Understanding the Laureate™ 1/8 DIN Panel Meters for 6-Digit Analog Input Totalizer & Process
The Laureate™ 1/8 DIN Panel Meters is a six-digit display of rate or total at the push of a front panel key. A Laureate with the Standard counter main board and a VF voltage-to-frequency signal conditioner board can be scaled to display rate or totalized rate to six digits for 0-1 mA, 4-20 mA, or 0-10V analog process signals converted to a frequency of 10 kHz to 110 kHz. The display can be scaled to show flow rate in gallons/minute or liters/sec, volume in gallons or liters, or power consumption in kilowatts and total utilized energy in kilowatt-hours based on the transducer's output.
Square Root Extraction and Accuracy
Square root extraction is selectable and can be applied to rate or total, making the VF Laureate ideal for differential pressure flow meters with a squared output — totalized volume is based on the already-linearized rate. Accuracy is ±0.005% of span ±1 count, among the highest of any panel meter.
Signal Input Characteristics
Input resistance differs by signal type: 50Ω at 4-20 mA, 1.00 kΩ at 0-1 mA, and 1.01 MΩ at 0-10V. Span tempco is ±0.003% of reading/°C, and zero tempco is ±0.003% of full scale/°C.
Principles of V-to-F Operation
The V-to-F signal conditioner converts the full-scale analog signal to a frequency of 10 kHz to 110 kHz, determined by measuring period over a selectable gate time (10 ms to 200 s) and taking the inverse. Selecting a short gate time provides much higher update rates than conventional counting-type frequency meters — at the lowest 10 kHz frequency and minimum 10 ms gate time, the meter achieves 25 updates per second. Totals are calculated as the product of rate and time in seconds, regardless of the selected gate time, and are stored in non-volatile memory in case of power loss.
Extended DPM Capabilities
- Batch Control Based on Linearized Total — totalizes linearized flow from an analog rate signal, counting up to a preset or down to zero for batch control; requires the dual-relay board, with one relay dedicated to ON/OFF batch control and the other available for rate/total alarm or slow-down near setpoint.
- Custom Curve Linearization — up to 180 data points linearize analog inputs, such as reading tank volume from an irregularly shaped vessel based on level or pressure; linearized readings can also be totalized.
- Time Based on Rate — displays a time inversely proportional to measured rate, such as conveyor time through an oven; as conveyor speed increases, displayed baking time decreases, based on time = distance/speed.
High Resolution Display
Rate or total may be scaled to ±999,999. The two least-significant digits may be set to display zero with rounding, or remain active digits. Noise in rate readings can be reduced with a longer gate time, and an adaptive digital filter reduces noise-driven variation while responding rapidly to genuine signal changes.
Factory-Calibrated Accuracy
All signal conditioner board ranges are factory-calibrated, with calibration factors stored in EEPROM that can be scaled via software to accommodate external shunts, enabling field replacement of the signal conditioner board without recalibrating the meter. Factory recalibration is recommended annually.
Where 6-Digit Analog Totalizer Panel Meters Are Used
- Differential Pressure Flow Metering — direct readout of flow or volume from orifice-plate or venturi DP transducers, with built-in square root extraction.
- Batch Filling & Dosing — up/down batch control driven directly by a 4-20 mA or 0-10V analog flow signal, without needing a pulse-output meter.
- Tank Gauging & Inventory — accurate volume readout from irregularly shaped tanks via level or pressure transmitters and custom curve linearization.
- Oven, Dryer & Conveyor Process Timing — process time computed directly from a rate signal, without a separate PLC calculation.
- Energy & Utility Metering — power and cumulative energy totalization from watt transducer outputs.
- Retrofit Flow Totalization — adding accurate rate/total display to existing analog-output flow transmitters without replacing the transmitter itself.
- Water & Wastewater Treatment — flow and volume totalization from DP, ultrasonic, or other analog-output flow instrumentation.
6-Digit Analog Totalizer Panel Meter Frequently Asked Questions
Why does totalizing accuracy not depend on which gate time I select for the rate measurement?
This is a documented, deliberate design characteristic — totals are calculated as the product of rate and time in seconds regardless of the selected gate time, meaning the totalizing math itself compensates for the gate time chosen, so an operator can select a gate time optimized for display responsiveness or noise reduction without worrying that it will bias the accumulated total.
Why does input resistance vary so much between the three signal types (50Ω, 1kΩ, 1.01MΩ)?
Each signal type has a fundamentally different electrical nature: 4-20 mA is a current signal, so a low input resistance (50Ω) is appropriate to develop a small, manageable voltage drop; 0-1 mA is also current-based but at a lower current level, needing higher resistance (1kΩ) to develop a comparable voltage; 0-10V is already a voltage signal, so a very high input resistance (1.01MΩ) is used specifically to avoid loading down the source.
What's the practical difference between span tempco and zero tempco for this meter?
Span tempco (±0.003% of reading/°C) describes how much the meter's overall calibrated scale factor drifts with temperature, an error that scales with the size of the actual reading — zero tempco (±0.003% of full scale/°C) describes how much the baseline zero-point itself shifts with temperature, a fixed error independent of the current reading's magnitude. Both contribute to overall accuracy, but they behave differently across the meter's range.
Can this meter apply square root extraction to the total as well as the rate, or only the rate?
Documented capability specifically states square root extraction can be applied to either rate or total — and total is specifically documented as being based on the already-linearized rate, meaning the square root correction happens before totalizing, so the accumulated total reflects genuinely linearized flow rather than a squared, uncorrected signal.
How does the "time based on rate" function actually compute process time from a speed signal?
It applies the mathematical relationship time = distance/speed — with a fixed, pre-configured distance (such as the length of an oven) and a live rate signal (such as conveyor speed from a tachometer), the meter continuously calculates and displays the resulting time, which decreases as the input rate signal increases and increases as it decreases.
