LTE DIN Rail Digital Transmitters with Ethernet Communication and Analog Outputs for Analog Input Totalizer Applications

LTE DIN Rail Digital Transmitters with Ethernet Communication and Analog Outputs for Analog Input Totalizer Applications

Price: $558.00
  • P/NLTE60VF1
- +

Features

  • High accuracy: ±0.005% of span ±1 count
  • 0-1 mA, 4-20 mA or 0-10V process signal input, (isolated)
  • Converts signal input to a scaled rate or totalized rate
  • Selectable square root for differential flow
  • Output accuracy maintained for narrow or wide spans
  • Extracts square root from differential pressure flow transducers & flow totalizer
  • All input ranges are user selectable and factory calibrated
  • 4-20 mA, 0-20 mA, 0-10V or -10V to +10V transmitter output, (isolated)
  • Analog output resolution 0.0015%  of span, accuracy ±0.02%  of span
  • Ethernet data I/O, Modbus TCP
  • Dual 120 mA solid state relays for alarm or control (isolated)
  • 5V, 10V, 12V, or 24V dc transducer excitation output (isolated)
  • Power 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac (isolated)
  • DIN rail mount housing, 22.5 mm wide, detachable screw-clamp connectors
  • Operating temperature from -40°C to 70°C (-40°F to 158°F)
  • Optional - Extended allows up to 180 data points for custom curve linearization of nonlinear inputs, batch operation, 1/rate (time)

The Laureate™ LTE Series DIN rail analog transmitter with ethernet communication and analog outputs for versatile connectivity.

The digitally programmable transmitter features two relays for alarm or control. The series offers exceptional accuracy with Input frequencies from 0.005 Hz to 1 MHz. The LTE Series transmitters offer the same high performance, signal conditioning, and programmable features as Laureate digital panel meters, counters, and timers.

The Laureate 4-20 mA, 0-20 mA, 0-10V or -10V to +10V and ethernet output transmitter for analog input totalizer accepts 0-1 mA, 4-20 mA or 0-10V signals from flow meters and other transducers, such as watt meters, to track rate or totalized rate.

  • With a Standard main board, the transmitter output can track rate (such as gallons per minute or watts) or totalized rate (such as gallons or kilowatt hours) whether the transducer output is linear or requires square root extraction (differential pressure flow transducers).
  • With an Extended main board, the transmitter can also perform custom curve linearization (provided by a curvilinear spline fit with up to 180 data points), display 1/ rate (such as the time it takes a conveyor to pass through an oven), and perform batch control for repetitive fill operations. Such applications typically make use of optional dual solid state relays, which are available as options. External reset of totals is provided by a special connector.

A signal conditioner board converts the full-scale 0-1 mA, 4-20 mA or 0-10 V analog signal to a frequency of 10 kHz to 110 kHz. This frequency is determined by measuring period over a selected gate time (from 10 ms to 200 s) and taking the inverse of period. At the lowest frequency of 10 kHz and the minimum gate time of 10 ms, the transmitter is capable of 25 updates per second. Scaling is done mathematically. Totals are calculated as the product of rate and time in seconds regardless of the selected gate time. Totals are stored in nonvolatile memory in case of power loss.

Exceptional Accuracy and Stability. Laureate transmitters determine frequency by taking the inverse of period as measured with a calibrated quartz crystal time base. This results in extremely accurate and stable 6-digit internal readings (±999,999 counts), which are then processed in software. The analog output is generated by an ultra-linear 16-bit (65,536 step) digital-to-analog converter (DAC) for 0.02% output accuracy. The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control.

The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control.

All signal conditioner board ranges are factory-calibrated, with calibration factors for each range securely stored in an onboard EEPROM. These factors can be scaled via software to accommodate external shunts, enabling field replacement of signal conditioner boards without necessitating recalibration of the associated transmitter. For optimal accuracy, factory recalibration is recommended annually. All Laurel Electronics instruments undergo factory calibration using the industry-leading Fluke calibrators, which are recalibrated yearly and certified traceable to national standards, ensuring the highest level of precision and reliability.

