LTE DIN Rail Analog Transmitters with Ethernet Communication and Analog Outputs for RTD Temperature Applications

LTE DIN Rail Analog Transmitters with Ethernet Communication and Analog Outputs for RTD Temperature Applications

Price: $558.00
  • P/NLTE20P385C
- +

Features

  • Reads 100Ω platinum, 10Ω copper & 120Ω nickel RTDs
  • Accuracy ±0.01%  of reading ±0.04°C (±0.07°F)
  • 2, 3 or 4-wire connection with lead resistance compensation
  • User selectable input span from entire RTD range down to 15.0°
  • Selectable 1°, 0.1°, or 0.01° resolution, °C, °F, K or R
  • All input ranges are user selectable and factory calibrated
  • Up to 60 conversions per second, Ideal for peak or valley capture
  • 4-20 mA, 0-20 mA, 0-10V or -10V to +10V transmitter output, (isolated)
  • Analog output resolution 0.0015%  of span, accuracy ±0.02%  of span
  • Ethernet data I/O, Modbus TCP
  • Dual 120 mA solid state relays for alarm or control (isolated)
  • Power 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac (isolated)
  • DIN rail mount housing, 22.5 mm wide, detachable screw-clamp connectors
  • Operating temperature from -40°C to 70°C (-40°F to 158°F)

The Laureate™ LTE Series DIN rail analog transmitter with ethernet communication and analog outputs for versatile connectivity.

The digitally programmable transmitter features two relays for alarm or control. The series offers exceptional accuracy of 0.01% of reading ± 2 counts, with high read rates at up to 60 or 50 conversions per second. The LTE Series transmitters offer the same high performance, signal conditioning, and programmable features as Laureate digital panel meters, counters, and timers.

The Laureate 4-20 mA, 0-20 mA, 0-10V or -10V to +10V and ethernet output transmitter for RTD temperature offers the same high performance, signal conditioning and programmable features as Laureate digital panel meters, counters & timers provides six voltage input ranges and four current input ranges, all factory calibrated and jumper selectable. The temperature transmitter provides a linearized, highly accurate, stable and repeatable transmitter output for 100 ohm platinum, 10 ohm copper and 120 ohm nickel RTDs. Pt100 platinum RTDs can have a DIN alpha of 0.00385 or ANSI alpha of 0.00392. The RTD type and temperature range, specified in °C or °F, are user-selectable. The temperature range can be as wide as the entire span of the RTD type or as narrow as 150 counts (such as 15.0°), limited only by considerations of electrical noise and digital filtering time constants.

RTD connections can be via 2, 3 or 4 wires. With 3 or 4-wire connections, the transmitter automatically compensates for changes in lead resistance to the sensor. With 2-wire connection, the transmitter can measure and then subtract the lead wire resistance.

All RTD types are factory-calibrated, with calibration factors for each range securely stored in an onboard EEPROM. These factors can be scaled via software to accommodate external shunts, enabling field replacement of signal conditioner boards without necessitating recalibration of the associated transmitter. For optimal accuracy, factory recalibration is recommended annually. All Laurel Electronics instruments undergo factory calibration using the industry-leading Fluke calibrators, which are recalibrated yearly and certified traceable to national standards, ensuring the highest level of precision and reliability.

Calibration data is stored in EEPROM on the signal conditioner board. This allows signal conditioner boards and ranges to be changed in the field with no need for recalibration. Typical accuracy for a Pt100 is better than ±0.04°C (±0.07°F) ±0.01%  of reading. Open sensor indication is standard and may be set up to indicate either upscale or downscale. RTD excitation is provided by the transmitter. RTD connections can be of the 2-, 3- or 4-wire type. With 3- and 4-wire connections, the transmitter automatically compensates for changes in lead resistance to the sensor. Instrument Setup Software allows user calibration for RTDs whose resistance is different than nominal at 0°C.

Laureate Transmitters are easily programmed with Laurel’s free Instrument Setup Software, downloadable from our website and compatible with Windows PCs, requiring a data interface board for setup.

High read rate of up to 50 or 60 conversions per second, the Laureate™ LTE Series transmitter uses Concurrent Slope (US Pat. 5,262,780) analog-to-digital conversion to integrate signals over a full power line cycle (50 Hz or 60 Hz). This read rate enables peak and valley capture, real-time computer interfacing, and control applications. Peak and valley values are automatically captured and can be viewed using Laurel’s free Instrument Setup Software (compatible with Windows PCs) or transmitted as serial data.

