Laurel Electronics
Call (714) 434 6131 for Product Assistance
Panel Meters - Counters - Timers - Transmitters, 4-20 mA & Modbus - Ethernet - USB - RS485 - RS232

Laureate™ AC Power Factor Meter & AC Phase Angle Meter

AC phase angle & power factor meter

Features

  • Programmable to read phase angle or power factor with two waveshapes of identical period
  • Phase angle resolution of 1°, 0.1° or 0.01° and accuracy of 0.03° at AC line frequency
  • Power factor from 1.000 to 0.000 with sinusoidal signals
  • Accepts AC signals from 1 Hz to 10 kHz at voltages up to 250 Vrms
  • Universal 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac powerr
  • Transducer excitation output (isolated)
  • Wide choice of options:
    - 2 or 4 relays, mechanical or solid state (isolated)
    - 1 or 2 analog outputs (isolated)
    - Communications: Ethernet, WiFi, USB, RS232, RS485 (isolated)
  • -X extended temperature option from -40°C to 70°C
AC phase angle & power factor meter

Features

  • Programmable to read phase angle or power factor with two waveshapes of identical period
  • Phase angle resolution of 1°, 0.1° or 0.01° and accuracy of 0.03° at AC line frequency
  • Power factor from 1.000 to 0.000 with sinusoidal signals
  • Accepts AC signals from 1 Hz to 10 kHz at voltages up to 250 Vrms
  • Universal 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac powerr
  • Transducer excitation output (isolated)
  • Wide choice of options:
    - 2 or 4 relays, mechanical or solid state (isolated)
    - 1 or 2 analog outputs (isolated)
    - Serial data I/O: Ethernet, USB, RS485, RS232 (isolated)
Description

AC Phase Angle Measurement

Phase angle measurement by digital phase meter
  • Phase angle in degrees indicates the phase lead or lag between two periodic signals of the same period, as determined from their zero crossings. These two signals will typically be the voltage and current applied to a load. As illustrated, the phase angle θ in degrees is +360*P1/P.
  • The Laureate™ Phase Angle & Power Factor Meter computes phase angle θ by timing zero crossings of two signals applied to Channels A and B. The phase angle range is selectable as 0° to 360° or -180° to +180°. Resolution is selectable as 1°, 0.1° or 0.01°. Typical accuracy is 0.01% from 1 Hz to 100 Hz, 0.1% at 1 kHz, and 1% at 10 kHz.

AC Power Factor Measurement

  • The power factor of an AC power system is the ratio of real power in watts (W) divided by apparent power in volt-amperes (VA). For sinusoidal signals differing by a phase angle θ, power factor is cos(θ).
  • The Laureate™ Phase Angle & Power Factor Meter computes power factor as cos(θ) from phase angle θ. Power factor readings can range from 1.000 to 0.000 with three decimal places and an accuracy of 0.1% for sinusoidal signals at 50/60 Hz power line frequency. While power factor is always positive, the meter artificially assigns a minus sign to power factor for negative phase angles, and it sets power factor to 0 for phase angles greater than 90°.

Designed for flexibility

The Laureate Phase Angle & Power Factor Meter utilizes the Laureate Extended counter main board and the FR dual-channel signal conditioner board, which accepts AC signals from 12 mV p-p to 250 Vrms. Optional plug-in boards for communications and control include Ethernet, WiFi and serial communication boards, dual or quad relay boards, and an isolated analog output board. Laureates may be powered from 85-264 Vac or optionally from 12-32 Vac or 10-48 Vdc. The display is available with red or green LEDs. The 1/8 DIN case meets NEMA 4X (IP65) specifications from the front when panel mounted. Any setup functions and front panel keys can be locked out for simplified usage and security. A built-in isolated 5, 10, or 24 Vdc excitation supply can power transducers and eliminate the need for an external power supply. All power and signal connections are via UL / VDE / CSA rated screw clamp plugs.