Laureate Transmitters are easily programmed with Laurel’s free Instrument Setup Software, downloadable from our website and compatible with Windows PCs, requiring a data interface board for setup.

Standard Features of Laureate LTE Transmitters Include:

  • Ethernet I/O, (isolated). The supported protocols are Modbus RTU and ASCII, which are tunneled via Modbus TCP. Note that RS232 or RS485 data I/O is provided by Laurel's LT Series transmitters.
  • 4-20 mA, 0-20 mA or 0-10V analog transmitter output, (isolated), jumper-selectable and user scalable. All selections provide 16-bit (0.0015 ) resolution of output span and 0.02%  output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.
  • Dual solid state relays, (isolated). Available for local alarm or control. Rated 120 mA at 130 Vac or 180 Vdc.
  • Selectable transducer excitation output, (isolated), user selectable 5V@100 mA, 10V@120 mA, 12V@100 mA or 24V@50 mA.
  • Power 85-264 Vac, (isolated), low-voltage 10-48 Vdc or 12-32 Vac power is optional.

Digital signal filtering modes can be selected to ensure stable readings in electrically noisy environments.

  • An unfiltered selection provides true peak and valley readings and aids in control applications.
  • A batch average filter selection averages each 16 conversions.
  • An adaptive moving average filter selection provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, the filter adapts by briefly switching to the shortest time to follow the change, then reverts back to its selected time constant. An Auto setting selects the time constant selection based on signal noise.

Peak and valley values are automatically captured. These may be displayed via Laurel's free Instrument Setup Software,  which runs on a PC under MS Windows or can be transmitted as serial data.

Two control inputs (CMOS/TTL levels, logic 0 = tied to digital ground, logic 1 = open) or dry contacts that can be set to control / activate 14 transmitter commands.

An (isolated) 5, 10, 12, or 24 Vdc excitation output is standard to power transducers or two-wire transmitters. Ratiometric operation, which automatically compensates for changes in the applied excitation, is jumper selectable for applications, such as bridges, where the signal to be measured is proportional to the excitation level.

Removable screw terminal connections of Laurel transmitters

LTE series DIN rail transmitters & signal conditioners can be interfaced to a wide range of sensors and transducers using one of seven available plug-in signal conditioner boards. The transmitters duplicate the high performance (high accuracy, high read rate) and extensive programmable features of Laureate 1/8 DIN digital panel meters, counters and timers. They utilize the same signal conditioners boards, much of the same firmware, and Laurel's free Windows-based Instrument Setup Software. They come in a compact DIN rail mount package with detachable screw-clamp connectors for easy wiring.

The LTE series Transmitters accessible from this page include a 4-20 mA, 0-20 mA, 0-10V, or -10V to +10V analog output (isolated, user selectable), an ethernet serial data interface (isolated, user selectable), and dual 120 mA solid state AC/DC relays (isolated). An (isolated) 5, 10, 12, or 24 Vdc transducer excitation output is included with all models other than those with a temperature or AC RMS signal conditioner.

Connecting Laureate LTE Transmitters to a Local Area Network (LAN)

Laurel LTE series Ethernet transmitters can connect directly to a LAN via an Ethernet cable. Up to 30 Laureate LT Transmitters and/or Digital Panel Meters can be configured for RS485 and daisy-chained to an LT Transmitter for seamless LAN integration. Setup for both configurations is streamlined using Laurel’s free Instrument Setup Software, which simplifies node discovery and transmitter configuration. 

Flexible Communication Options for LTE Transmitters

Laureate Transmitters can be equipped with Laurel communication boards to support various interfaces and protocols. These include serial interfaces with ASCII or Modbus RTU protocols, and Ethernet interfaces with web access, ASCII, or Modbus TCP/IP protocols, ensuring versatile connectivity for your commercial applications.