Standard Features of Laureate LTE Transmitters Include:

  • Ethernet I/O, (isolated). The supported protocols are Modbus RTU and ASCII, which are tunneled via Modbus TCP. Note that RS232 or RS485 data I/O is provided by Laurel's LT Series transmitters.
  • 4-20 mA, 0-20 mA or 0-10V analog transmitter output, (isolated), jumper-selectable and user scalable. All selections provide 16-bit (0.0015 ) resolution of output span and 0.02%  output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.
  • Dual solid state relays, (isolated). Available for local alarm or control. Rated 120 mA at 130 Vac or 180 Vdc.
  • Selectable transducer excitation output, (isolated), user selectable 5V@100 mA, 10V@120 mA, 12V@100 mA,  or 24V@50 mA.
  • Power 85-264 Vac, (isolated), low-voltage 10-48 Vdc or 12-32 Vac power is optional.

Digital signal filtering modes can be selected to ensure stable readings in electrically noisy environments.

  • An unfiltered selection provides true peak and valley readings and aids in control applications.
  • A batch average filter selection averages each 16 conversions.
  • Dual solid state relays for control or alarm, (isolated). Rated 120 mA at 140 Vac or 180 Vdc. The relays can respond to digital readings or to received control characters.
  • An adaptive moving average filter selection provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, the filter adapts by briefly switching to the shortest time to follow the change, then reverts back to its selected time constant. An auto setting selects the time constant selection based on signal noise.

Two tare functions: auto-tare and manual tare. In auto-tare, an input line is grounded by an external pushbutton. This causes the current weight, which is normally the empty weight of the container to be stored in memory as an offset. In manual tare, the tare value can be entered manually via a control input pushbutton or using Laurel's free Instrument Setup Software.

Peak and valley values are automatically captured. These may be displayed via Laurel's free Instrument Setup Software, which runs on a PC under MS Windows or can be transmitted as serial data.

Removable screw terminal connections of Laurel transmitters

LTE series DIN rail transmitters & signal conditioners can be interfaced to a wide range of sensors and transducers using one of seven available plug-in signal conditioner boards. The transmitters duplicate the high performance (high accuracy, high read rate) and extensive programmable features of Laureate 1/8 DIN digital panel meters, counters and timers. They utilize the same signal conditioners boards, much of the same firmware, and Laurel's free Windows-based Instrument Setup Software. They come in a compact DIN rail mount package with detachable screw-clamp connectors for easy wiring.

The LTE series Transmitters accessible from this page include a 4-20 mA, 0-20 mA, 0-10V, or -10V to +10V analog output (isolated, user selectable), an ethernet serial data interface (isolated, user selectable), and dual 120 mA solid state AC/DC relays (isolated). An (isolated) 5, 10, 12, or 24 Vdc transducer excitation output is included with all models other than those with a temperature or AC RMS signal conditioner.

Connecting Laureate LTE Transmitters to a Local Area Network (LAN)

Laurel LTE series Ethernet transmitters can connect directly to a LAN via an Ethernet cable. Up to 30 Laureate LT Transmitters and/or Digital Panel Meters can be configured for RS485 and daisy-chained to an LT Transmitter for seamless LAN integration. Setup for both configurations is streamlined using Laurel’s free Instrument Setup Software, which simplifies node discovery and transmitter configuration. 

Flexible Communication Options for LTE Transmitters

Laureate Transmitters can be equipped with Laurel communication boards to support various interfaces and protocols. These include serial interfaces with ASCII or Modbus RTU protocols, and Ethernet interfaces with web access, ASCII, or Modbus TCP/IP protocols, ensuring versatile connectivity for your commercial applications.

