the Laurel ASCII Protocol. A single software command switches between the Modbus and Laurel ASCII Protocols.

Transmitter Options

Options include dual solid state relays for local alarm or control and an isolated 4-20 mA or 10V (selectable) analog output, effectively providing a linearized analog transmitter output that tracks the reading that would be transmitted digitally. The analog output provides 12-bit (4096 step) resolution of the output span and is ultra-linear to within one bit. Its accuracy is ±0.05% of span for all signal types, except for AC rms, where accuracy is ±0.1%. Output isolation from signal and power grounds is provided by a separate on-board power supply, which can drive 20 mA into a 500 ohm load for 10V compliance. Output isolation eliminates problems caused by ground loops.

DIN Rail Mounting 

Laureate transmitters are housed in a 35 mm DIN rail case that is only 22.5 mm (0.89") thick. Signal connections are via detachable screw clamp plug connectors.

Specifications
Laureate Serial I/O Transmitter, Stopwatch Input

Pulse Input
Types

Ch A Frequency, Max
Ch B Frequency, Max
Signal Ground
Minimum Signal
Maximum Signal
Maximum Frequency
Contact Debounce
Time Base Accuracy
Span Tempco
Long-term Drift
AC, pulses from NPN, PNP transistors, contact closures, magnetic pickups.
1 MHz.
250 kHz.
Common ground for channels A & B.
Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V).
250 Vac
1 MHz, 30 kHz,  250 Hz (selectable).
0, 3, 50 ms (selectable).
Quartz crystal calibrated to ±2 ppm.
±1 ppm/°C (typical)
±5 ppm/year
Stopwatch Operation

Timing Modes:
    With CH A only
    With CH A tied to CH B
    With CH A and CH B
   
Timing Interval
Timing Resolution
Selectable Decimal Time
Selectable Clock Time
Output Update
Gate Time

  
+ to + edge, or - to - edge.
+ to - edge, or - to + edge.
+ edge of A to + edge of B, + edge of A to - edge of B,
- edge to A to - edge of B, - edge of A to - edge of B
1 µs to 999,999 hrs
0.2 µs to 1 hr
999999 H, M or S format with decimal point
HH.MM.SS format
Gate time + 30 ms
Programmable from 10 ms to 199.99 s

Serial I/O (standard)
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance
RS485 (default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002).
Transducer Excitation Output (standard)
Jumper Selection 1
Jumper Selection 2
Jumper Selection 3
10V @ 60 mA, isolated to 50V from signal ground
5V @ 50 mA, isolated to 50V from signal ground
15V @ 60 mA, non-isolated
Dual Relay Output (optional)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance.
Analog Output (optional)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
0-20 mA, 4-20 mA or  0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test
Power Input
Standard power
Low power option
Frequency
Power Isolation
95-240V AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test.
Mechanical
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw clamp plug connectors
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
0°C to 70°C
-40°C to 85°C
95% at 40°C, non-condensing

Typical Applications

Stopwatch Mode

Stopwatch mode of Laureate Serial Output Transmitter The stopwatch mode is used to time single events between start and stop pulses on the same channel. Duration of a single wave shape can be measured by tying the A and B channels together.

Timing Process Dynamics

Timing process dynamics by Laureate stopwatch transmitter The start and stop pulses used for timing can be generated by the dual relays in a Laureate panel meter, counter, or transmitter. For instance, the start and stop pulse edges can be created as temperature passes two alarm setpoints, or as temperature cycles in a hysteresis control mode.

Replacing an Oscilloscope with a Laureate Meter or Transmitter

Replacing an oscilloscope by a Laureate stopwatch transmitter

An oscilloscope is great for viewing and timing pulses in a lab. However, in fixed installations where digital timing accuracy and control outputs are required, a low-cost Laureate time interval meter or transmitter will be the instrument of choice. Resolution to 0.2 µs is feasible.

Instrumenting a Pulsed Laser System

Instrumenting a laser system using Laureate timers and stopwatches

Some of the many possibilities in instrumenting a pulsed laser system with Laureate dual-channel counters and transmitters: elapsed time, number of pulses, pulse width, pulse separation, duty cycle, and pulse rep rate.

Pinout
Laureate Serial Output Transmitter
Stopwatch for Single Events or Accumulated Events
(shown with optional analog output and dual relay output)

Pinout, Serial ASCII or Modbus Transmitter, Stopwatch Input

                                   Transmitter Powering a Single Sensor
 

Pinout, Pinout, Serial ASCII or Modbus Transmitter, Stopwatch Input

Pinout, Serial ASCII or Modbus Transmitter, Stopwatch Input
Transmitter Powering Two Sensors Transmitter with Active or Passive Sensors

Ordering Guide
Modbus or Laurel ASCII Protocol Serial I/O Transmitters,
Stopwatch Input

Create a model number in this format: TM6020FR. This example calls out a Modbus output transmitter, Standard main board, 95-240 Vac power, isolated dual solid state relays, no analog output, and dual channel pulse input signal conditioner. Includes plug-in screw clamp connectors.
 
Transmitter
Type
TM    Laureate Transmitter, Modbus or Laurel protocol. $210
Main Board Standard Main Board. NC
Power Isolated 95-240 Vac & 90-300 Vdc
Isolated 12-30 Vac & 10-48 Vdc.
NC
$30
Setpoint
Output
None.
Isolated Dual Solid State Relays.
NC
$30
Analog Output None.
4-20 mA or 0-10V analog output.
NC
$25
Input Type FR  Dual-Channel Pulse Input. NC
Accessories CBL03  RS-232 cable, TM to computer.
CBL02  USB to RS-232 cable adapter.
$19
$39
 
Laurel Electronics domestic orders Order from distributors for shipment to USA or Canada.
Laurel Electronics international orders Order online for international shipment.

 

Price List  |  Distributors  |  Search  |  Inquiry  |  Privacy  |  Home

  
Laurel Electronics, Inc.
Industrial Instrumentation & Displays
3183-G Airway Avenue
Costa Mesa, CA 92626, USA
Phone: (714) 434-6131
Fax:
     (714) 434-3766

  
© 1996-2008 Laurel Electronics, Inc.