Laureate Ethernet network by Laurel Electronics

Laureate™ Ethernet & 4-20 mA Transmitter & Totalizer for 0-1 mA, 4-20 mA or 0-10V Process Signals

Analog Input 0-1 mA 4-20 mA 0-10 V
Input resistance 1.00 kΩ 50 Ω 1.01 MΩ
Max current or voltage 35 mA 70 mA 600 V
Input Resolution 6 digits
Span Tempco ±0.003% reading/°C
Zero Tempco ±0.003% FS/°C
Accuracy at 25°C ±0.01% FS ± 1 count
Read Rate 25/sec (typical)
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.
Analog Output (standard)
Output Levels 4-20 mA and 0-10 Vdc (selectable)
Compliance, 4-20 mA 10V (0-500Ω load)
Compliance, 0-10V 2 mA (5 kΩ load)
Output Resolution 16 bits (65,536 steps)
Output Accuracy 0.02% of output span
Output Update Rate 25/sec
Output Isolation 250V rms working, 2.3 kV rms per 1 minute test
Ethernet Data I/O (standard)
Type 10/100 Base-T Ethernet per IEEE 802.3
Data Rates 300, 600, 1200, 2400, 4800, 9600, 19200 baud
Output Isolation 250V rms working, 2.3 kV rms per 1 min test
Serial Protocols Modbus TCP, Modbus RTU, Modbus ASCII, Laurel ASCII
Modbus Compliance Modbus over Serial Line Specification V1.0 (2002)
Digital Addresses 247 for Modbus, 31 for Laurel ASCII
Excitation Output (standard)
5 Vdc 5 Vdc ± 5%, 100 mA (jumper selectable)
10 Vdc 10 Vdc ± 5%, 120 mA (jumper selectable)
12 Vdc 12 Vdc ± 5%, 100 mA (jumper selectable)
24 Vdc 24 Vdc ± 5%, 50 mA (jumper selectable)
Output Isolation 50 Vdc from signal ground
Dual Relay Output (standard)
Relay Type Two solid state relays, SPST, normally open, Form A
Load Rating 120 mA at 140 Vac or 180 Vdc
Power Input
Standard Power 85-264 Vac or 90-300 Vdc
Low Power Option 10-48 Vdc or 12-32 Vac
Power Frequency DC or 47-63 Hz
Power Isolation 250V rms working, 2.3 kV rms per 1 min test
Power Consumption 2W typical, 3W with max excitation output
Environmental
Operating Temperature -40°C to 70°C (-40°F to 158°F)
Storage Temperature -40°C to 85°C (-40°F to 185°F)
Relative Humidity 95% at 40°C, non-condensing
Cooling Required Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan.
Mechanical
Enclosure Rugged black polycarbonate housing material
Mounting 35 mm rail per DIN EN 50022
Dimensions 129 x 104 x 22.5 mm case
Connectors Detachable screw clamp connectors meet VDE / IEC / UL / CSA standards. RJ45 jack for Ethernet
Tightening Torque Screw terminal connectors: 5 lb-in (0.56 Nm)
Weight Complete transmitter: 183 g (6.5 oz)
Replacement Case Screws
Size 6
Thread Pitch 6-19
Length 1/2"
Head Style Pan Head
Drive Style Phillips
Head Diameter 0.256-0.270
Head Height 0.087-0.097
Full/Partial Thread Full
Drive Size 2
Material Steel
Finished Black Oxide
General
Programming Utilize Laurel's free Instrument Setup Software, which runs on a PC under MS Windows. 
Security Lockout options available using Laurel's free Instrument Setup Software.
Warranty 3 years parts & labor
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.

Transmitter Pinout

LTE Ethernet Transmitter Pinout

 

Free Instrument Setup Software for Series 2 Laureates

Digital Panel Meter Laurel Electronics Digital Transmitters
1/8 DIN Digital Panel Meters DIN Rail Transmitters

Free Downloadable Windows-based Instrument Setup (IS) software (Data Interface Board Required) for use with our programmable Digital Panel Meters, Scale Meters, Counters, Timers, Remote Displays, and Transmitters, are an easy method to set up Laureate 1/8 DIN digital panel meters, counters, timers, remote displays, and DIN-rail transmitters, as explained in the Instrument Setup Software Manual. Laureate 1/8 DIN instruments can also be set up from the front panel, as explained in their respective Owners Manuals. Instrument Setup software is of benefit whether or not the PC is connected to the instrument.

