Understanding the Laureate™ 1/8 DIN Digital Panel Meter for DC Voltage and Current
The Laureate™ 1/8 DIN Digital Panel Meter for DC voltage and current is a programmable meter with a DC signal conditioner board, combining high accuracy with a high read rate and a wide range of isolated plug-and-play output option boards. Accuracy is 0.01% of reading ± 2 counts. Voltmeter operation provides six full-scale ranges from ±200.00 mV to ±600.0V, jumper-selected; ammeter operation provides four ranges from ±2.0000 mA to ±5.000 A, with the 5.000A range measuring the IR drop across a built-in 10 milliohm current shunt.
Concurrent Slope A/D Conversion
The meter uses Concurrent Slope (US Pat. 5,262,780) analog-to-digital conversion to integrate signals over a full power line cycle (50 Hz or 60 Hz), enabling a high read rate of up to 50 or 60 conversions per second — distinct from the slower 3.5 (60 Hz) or 3 (50 Hz) readings/second update rate of the visible display itself, which is kept legible for a human operator while the meter samples much faster internally for peak/valley capture.
Noise Rejection and Temperature Stability
Common-mode rejection (CMR) is 130 dB from DC to 60 Hz; normal-mode rejection (NMR) is 90 dB at 50/60 Hz with minimum filtering. Span tempco is 0.003% of reading/°C; zero tempco is 0.1 count/°C.
Range-Dependent Protection
Maximum applied voltage is 600 Vac for the 20V, 200V, and 300V ranges, but only 125 Vac for other ranges. Overcurrent protection varies by current range: 25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, and 1x for the 5A range.
Digital Filtering Modes
An unfiltered selection provides true peak and valley readings for control applications. A batch average filter averages each 16 conversions. An adaptive moving average filter offers a choice of 8 time constants from 80 ms to 9.6 seconds — when a significant signal change occurs, the filter briefly switches to the shortest time constant to follow the change, then reverts to its selected constant; an Auto setting picks the time constant based on signal noise.
Tare Functions
Two tare functions are available: auto-tare, where grounding an input line via an external pushbutton stores the current reading (typically an empty container weight) in memory as an offset, and manual tare, where the tare value is entered directly via front panel or setup software. Pressing the front-panel Reset button toggles between gross reading (total) and net reading (gross with tare subtracted).
Control Inputs and Extended Capability
Two rear panel control inputs (CMOS/TTL levels or dry contacts) can be set to control or activate 14 meter commands. The optional Extended computer board displays rate derived from successive readings and enables custom curve linearization with up to 180 data points — for example, calculating liquid volume or flow rate in a horizontal cylindrical tank from a 4-20 mA level transmitter.
Factory-Calibrated Accuracy
All signal conditioner board ranges are factory-calibrated, with calibration factors stored in EEPROM. Field replacement of the signal conditioner board doesn't require recalibrating the meter. Factory recalibration is recommended annually.
Where DC Voltage & Current Digital Panel Meters Are Used
- Battery Bank & Charging System Monitoring — voltage and current readout for UPS, telecom, and backup power systems.
- Renewable Energy Systems — PV array, charge controller, and inverter DC-side voltage/current monitoring.
- Motor & VFD Control Panels — DC bus and field voltage monitoring for industrial drives.
- Weighing & Batching via Tare — gross/net readout for scale and dosing applications using the built-in tare functions.
- Tank Volume & Level Readout — custom curve linearization of 4-20 mA level signals into volume for irregular tanks.
- Laboratory Power Supply Monitoring — precise DC voltage/current readout for test benches and calibration.
- Process Retransmission — analog output retransmission of DC readings to PLCs, chart recorders, or SCADA.
DC Voltage & Current Digital Panel Meter Frequently Asked Questions
Why does the meter sample internally at up to 60 conversions per second but only update the visible display 3.5 times per second?
This split is intentional — the fast internal A/D conversion rate (via Concurrent Slope conversion) is specifically what enables reliable peak and valley capture of brief signal excursions, while the much slower display update rate keeps the visible reading legible for a human operator; a display refreshing 60 times a second would be an unreadable blur, so the two rates serve genuinely different purposes.
