A 16-bit analog output option board can turn a Laureate 1/8 DIN digital panel meter, counter, timer or remote display into a superb, isolated, linearized transmitter or signal conditioner with exceptional accuracy and high-speed response. The analog output for thermocouples, RTDs and custom curves is linearized to the displayed reading.
The analog output can be selected as 4-20 mA, 0-20 mA, unipolar 0-10V, or bipolar -10V to +10V with a 20V span and 0V at mid-range. If a voltage output is selected, output pins 1 and 2 may be reversed to provide reversed polarity.
A 16-bit D-to-A converter provides 0.0015% full-scale resolution and ±0.02% full-scale accuracy. The update rate for meters is a fast 60/sec for 60 Hz power or 50/sec at 50 Hz power. The analog output can track the unfiltered signal for fastest response, or a digitally filtered signal for best noise rejection.
Isolation from power and signal is provided by a separate power supply in the meter. This supply can drive 20 mA of current into loads up to 600 ohms for 12V compliance. Isolation to signal ground and power ground eliminates problems caused by ground loops.
Scaling of the analog output can be via the meter's front panel pushbuttons or a serial digital interface using Instrument Setup software. The displayed readings to produce the low and high analog outputs can be set to any value from -99999 to +99999 for DPMs or from -999999 to +999999 for counters and timers. Depending on your selected output range, simply set the meter reading for low analog output (4 mA, 0 mA, 0V or -10V) and for high analog output (20 mA or 10V).
The bipolar -10V to +10V analog output can provide a negative signal for a negative deviation from a setpoint, and a positive signal for a positive deviation. It can also be used for proportional control around a setpoint. For example, if proportional control is desired around 170°C with a ±10°C span, set the -10V output to 160°C and the +10V output to 180°C. The control signal will be 0V at 170°C.
Laureate DIN rail transmitters come standard with a 4-20 mA, 0-20 mA, 0-10V, or bipolar -10 to +10V analog output with 16-bit resolution.
Electrical | |||
---|---|---|---|
Power source | Provided by meter | ||
Signal source | Filtered or unfiltered digitized signal | ||
Output linearization | Linearized to reading | ||
Output Levels (selectable) | 4-20 mA, 0-20 mA, 0-10V, -10 to 10V | ||
Compliance at 20 mA | 12V ( 600 Ω max load ) | ||
Compliance at 10 V | 2 mA ( 5 kΩ min load) | ||
Isolation | 250V rms working, 2.3 kV rms per 1 min test | ||
Output resolution | 16 bits (0.0015% of full scale) | ||
Output nonlinearity | < 0.01% of full scale | ||
Accuracy | < 0.02% of full scale | ||
Output update rate, DPMs | 50 or 60/sec (output may be digitally filtered) | ||
Output update rate, counter rate meter | Gate time + 30 ms + 0-2 periods | ||
Scaling | |||
Zero output & full-scale output, DPMs | -99,999 to +99,999 counts | ||
Zero output & full-scale output, counters | -999,999 to +999,999 counts | ||
Minimum span | 150 counts | ||
J4 Pin Assignments | |||
Unipolar Connections | Bipolar Connections | ||
4-20 mA or 0-20 mA output 1 | Reference or Return 1 | ||
0-10V output 2 | -10V to +10V Output 2 | ||
Isolated ground 3 | N/C 3 | ||