  • When the PC is connected to the instrument, Instrument Setup software can retrieve the setup file from the instrument or open a default setup file or previously saved setup file from disk View Setup, then provides graphical user interface (GUI) screens with pull-down menus applicable to input, display, scaling, filtering, alarms, communications, analog output, and front panel lockouts. Fields that are not applicable to the instrument as configured are either left out or grayed out. Clicking on any item will bring up a detailed Help screen for that item. After editing, the setup file can be downloaded, uploaded to the instrument, or saved to a disk. The same setup file can then be downloaded into multiple instruments.
  • When the PC is not connected to the instrument, the above GUI screens can be used to set up a virtual instrument. The setup file can then be saved to disk. Switching toView Menu then brings up a screen with the required front panel programming steps. This view can be printed out for use at the instrument site and to serve as a hard copy record.

    Download Free Instrument Setup Software


Installation

Set User Account Control (UAC) of MS Windows to "Never notifiy me" so that Instrument Setup Software can create directories. The UAC change screen can be reached as follows:

  • Under Windows 7, click on the Windows Start button in the lower left of the desktop and enter "UAC" in the search field.
  • Under Windows 8, navigate to Control Panel, then to the "User Accounts and Family Safety" section, and click on "Change User Account Control Settings."
  • Under Windows 10, click on the Windows Start button in the lower left of the desktop, then on "Settings", and enter "UAC" in the search field.
  • Reboot your computer for the changed UAC setting to take effect.
Meter board with USB Type-B connector

RJ11-to-DB9 cable with rear view of DB9 connector to PC

Laurel USB cable, P/N CBL05

RS232 cable, meter to PC, P/N CBL01

Laureate 1/8 DIN Laureate instruments must be equipped with a serial communications board and be connected to the computer via a serial communications cable. The connection can be via RS232, RS485, USB or Ethernet. Following setup, the serial communications board may be removed from the instrument if desired. The wiring of the RS232 cable is illustrated above with end views of the two connectors.

Laureate LT Series transmitters come standard with a 3-wire serial interface, which can be jumpered for RS232 or RS485.
Laureate LTE Series transmitters come standard with an Ethernet interface.

Meter Setup Screens

Click on any of the reduced screens below for a full-size screen view, then click on the Back button of your browser to return to this page. The screens examples below are for a fully-loaded Series 2 Digital Panel Meter (DPM), which is connected to the PC via RS232. If the meter is a Series 1 meter (pre-2007), this is sensed by the software, and somewhat different screens are brought up. Please see Series 1 setup screens.