Laureate Ethernet network by Laurel Electronics

Laureate Ethernet & 4-20 mA Output Thermocouple Temperature Transmitter

RTD Metal Alpha R at 0°C R at top
of range
Excitation
Current
Range Max Error
Platinum
Pt100
0.003850 (DIN) 100Ω 390.48Ω
at 850°C
196 µA -202°C to +850°C
-331°F to +1562°F
±0.03°C ±0.01% of rdg
±0.05°F ±0.01% of rdg
Platinum
Pt100
0.003902 (ANSI) 100Ω 394.36Ω
at 850°C
196 µA -202°C to +850°C
-331°F to +1168°F
±0.04°C ±0.01% of rdg
±0.07°F ±0.01% of rdg
Nickel
Ni120
0.00672 120Ω 380.31Ω
at 260°C
196 µA -80°C to +260°C
-112°F to +500°F
±0.05°C ±0.01% of rdg
±0.09°F ±0.01% of rdg
Copper
Cu10
0.00427 9.035Ω 19.116Ω
at 260°C
5.0 mA -100°C to +260°C
-148°F to +500°F
±0.05°C ±0.01% of rdg
±0.09°F ±0.01% of rdg
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.
RTD Input
Calibration, Pt 100 DIN IEC 751 (IPTS-68)
Calibration, Pt 100 ANSI NIST Monograph 126
Configuration 2, 3 or 4-wire connection
Excitation current 0.2 mA
Max error at 25°C, Pt100 ±0.04°C (±0.07°F) ±0.01% of reading
Span tempco ±0.003% of reading/°C
Zero tempco ±0.03 deg/deg
Sensor lead resistance 2-wire: 10 mdeg/Ω/deg up to 10Ω;
tempco per conductor 3 & 4-wire: 10 μdeg/Ω/deg up to 100Ω
Over-voltage protection 125 Vac
Open sensor indication 0 mA or > 20 mA output, selectable
Provision for user calibration Multiplier of RTD resistance plus offset in degrees
Analog Output (standard)
Output Levels 4-20 mA and 0-10 Vdc (selectable)
Compliance, 4-20 mA 10V (0-500Ω load)
Compliance, 0-10V 2 mA (5 kΩ load)
Output Resolution 16 bits (65,536 steps)
Output Accuracy ±0.02% of output span
Output Isolation 250V rms working, 2.3 kV rms per 1 minute test
Step response time 50 ms
Ethernet Data I/O (standard)
Type 10/100Base-T Ethernet per IEEE 802.3
Data Rates 300, 600, 1200, 2400, 4800, 9600, 19200 baud
Output Isolation 250V rms working, 2.3 kV rms per 1 min test
Serial Protocol Modbus TCP
Modbus Compliance Modbus over Serial Line Specification V1.0 (2002)
Digital Addresses 247 for Modbus
Dual Relay Output (standard)
Relay Type Two solid state relays, SPST, normally open, Form A
Load Rating 120 mA at 140 Vac or 180 Vdc
Power Input
Standard Power 85-264 Vac or 90-300 Vdc
Low Power Option 10-48 Vdc or 12-32 Vac
Power Frequency DC or 47-63 Hz
Power Isolation 250V rms working, 2.3 kV rms per 1 min test
Power Consumption 2.5W typical at 24V
Environmental
Operating Temperature -40°C to 70°C (-40°F to 158°F)
Storage Temperature -40°C to 85°C (-40°F to 185°F)
Relative Humidity 95% at 40°C, non-condensing
Cooling Required Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan.
Mechanical
Enclosure Rugged black polycarbonate housing material
Mounting 35 mm rail per DIN EN 50022
Dimensions 129 x 104 x 22.5 mm case
Connectors Detachable screw clamp connectors meet VDE / IEC / UL / CSA standards. RJ45 jack for Ethernet
Tightening Torque Screw terminal connectors: 5 lb-in (0.56 Nm)
Weight Complete transmitter: 183 g (6.5 oz)
Replacement Case Screws
Size 6
Thread Pitch 6-19
Length 1/2"
Head Style Pan Head
Drive Style Phillips
Head Diameter 0.256-0.270
Head Height 0.087-0.097
Full/Partial Thread Full
Drive Size 2
Material Steel
Finished Black Oxide
General
Programming Utilize Laurel's free Instrument Setup Software, which runs on a PC under MS Windows. 
Security Lockout options available using Laurel's free Instrument Setup Software.
Warranty 3 years parts & labor
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.

Transmitter Pinout

LTE Ethernet transmitter pinout, analog input

RTD hookup can be via 2, 3 or 4 wires to the J5 connector. The transmitter applies an excitation current of 196 µA (Pt 100 and Ni 120) or 5 mA (Cu 10).

4-wire hookup of RTD signal conditioner board In 4-wire hookup, different pairs of leads are used to apply the excitation current and sense the voltage drop across the RTD, so that the IR drop across the excitation leads is not a factor.
3-wire hookup of RTD signal conditioner board In 3-wire hookup, the transmitter senses the combined voltage drop across the RTD plus two excitation leads. It also senses the voltage drop across one excitation lead, and then subtracts twice this voltage from the combined total. This technique effectively subtracts all lead resistance and compensates for ambient temperature changes if the two excitation leads are identical.
2-wire hookup of RTD signal conditioner board In 2-wire hookup, the transmitter senses the combined voltage drop across the RTD and both lead wires. The voltage drop across the lead wires can be measured by shorting out the RTD during transmitter setup, and this voltage is then automatically subtracted from the combined total. However, changing resistance of the lead wires due to ambient temperature changes will not be compensated.