Does the batch control mode require both relays on the dual-relay board, or can it work with a single relay?
Documented setup specifically requires the dual-relay output board for batch control, with one relay dedicated specifically to ON/OFF batch control — the second relay is available but not strictly required for basic batch control itself, since it's documented as being available for an additional function like slowing rate near setpoint or providing a separate alarm.
If I set the two least-significant digits to round to zero, does that affect the accuracy of the totalized value stored internally, or just what's displayed?
This is documented specifically as a display option — rounding the least-significant digits affects what's shown on the display for readability, and doesn't inherently change the meter's underlying accuracy or the value used internally for totalizing and analog output; it's a presentation choice rather than a measurement precision tradeoff.
Can the meter's totalizer continue accumulating correctly through a brief power interruption?
Yes — totals are documented as being stored in non-volatile memory specifically in case of power loss, meaning a brief interruption doesn't reset or lose the accumulated total; counting resumes from the last stored value once power is restored.
Does custom curve linearization for an irregular tank need to account for the specific pressure or level transmitter's own nonlinearity, or just the tank's shape?
The 180-point linearization is applied to the overall relationship between the transmitter's signal and the actual desired reading (such as volume), which inherently captures both the tank's shape and any nonlinearity contributed by the transmitter itself — since the calibration points are based on real measured data pairs, whatever combination of tank geometry and transmitter behavior produces the actual signal-to-volume relationship gets captured together.
Is the 25 updates/second maximum rate achievable at any input frequency, or only at the lowest end of the V-to-F range?
Documented specifically as achievable at the lowest frequency (10 kHz) combined with the minimum 10 ms gate time — since higher V-to-F output frequencies inherently provide more signal periods within the same gate time, the update rate relationship across the full 10 kHz to 110 kHz range isn't necessarily uniform, and the specific 25 updates/second figure is documented for that particular combination of conditions.
4-20mA Current Loop Wiring & Distance Questions From the Field
Why doesn't wire resistance corrupt a 4-20 mA signal the way it would a voltage signal over a long cable run?
Documented current loop principles specifically explain this: in a series circuit, current is constant throughout the loop regardless of wire resistance, so the receiving device measuring current sees the correct value as long as the transmitter has enough compliance voltage to push the required current through the total loop resistance — voltage signals, by contrast, are directly attenuated by wire resistance because the receiver is measuring voltage, which does divide across that resistance.
How do I calculate whether my power supply voltage is adequate for a specific 4-20 mA loop distance?
Documented calculation approach: sum all voltage drops around the loop at the maximum 20 mA signal current — the receiving device's input resistance, the wire resistance (both conductors, since current must return), and the transmitter's own minimum operating voltage — then confirm the power supply voltage exceeds that total sum, ideally with a volt or more of margin for future wiring changes or component drift.
Does wire temperature actually affect a current loop's maximum reliable distance?
Yes, and this is specifically documented and quantified — copper wire resistance increases with temperature (a documented example shows wire resistance increasing by roughly 16% between 20°C and 60°C), meaning a loop voltage budget calculated only at room temperature can leave insufficient margin at hot equipment shaft or outdoor installation temperatures; worst-case calculations should specifically use the highest expected operating temperature.
Why is 4 mA specifically used as the "zero" signal level instead of using 0 mA?
Documented rationale specifically ties this to fault detection and transmitter power: using a 4 mA baseline (rather than 0 mA) leaves a usable current margin below the live signal range that can indicate an open circuit or wiring fault, while also providing operating current to power loop-powered transmitter electronics — a 0-20 mA scheme would make a genuine 0% signal indistinguishable from a broken wire and would leave no baseline current to power the transmitter.
What does it mean if a receiving instrument reads slightly below 4 mA, such as 3.6 mA?
Documented troubleshooting guidance specifically identifies a reading below 4 mA (commonly around 3.6 mA) as a deliberate fault or "downscale burnout" indication from the transmitter itself, signaling a detected sensor failure (such as a broken thermocouple, open RTD, or plugged impulse line) — rather than treating this as random signal noise, it should be investigated as an intentional fault flag from the transmitter.
Can I measure loop current without breaking the circuit to install a meter in series?
Yes — documented troubleshooting practice specifically recommends a clamp-on milliamp meter (such as a Fluke 771 or 772), which clamps around a single loop conductor and measures the DC current flowing through it without interrupting the circuit — this is specifically documented as essential when troubleshooting a live process where breaking the loop would cause a process trip or false alarm.
Does exceeding a transmitter's rated maximum load resistance cause a gradual accuracy loss, or a hard failure?
Documented guidance specifically warns this causes signal dropout or nonlinearity, particularly at the upper end of the current range (near 20 mA) — rather than a gradual, proportional accuracy degradation, exceeding the rated load can produce a more abrupt failure mode where the transmitter simply can't develop enough voltage to push the required current through the excessive total loop resistance.
If I detect AC voltage riding on top of my 4-20 mA DC signal, what does that typically indicate?
Documented troubleshooting guidance specifically flags AC voltage noise exceeding roughly 100 mV superimposed on the DC current loop signal as an indication of inadequate shielding or grounding — using a high-impedance multimeter set to measure AC voltage across the loop is the documented method for detecting and quantifying this specific noise-coupling problem.






















Slide the meter into a 45 x 92 mm 1/8 DIN panel cutout. Ensure that the provided gasket is in place between the front of the panel and the back of the meter bezel.
The meter is secured by two pawls, each held by a screw, as illustrated. Turning each screw counterclockwise extends the pawl outward from the case and behind the panel. Turning each screw clockwise further tightens it against the panel to secure the meter. 