Laurel Dual Channel Pulse Input Rate Meter
Welcome Screen
From the computer desktop, click on Start > Programs > IS2 > IS2. Or click on the IS icon on your desktop. This splash screen will be displayed for three seconds. The software revision number is in the lower right.
more
Setup Screen 02s for Digital Panel Meters and Digital Transmitters
Communications Selection Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 3 for Digital Panel Meters and Digital Transmitters
Establish Communications Screen
If you selected RS-232, you will be asked to specify the PC Com Port and Baud Rate, which should match the jumper setup of the instrument. Click on Establish. With the right settings, the Communications Established field will light up in green, and the Meter Type will be recognized. If so, click onMain Menu.
more
Setup Screen 4 for Digital Panel Meters and Digital Transmitters
Main Menu Screen
Click on File > Default Setup to retrieve the default setup file from disk for your type of meter. Click on File > Open Setupto retrieve a previously saved setup file from disk or on File > Save Setup to save your edited setup file to disk. Click onDPM > Get Setup to retrieve the setup file from your meter or on DPM > Put Setup to download your edited setup file into the meter.
more
Setup Screen 5 for Digital Panel Meters and Digital Transmitters
DPM Input + Display Setup Screen
From the Main Menu, click on View > Setup, then on theInput+Display tab. You can now specify the meter hardware, signal type, display mode, and functions of control inputs A and B. Clicking on any item brings up a pull-down menu with the available choices.
more
Setup Screen 6 for Digital Panel Meters and Digital Transmitters
DPM Scaling Setup Screen
Click on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 7 for Digital Panel Meters and Digital Transmitters
DPM Filter Setup Screen
Click on the Filter tab, which allows you to specify the digital filter time constant (if any), the adaptive filter threshold, and whether Peak / Valley values are filtered or unfiltered. As for all setup screens, clicking on the F1 key while an item is highlighted brings up a Help screen for that item, as illustrated.
more
Setup Screen 8 for Digital Panel Meters and Digital Transmitters
DPM Relay Alarms Setup Screen
Click on the Relay Alarms tab, which allows you to set up Alarms 1 and 2 for the optional dual relay output board. Clicking on any of the four numeric fields changes these to green and brings up a special field to enter the desired numeric value, which is tied to the displayed reading.
more
Setup Screen 9 for Digital Panel Meters and Digital Transmitters
DPM Communications Setup Screen
Click on the Communications tab so set up serial communications. In particular, you can special the Serial Protocol and the meter address if multiple meters are to be addressed on the same serial data line.
more
Setup Screen 10 for Digital Panel Meters and Digital Transmitters
DPM Analog Output Setup Screen
Click on the Analog Out tab so set up the optional analog output board. Three output ranges are selectable, the endpoints of which can be tied to user-specified High and Low readings.
more
Setup Screen 11 for Digital Panel Meters and Digital Transmitters
DPM Lockouts Setup Screen
Click on the Lockouts tab to check off menu items which will no longer be accessible from the front panel of the meter. This will simplify meter operation and prevent unintended setup changes.
more

Meter Setup Utilities

Setup Screen 12 for Digital Panel Meters and Digital Transmitters
DPM Front Panel Setup Screen
As an aid to programming the meter from the front panel when a serial connection is not available, you can return to the Main Menu and click on View > Menu. The required sequence of front panel screens will then be displayed. Click on any step in the sequence for the meaning of each digit, as illustrated for the FILtEr step. For a hardcopy, simply press on Print.
more
Setup Screen 13 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 14 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screens
Click on any of the displayed plug-in boards, and you will be presented with the jumper positions and electrical connections for your selected board. This minimizes the need to refer to the printed manual.
more
Setup Screen 15 for Digital Panel Meters and Digital Transmitters
DPM Commands Screen
This page allows you set up external input, serial communications, an analog output proportional to the display (optional), and lockouts for Laureate digital counters. The grayed out area at the top right of the screen applies to Laureate remote displays.
more
Graphical Output Screens (not available with Ethernet)

From the Main Menu, click on Readings if your PC is connected to the meter. A pull-down menu then offers three choices: ListPlot and Graph.

  • List presents the latest readings in a 20-row by 10-column table. Press Pause at any time to freeze the display. This is one method to capture peak readings.   
  • Plot generates a plot of readings vs. time in seconds. It effectively turns the DPM-PC combination into a printing digital oscilloscope.
    more 
  • Graph generates a histogram where the horizontal axis is the reading and the vertical axis is the number of occurrences of readings. The display continually resizes itself as the number of readings increases.
    more
Setup Screen 18 for Digital Panel Meters and Digital Transmitters
DPM Calibration Screens
Click on the Scaling tab, which provides three scalClick on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 19 for Digital Panel Meters and Digital Transmitters
Frequency Meter Calibration Screen
Calibration of the quartz crystal of the Laureate frequency meter requires the input of a known frequency from a calibrator. Apply the frequency, then enter the frequency in Hertz. Calibration will be automatic, with storage of the calibration factor stored in non-volatile memory.
more

 

Dimensions

Laurel transmitter case

Dimensioned CAD assembly drawings in EPRT, STEP, x_t, .dwg, pdf file formats: Laureate-transmitter-case.zip (zipping prevents browser from opening CAD files as text files).