Specifications

AC Power Factor Meter & AC Phase Angle Meter

Phase Angle Mode
Item Displayed Phase angle difference between two waves of same period
Display Units 1°, 0.1°, 0.01°
Frequency Range 0.005 Hz to 10 kHz
Resolution 0.01°, 1 Hz to 100 Hz; 0.1° at 1 kHz; 1° at 10 kHz
Accuracy 0.05° at 50 or 60 Hz
Maximum Timing Interval 200 sec
Power Factor Mode
Item Displayed Power factor between two sine waves of same period
Display Units 1.000 to 0.000
Polarity Negative sign indicates negative phase angle
Frequency Range 0.005 Hz to 10 kHz
Accuracy 0.1% at power line frequencies
Update Rate
Timing Interval Gate time + 30 ms+ 0-2 signal periods
Gate Time Selectable 10 ms to 199.99 s
Time Before Zero Out Selectable 10 ms to 199.99 s (to indicate loss of signal)
Display
Readout 6 LED digits, 7-segment, 14.2 mm (.56"), red or green.
Range -999999 to +999999
Indicators Four LED lamps
Inputs
Signal ranges Nine AC signal ranges from 12 mVp-p to 250 Vac
Signal ground Common ground for channels A & B
Noise filter 1 MHz, 30 kHz, 250 Hz (jumper selectable) + digital filter
Power Supply Boards (one required)
Voltage, standard 85-264 Vac or 90-300 Vdc
Voltage, optional 12-32 Vac or 10-48 Vdc
Frequency DC or 47-63 Hz
Power  consumption (typical, base meter) 1.2W @ 120 Vac, 1.5W @ 240 Vac, 1.3W @ 10 Vdc, 1.4W @ 20 Vdc, 1.55W @ 30 Vdc, 1.8W @ 40 Vdc, 2.15W @ 48 Vdc
Power Isolation 250V rms working, 2.3 kV rms per 1 min test
Excitation Output (standard)
5 Vdc 5 Vdc ± 5%, 100 mA
10 Vdc 10 Vdc ± 5%, 120 mA
24 Vdc 24 Vdc ± 5%, 50 mA
Output Isolation 50 Vdc to meter ground
Analog Output Boards (one optional)
Output levels 4-20 mA, 0-20 mA, 0-10V, -10 to +10V (jumper selectable)
4-20 mA, 0-20 mA, 0-10V (dual-output option)
Current compliance 2 mA at 10V ( > 5 kΩ load)
Voltage compliance 12V at 20 mA (< 600 Ω load)
Scaling Zero and full scale adjustable from -99999 to +99999
Resolution 16 bits (0.0015% of full scale)
Isolation 250V rms working, 2.3 kV rms per 1 min test
Relay Output Boards (one optional)
Dual magnetic relays 2 Form C, 8A at 250 Vac or 24 Vdc, 0.3A at 250 Vdc, resistive load
Quad magnetic relays 4 Form A (NO), 8A at 250 Vac or 24 Vdc, 0.3A at 250 Vdc, resistive load
Dual solid state relays 2 Form A (NO), 120 mA at 140 Vac or 180 Vdc, resistive load
Quad solid state relays 4 Form A (NO), 120 mA at 140 Vac or 180 Vdc, resistive load
Relay commons Isolated commons for dual relays or each pair of quad relays
Relay isolation 250V rms working, 2.3 kV rms per 1 minute test
Relay latching modes Latching or non-latching
Relay active modes Active on or off, active high or low
Hysteresis modes QA passband mode, split hysteresis, span hysteresis
Communication Boards (one optional)
Board selections RS232RS485 with dual RJ11 connectors, RS485 with dual RJ45 connectors, USB, Ethernet, USB-to-RS485 gatewayEthernet-to-RS485 gateway, WiFi with built-in antenna plus USB & RS485, WiFi with external antenna plus USB & RS485
Protocols Laurel Custom ASCII (serial), Modbus RTU (serial), Modbus TCP (Ethernet or WiFi)
Digital addresses 247 (Modbus), 31 (Laurel ASCII),
Isolation 250V rms working, 2.3 kV rms per 1 min test
Environmental
Operating temperature 0°C to 55°C standard, -40°C to 70°C with -X option
Storage temperature. -40°C to 85°C
Relative humidity 95% at 40°C, non-condensing
Protection NEMA-4X (IP-65) when panel mounted
Electrical Connections
Signal connections to Laurel pulse input batch controller
Applications
Optimizing Meter Inputs for Phase Angle & Power Factor Measurement

Phase angle and power factor measurement with the Laureate™ Phase Angle & Power Factor Meter require that two signals of identical periods be applied to Channels A and B. For best accuracy, both signals should have the same amplitude, the signal amplitude should be larger than 1V, and the trigger level should be minimized by selecting the ±12 mV jumper position.

The meter times zero crossings to 0.1 µs resolution over a user-selectable gate time from 10 ms to 199.99 s. By selecting the minimum gate time of 10 ms, the meter update rate will be approximately 20/s for 50/60 Hz AC line frequency. Improved accuracy will be obtained by making the gate time long enough so that multiple cycles are averaged.

Both signals applied to the meter should be mutually isolated by transformer coupling, so that they can then share the same ground in the meter. The current signal is typically obtained from a current transformer (CT). This should ideally be a CT with a voltage output or a current output in the mA range, which can then be converted to a voltage higher than 1V across an external dropping resistor without excessive heat generation.

Using Laureate Meters and Counters to Synchronize Motor Generators
Using Laurel Meters and Counters to Synchronize Two Motor Generators

Synchronization of two motor generators requires that the two frequencies be identical, that the lines be in phase, and that the line voltages be close to each other. In this illustration, a single Laureate dual channel counter measures both frequencies to six-figure accuracy in a few line cycles. Another Laureate dual channel counter measures phase angle to 0.1° resolution. Two Laureate AC RMS Voltmeters, which offer ranges of 200.00 V and 600.0 V, are used to display the two RMS voltages to 0.1% accuracy.