What's the practical difference between the meter's CMR and NMR noise rejection specs?
CMR (common-mode rejection, 130 dB) describes rejection of noise or voltage appearing equally on both input leads relative to ground, while NMR (normal-mode rejection, 90 dB) describes rejection of noise appearing directly in series with the signal itself — both matter for real installations, but they protect against different physical noise-coupling paths, and an installation with strong ground-referenced noise benefits primarily from CMR while series-injected line-frequency noise is addressed by NMR.
Why does maximum applied voltage differ across ranges (600 Vac on some, only 125 Vac on others)?
The higher 600 Vac rating specifically applies to the 20V, 200V, and 300V ranges, which are documented as designed with input protection sized for that higher overvoltage tolerance; the lower-voltage millivolt and current ranges use different internal protection circuitry appropriate to their much smaller nominal signal levels, so the 125 Vac rating on those ranges reflects a genuinely different protection design, not a uniform blanket spec across the whole meter.
Why is overcurrent protection expressed as a multiplier (25x, 8x, 2.5x, 1x) that gets smaller on higher current ranges?
These multipliers describe how much above the range's own full-scale current the input protection can tolerate before damage — the lower-current ranges (2 mA, 20 mA) have proportionally more protection headroom (25x, 8x) since an accidental overcurrent event relative to their small full-scale rating is a smaller absolute current, while the 5A range's 1x rating reflects that its full-scale current is already substantial, leaving little additional margin before the protection circuitry's own limits are reached.
Does the adaptive moving average filter's "briefly switching to the shortest time constant" behavior risk missing a genuine transient in favor of following noise?
The documented design specifically distinguishes this from simple noise-following — the filter switches to its shortest available time constant specifically when a significant change in signal level occurs, which is intended to track genuine step changes quickly, then reverts to the selected longer time constant for steady-state noise smoothing; the Auto setting further refines this by basing the time constant selection on the actual signal noise characteristics observed.
Can auto-tare and manual tare both be used on the same meter, or is it one or the other?
Both mechanisms are documented as available on the same meter — auto-tare (grounding an input line via external pushbutton to capture the current reading as an offset) and manual tare (entering a known tare value directly) serve different practical situations, such as zeroing out an empty container's weight on the spot (auto-tare) versus entering a rail car's stated empty weight from a placard (manual tare), and an installation could use either method as the situation calls for.
What kinds of functions can the 14 available meter commands assigned to the two rear panel control inputs actually perform?
While the specific list of all 14 commands is detailed in the meter's user manual, the two control inputs are documented as accepting either CMOS/TTL logic levels or simple dry contacts, and are used to remotely trigger meter behaviors (such as tare, peak/valley reset, or display mode changes) without needing to physically access the front panel — useful when the meter is installed somewhere not easily reachable during normal operation.
Does the Extended board's "rate derived from successive readings" feature need the input signal itself to be linear?
No — since rate is calculated by comparing already-linearized, already-scaled readings against each other over time, the raw input signal feeding the meter can be nonlinear; the custom curve linearization step (if used) corrects the raw signal into an accurate engineering-unit reading first, and the rate calculation then simply compares those corrected readings, so nonlinearity in the raw signal doesn't propagate into the rate calculation.
Is the built-in 10 milliohm shunt for the 5.000A range field-replaceable if higher current ranges are needed later?
The 5A range's built-in shunt is part of that specific signal conditioner board's design — for substantially higher current measurement needs, the documented general approach across the Laureate line is using an external shunt with a voltage-range board (such as the 200.00 mV range) rather than modifying the built-in 5A board's internal shunt, since calibration factors can be scaled via software to accommodate external shunts on the voltage ranges.
Do the 200.00 mV and 2.0000V ranges' 1 GΩ input impedance actually matter for a typical DC voltage measurement?
It matters most specifically for high-source-impedance signals — a very high input impedance like 1 GΩ ensures the meter draws negligible current from the source being measured, avoiding the "loading" effect where the measurement itself alters the voltage being read; for low-impedance sources this is less critical, but for delicate sensor outputs or high-impedance voltage dividers on the lowest two ranges, that 1 GΩ figure is what keeps the meter from meaningfully disturbing the circuit under test.