 

 

CAL-Digital

Certificate of Calibration

$65.00

CBL02

USB-to-RS232 Adapter Cable

$47.00

CBL04

RS232 Cable for LT Transmitters

$47.00

CBL12

12-foot Power Cable

$47.00

CBL6

6-foot Power Cable

$41.00
Ordering Guide
Part Number as Configured: LTE60VF1
Price as Configured: $558.00

Click on the Option Board Links for More Product Information

Base Item
$388.00
Main Board
$0.00
With Standard Main Board: Rate, square root of rate, or totalized rate from differential pressure flow transducers with a DC output.
With Extended Main Board: Above plus linearization of nonlinear inputs, batch operation, 1/rate (time).
$55.00
Power (Isolated)
$89.00
$89.00
Signal Input (Isolated)
$81.00
$81.00
Note: All ranges are factory calibrated and user selectable
$81.00
Part Number as Configured:
LTE60VF1
Price as Configured:
$558.00
Quantity:
- +
Extended Price:
$558.00

Understanding the Laureate™ LTE Series DIN Rail Transmitter for Analog Input Totalizer

The Laureate™ LTE Series DIN rail transmitter for analog input totalizer accepts 0-1 mA, 4-20 mA or 0-10V signals from flow meters and other transducers, such as watt meters, to track rate or totalized rate. With a Standard main board, the transmitter output can track rate (such as gallons per minute or watts) or totalized rate (such as gallons or kilowatt hours) whether the transducer output is linear or requires square root extraction (differential pressure flow transducers).

V-to-F Signal Conditioner

A signal conditioner board converts the full-scale 0-1 mA, 4-20 mA, or 0-10V analog signal to a frequency of 10 kHz to 110 kHz. This frequency is determined by measuring period over a selected gate time (from 10 ms to 200 s) and taking the inverse of period. At the lowest frequency of 10 kHz and the minimum gate time of 10 ms, the transmitter is capable of 25 updates per second. Scaling is done mathematically. Totals are calculated as the product of rate and time in seconds regardless of the selected gate time. Totals are stored in nonvolatile memory in case of power loss.

Signal Specifications

Input resistance is 1.00 kΩ (0-1 mA), 50 Ω (4-20 mA), or 1.01 MΩ (0-10V). Maximum current or voltage is 35 mA, 70 mA, or 600V respectively. Accuracy at 25°C is ±0.01% FS ±1 count, with typical read rate of 25/sec. Span tempco is ±0.003% reading/°C; zero tempco is ±0.003% FS/°C.

Extended Main Board Capabilities

With an Extended main board, the transmitter can also perform custom curve linearization (curvilinear spline fit with up to 180 data points), display 1/rate (such as the time it takes a conveyor to pass through an oven), and perform batch control for repetitive fill operations, typically using the optional dual solid state relays. External reset of totals is provided by a special connector.

Ethernet & Serial Protocols

Standard Ethernet Data I/O is 10/100 Base-T per IEEE 802.3, isolated to 250V rms working / 2.3 kV rms per 1 minute test. Serial protocols supported are Modbus TCP, Modbus RTU, Modbus ASCII, and Laurel ASCII, with digital addresses 247 for Modbus and 31 for Laurel ASCII.

Where LTE Analog Input Totalizer Transmitters Are Used

  • Networked Flow & Energy Totalization — Ethernet-connected watt-hour and volume totalizing from 4-20 mA transducers.
  • Differential Pressure Flow Totalizing — square-root-extracted flow rate and total from DP transducers.
  • Conveyor Oven Dwell Time Monitoring — 1/rate display for residence time control.
  • Batch Fill Control from Analog Signals — repetitive fill operations from 4-20 mA flow signals.
  • Multi-Point Networked Totalizing — several transmitters on one Modbus TCP network.
  • OEM Networked Totalizer Instrumentation — DIN rail integration into Ethernet-based control panels.

LTE Analog Input Totalizer Transmitter Frequently Asked Questions

Why does this LTE Analog Input Totalizer page document four serial protocols (Modbus TCP, Modbus RTU, Modbus ASCII, Laurel ASCII), unlike other LTE pages that document only Modbus TCP?