For applications assistance, phone 714-434-6131 ext. 104, or email support@laurels.com
Ordering Guide
Laureate™ AC Phase Angle & Power Factor Meter
Click on the radio buttons to build a model number with pricing as shown below. Prices are in US dollars and do not include shipping or duty charges (export sales). Please see our explanations and limitations applicable to pricing and online orders. Prices shown are in US Dollars and are Laurel's manufacturer's suggested retail price (MSRP) in the USA. Orders are processed manually, not directly by our shopping cart system. You don't have to supply credit card information when placing an online order.

North American Orders. Laurel does not sell factory-direct in the USA or Canada. Online sales orders are filled through distribution. During the ordering process, you will have the chance to select an authorized Laurel distributor, or you can ask Laurel to refer you to a distributor. The distributor will then contact you to quote shipping, tax and duty (where applicable), and arrange for payment.

International Orders. If your ship-to address indicates that you are outside of the USA or Canada and Laurel has a distributor in your country, we will forward your order to that distributor for follow-up. If Laurel does not have a distributor in your country, we will email you an order acknowledgment and a pro forma invoice which states the product price, shipping charges, and wire transfer information, which includes a $25 bank wire transfer fee.

Questions about your order? Please email your distributor or sales@laurels.com
 
Quantity
Main Board L   Laureate Series multifunction counter / timer / rate meter main board $169
Display Color 7   Extended meter, green LEDs $3741
8   Extended meter, red LEDs $41
Note 1: Use of the Extended Main Board also makes this counter suitable for A-B time interval, stopwatch, frequency, rate, period, square root of rate, up or down total, arithmetic functions, simultaneous rate and total, duty cycle, batching, and custom curve linearization.
Note 2: The microcomputer firmware version has to be CTR2-32, not CTR2-33. If the meter is to be used for power factor, please so indicate at the time order.
Power 0  Isolated 85-264 Vac or 90-300 Vdc $75
1  Isolated 12-32 Vac or 10-48 Vdc $115
Relay
Output
(isolated)
0  None $0
1  Two 8A Form C contact relays $101
2  Two 120 mA solid state relays $70
3  Four 8A Form A contact relays $128
4   Four 120 mA solid state relays $96
Analog
Output
0  None $0
1  Single Isolated 4-20 mA, 0-20 mA, 0-10 V, -10 to +10V $115
2  Dual isolated 4-20 mA, 0-20 mA, 0-10V $172
Data
Interface
(isolated)
0  None $0
1  RS232 (L232) $81
2  RS485 (L485, dual RJ11 connectors) $109
4  RS485 (LMOD, dual RJ45 connectors, not for new design) $135
5  USB (LUSB) $81
6  USB-to-RS485 gateway (LUSB485) $135
7  Ethernet (LNET) $237
8  Ethernet-to-RS485 gateway (LNET485) $259
A  Ethernet + USB (LNET1) $182
B  Ethernet + RS485 (LNET1485) $204
C  WiFi + USB internal antenna (LWIFI) $171
D  WiFi + USB, external antenna (LWIFIX) $193
E  WiFi + USB + RS485, internal antenna (LWIFI485) $204
F  WiFi + USB + RS485, external antenna (LWIFIX485) $226
Input
Type
FR  Scalable to 999,999 $81
Add-on
Options
CBL01  RS232 cable, RJ11 to DB9, 7 ft. Connects RS232 ports of meter and PC. $23
CBL02  USB to RS232 adapter cable. Combination of CBL02 and CBL01 connects meter RS232 port to PC USB port. Combination of CBL02 and CBL04 connects transmitter RS232 terminals to PC USB port. $47
CBL03-1  6-wire data cable, RJ11 to RJ11, 1 ft. Used to daisy chain meters via RS485. $10
CBL03-7  6-wire data cable, RJ11 to RJ11, 7 ft. Used to daisy chain meters via RS485. $10
CBL05  USB cable, A-B. Connects USB ports of meter and PC. $19
CBL06  USB to RS485 adapter cable, half duplex, RJ11 to USB. Connects meter RS485 port to PC USB port. $47
CASE1  Benchtop Laboratory Case for One 1/8 DIN Meter $140
CASE2  Benchtop Laboratory Case for Two 1/8 DIN Meters $140
NL  Meter Lens with Button Pads but no Laurels Logo $5
BL  Meter Lens without Button Pads or Laurels Logo $5
IPC  Splash-proof Cover $48
BOX1  NEMA-4 Enclosure $169
BOX2  NEMA-4 Enclosure plus IPC $218
 
Configured model number L70000FR
Configured price per model $366
Quantity 1
Extended price $366
Legal Information
seal-20th24    
facebook   G+   twitter   linkedin
© 1990-2024 Laurel Electronics
feedback