Current Shunt Selection & Kelvin Sensing Questions From the Field
At what shunt resistance value does a 4-wire Kelvin connection actually become necessary rather than just nice to have?
Documented guidance specifically identifies meaningful accuracy improvement from Kelvin sensing below roughly 10 mΩ, becoming essentially mandatory at 1 mΩ and below — above roughly 100 mΩ, standard 2-wire connections are documented as generally sufficient, since trace and contact resistance becomes negligible relative to the much higher shunt resistance itself at that point.
Why does a 4-wire Kelvin connection eliminate lead and contact resistance error when a simple 2-wire connection doesn't?
Documented explanation specifically describes the mechanism: with Kelvin sensing, dedicated sense traces tap voltage directly across the shunt element itself, and since the current flowing into those sense connections is negligible (typically nanoamps into a high-impedance amplifier input), the parasitic resistance in the sense leads themselves doesn't meaningfully affect the measured voltage — a 2-wire connection instead measures voltage across the same path that's also carrying the full load current, so any resistance in that shared path directly corrupts the reading.
What's a common target range for the full-scale voltage drop a shunt should produce, and why not simply use a much larger drop for a stronger signal?
Documented guidance commonly cites a target full-scale shunt voltage in the range of 25-100 mV as a practical starting point — a much larger voltage drop would provide a stronger signal, but it also means more power dissipated as heat (P = I²R) at the same current, directly working against the shunt's own accuracy and thermal stability, so shunt sizing is documented as a genuine tradeoff between signal strength and self-heating.
Does a shunt's low-side (ground-referenced) placement genuinely simplify measurement compared to high-side placement?
Yes — documented guidance specifically describes low-side sensing (shunt placed between load and ground) as safer and simpler to wire, since the sensed voltage stays close to ground potential, while high-side sensing (shunt placed between the supply and the load) allows full-path current sensing but often requires isolation or differential amplification to handle the common-mode voltage present at the sense points relative to ground.
Why can PCB copper trace resistance become a hidden accuracy problem even when using a nominally low-TCR precision shunt?
Documented analysis specifically flags this: PCB copper has a temperature coefficient of roughly 3900 ppm/°C, dramatically higher than a precision shunt's typical 50 ppm/°C or lower — if a 2-wire layout includes significant trace resistance in the measurement path, that trace resistance's much higher temperature coefficient can end up dominating the overall temperature behavior of the measurement, undermining the benefit of having selected a genuinely low-TCR shunt component in the first place.
Does routing the Kelvin sense connections at the wrong physical point on a shunt's pad layout actually matter, or is "close enough" acceptable?
It matters, and is documented as a specific, real troubleshooting issue — a common documented symptom is measurement drift with load current, traced specifically to sense traces connecting to the power pad at a point where load current still flows through them before reaching the shunt element itself; the fix is ensuring sense connections tap at the inner pad edge, electrically downstream of where the high current actually flows, not just anywhere near the shunt.
What margin above expected maximum current is generally recommended when selecting a shunt's current rating?
Documented general guidance recommends selecting a shunt rated with at least 25-50% margin above the maximum expected current — this margin accounts for real-world current spikes, measurement uncertainty, and thermal safety margin, rather than sizing a shunt to its documented rating with no headroom for the actual peak currents an installation might experience.
For steady-state AC power metering, is a shunt resistor still the preferred current-sensing method, or do other technologies do better?
Documented comparison specifically notes that for steady-state AC metering at 50/60 Hz, a current transformer (CT) is generally the better choice compared to alternatives like Rogowski coils, which are documented as having a genuine advantage specifically in high-frequency, high-peak-current transient capture rather than steady 50/60 Hz metering — meaning the "best" current-sensing technology genuinely depends on whether the application is steady-state power metering or transient/high-frequency capture.






















Slide the meter into a 45 x 92 mm 1/8 DIN panel cutout. Ensure that the provided gasket is in place between the front of the panel and the back of the meter bezel.
The meter is secured by two pawls, each held by a screw, as illustrated. Turning each screw counterclockwise extends the pawl outward from the case and behind the panel. Turning each screw clockwise further tightens it against the panel to secure the meter.