Documented specification specifically lists this broader protocol set for this particular transmitter model, distinct from the Modbus-TCP-only listing documented on several other LTE Series product pages — this reflects that documented protocol support can genuinely vary by specific LTE transmitter model, so the exact protocol set available should be confirmed against this specific product's own documented specification rather than assumed to match other LTE Series pages.

Why does totalized value calculation specifically use "the product of rate and time in seconds regardless of the selected gate time," rather than depending on gate time?

Documented description specifically distinguishes this from the rate reading's own update timing — since gate time governs how often the transmitter refreshes its rate calculation, but the accumulated total is documented as computed from rate multiplied by elapsed time independent of that gate time setting, this design ensures the running total stays mathematically consistent and doesn't drift based on whatever gate time happens to be configured for the rate display.

Why do the three signal input types (0-1 mA, 4-20 mA, 0-10V) have such different documented input resistance values (1.00 kΩ, 50 Ω, 1.01 MΩ)?

Documented specification lists these three distinct input resistance values without detailing the underlying circuit reasoning — this is consistent with each input type requiring an input impedance appropriate to its own signal characteristics: current-loop signals (0-1 mA, 4-20 mA) typically use a low burden resistance to develop a measurable voltage without excessively loading the current source, while a voltage input (0-10V) is documented with a much higher input resistance specifically to minimize loading on the voltage source.

Does achieving the documented 25 updates/second rate specifically require the signal to be at the VFC's minimum output frequency (10 kHz)?

Yes — documented phrasing specifically ties the 25/sec figure to "the lowest frequency of 10 kHz and the minimum gate time of 10 ms," identifying this as a specific combination of conditions rather than a rate achievable at any input signal level; this reflects that the update rate is documented as bounded by how long it takes to time a sufficient number of periods at the actual frequency the input signal is converted to.

Does the documented 1/rate function specifically require the Extended main board, or is it available on the Standard board?

Documented specification lists 1/rate specifically as an Extended main board capability, distinct from the Standard board's documented rate/total/square-root functions — this is consistent with 1/rate (time) being a more advanced processing function built on top of the underlying rate measurement the Standard board already provides, requiring the additional Extended board capability to compute and output that inverse relationship.

Does selecting VF1 (4-20 mA) versus VF2 (0-1 mA) versus VF3 (0-10V) change the documented ±0.01% FS ±1 count accuracy specification?

No — documented accuracy specification is listed once, applying generally across the analog input signal conditioner, without separate accuracy figures for VF1, VF2, or VF3 specifically; the choice between these three signal input types is documented as matching the transmitter to whatever signal format the connected transducer outputs, rather than trading off measurement accuracy between the three options.

Does the documented batch control capability on this analog-input totalizer require external relay hardware, or is it self-contained?

Documented description specifically notes batch operation applications "typically make use of optional dual solid state relays, which are available as options" — this indicates the relay hardware needed to actually control a fill valve or similar external device is documented as an optional add-on rather than automatically included, meaning the transmitter's batch control logic itself is built in, but the physical relay output hardware to act on that logic is a separate documented ordering option.

Why does span tempco use "% reading" while zero tempco uses "% FS" as their respective documented reference points?

Documented specification lists these with genuinely different reference bases — span tempco (±0.003% of reading/°C) scales with the actual measured value, consistent with span-related drift being proportional to signal magnitude, while zero tempco (±0.003% FS/°C) is referenced to full scale, consistent with zero-point drift being a roughly fixed offset independent of where in the range the actual reading falls; this distinction reflects the different physical origins of these two documented drift mechanisms.

Does the documented power consumption figures (2W typical, 3W with max excitation) differ from other LTE Series transmitters' documented power consumption?

Yes — this page documents notably lower power consumption (2W typical, 3W with max excitation) compared to the 2.5W typical / 4.0W max figures documented on several other LTE Series pages; this genuine difference reflects that documented power consumption varies by specific transmitter model and its particular signal conditioner board, so this analog-input totalizer's own figures shouldn't be assumed to match other LTE Series product pages.

Does custom curve linearization on this transmitter apply before or after the rate-to-total calculation?

The page documents custom curve linearization as correcting the underlying signal (for example, to extend transducer range and accuracy), with totals separately documented as calculated by multiplying rate by elapsed time — this is consistent with linearization being applied to correct the rate signal itself first, with the already-linearized rate then feeding into the documented total-accumulation calculation, rather than linearization being applied as a separate correction after totaling.

Voltage-to-Frequency Converter (VFC) Questions From the Field

What specifically is a voltage-to-frequency converter, and what makes its output fundamentally different from a typical analog-to-digital converter?

Documented explanation specifically describes a VFC as accepting an analog voltage or current input and producing an output pulse train whose frequency is proportional to the input's magnitude — documented comparison specifically notes this differs from typical ADCs that use parallel digital outputs, since a VFC's output is instead a serial pulse stream whose frequency itself directly carries the analog information, converted to a digital word by counting pulses over a fixed count/gate time.

Is there a documented practical formula for calculating how much count time a VFC-based conversion needs for a given resolution?

Yes — documented technical guidance specifically provides a formula relating required count time to the number of codes needed for a target resolution and the VFC's full-scale output frequency, with a specific documented worked example: a VFC with a 1 MHz full-scale frequency requires a count time of just over 0.262 seconds to achieve 16-bit resolution (1 part in 262,144).

Is inherent monotonicity documented as a genuine advantage of VFC-based analog-to-digital conversion compared to binary-weighted-network converters?

Yes — documented technical analysis specifically identifies this as a real, structural advantage: unlike converters based on binary-weighted networks, VFC-based conversion is documented as inherently monotonic under all supply and temperature conditions, meaning the digital output reliably increases as the analog input increases, without the risk of non-monotonic behavior that binary-weighted architectures can exhibit under certain conditions.

Does averaging multiple VFC pulse-count samples reduce quantization error at the same rate as simple statistical averaging would predict?

Documented technical analysis specifically notes VFC-based conversion can reduce quantization error faster than typical statistical averaging — specifically citing an error reduction rate of 1/N (where N is the number of samples) rather than the more commonly expected 1/√N rate seen in ordinary statistical averaging, attributed to the documented "no-loss" nature of VFC-based conversion during the counting process.

Is there a documented advantage to locating a VFC physically remote from its receiving counter, rather than co-located with it?

Yes — documented explanation specifically notes that because a VFC's signal is converted into an easily-transmitted serial pulse stream, the analog signal-conditioning circuitry can be physically located close to the actual sensor, with only the resulting pulse train needing to travel over distance to a remote counter; documented guidance specifically identifies this as particularly advantageous in multi-channel data acquisition systems using a "converter-per-channel" architecture.

Can a VFC be paired with a second VFC configured as a frequency-to-voltage converter (FVC) to transmit an analog signal across an isolation barrier?

Yes — documented technical guidance specifically describes this exact VFC-FVC combination as "a very useful way of sending a precision analog signal across an isolation barrier," since the pulse-stream output of the VFC can cross an isolation boundary (such as through an optical or transformer-coupled path) more readily than a raw analog signal, with the receiving FVC then reconstructing an analog output on the other side.

Is there a documented distinction between a standard VFC and a "synchronous VFC" (SVFC) used in precision multi-channel systems?

Yes — documented technical description specifically identifies a synchronous VFC as a form of VFC that utilizes an external clock to synchronize its frequency output, distinguishing it from a standard free-running VFC; this documented synchronization capability is specifically noted as valuable in precision, multi-channel data acquisition systems.

Are VFC-based ADC techniques still an active area of documented engineering development, or is this considered a mature, unchanging technology?

Documented recent research specifically continues developing VFC-based conversion techniques — one documented example describes an advanced voltage-to-frequency-to-digital conversion method specifically aimed at remote sensor and telemetry applications, addressing a documented "bottleneck" problem in the frequency-to-digital conversion stage through a proposed dependent-count method, indicating VFC-based conversion remains an area of genuine, ongoing documented technical refinement rather than a static, decades-frozen technology.