 

Free Instrument Setup Software for Series 2 Laureates

Digital Panel Meter Laurel Electronics Digital Transmitters
1/8 DIN Digital Panel Meters DIN Rail Transmitters

Free Downloadable Windows-based Instrument Setup (IS) software (Data Interface Board Required) for use with our programmable Digital Panel Meters, Scale Meters, Counters, Timers, Remote Displays, and Transmitters, are an easy method to set up Laureate 1/8 DIN digital panel meters, counters, timers, remote displays, and DIN-rail transmitters, as explained in the Instrument Setup Software Manual. Laureate 1/8 DIN instruments can also be set up from the front panel, as explained in their respective Owners Manuals. Instrument Setup software is of benefit whether or not the PC is connected to the instrument.

  • When the PC is connected to the instrument, Instrument Setup software can retrieve the setup file from the instrument or open a default setup file or previously saved setup file from disk View Setup, then provides graphical user interface (GUI) screens with pull-down menus applicable to input, display, scaling, filtering, alarms, communications, analog output, and front panel lockouts. Fields that are not applicable to the instrument as configured are either left out or grayed out. Clicking on any item will bring up a detailed Help screen for that item. After editing, the setup file can be downloaded, uploaded to the instrument, or saved to a disk. The same setup file can then be downloaded into multiple instruments.
  • When the PC is not connected to the instrument, the above GUI screens can be used to set up a virtual instrument. The setup file can then be saved to disk. Switching toView Menu then brings up a screen with the required front panel programming steps. This view can be printed out for use at the instrument site and to serve as a hard copy record.

    Download Free Instrument Setup Software


Installation

Set User Account Control (UAC) of MS Windows to "Never notifiy me" so that Instrument Setup Software can create directories. The UAC change screen can be reached as follows:

  • Under Windows 7, click on the Windows Start button in the lower left of the desktop and enter "UAC" in the search field.
  • Under Windows 8, navigate to Control Panel, then to the "User Accounts and Family Safety" section, and click on "Change User Account Control Settings."
  • Under Windows 10, click on the Windows Start button in the lower left of the desktop, then on "Settings", and enter "UAC" in the search field.
  • Reboot your computer for the changed UAC setting to take effect.
Meter board with USB Type-B connector

RJ11-to-DB9 cable with rear view of DB9 connector to PC

Laurel USB cable, P/N CBL05

RS232 cable, meter to PC, P/N CBL01

Laureate 1/8 DIN Laureate instruments must be equipped with a serial communications board and be connected to the computer via a serial communications cable. The connection can be via RS232, RS485, USB or Ethernet. Following setup, the serial communications board may be removed from the instrument if desired. The wiring of the RS232 cable is illustrated above with end views of the two connectors.

Laureate LT Series transmitters come standard with a 3-wire serial interface, which can be jumpered for RS232 or RS485.
Laureate LTE Series transmitters come standard with an Ethernet interface.

Meter Setup Screens

Click on any of the reduced screens below for a full-size screen view, then click on the Back button of your browser to return to this page. The screens examples below are for a fully-loaded Series 2 Digital Panel Meter (DPM), which is connected to the PC via RS232. If the meter is a Series 1 meter (pre-2007), this is sensed by the software, and somewhat different screens are brought up. Please see Series 1 setup screens.

Laurel Dual Channel Pulse Input Rate Meter
Welcome Screen
From the computer desktop, click on Start > Programs > IS2 > IS2. Or click on the IS icon on your desktop. This splash screen will be displayed for three seconds. The software revision number is in the lower right.
more
Setup Screen 02s for Digital Panel Meters and Digital Transmitters
Communications Selection Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 3 for Digital Panel Meters and Digital Transmitters
Establish Communications Screen
If you selected RS-232, you will be asked to specify the PC Com Port and Baud Rate, which should match the jumper setup of the instrument. Click on Establish. With the right settings, the Communications Established field will light up in green, and the Meter Type will be recognized. If so, click onMain Menu.
more
Setup Screen 4 for Digital Panel Meters and Digital Transmitters
Main Menu Screen
Click on File > Default Setup to retrieve the default setup file from disk for your type of meter. Click on File > Open Setupto retrieve a previously saved setup file from disk or on File > Save Setup to save your edited setup file to disk. Click onDPM > Get Setup to retrieve the setup file from your meter or on DPM > Put Setup to download your edited setup file into the meter.
more
Setup Screen 5 for Digital Panel Meters and Digital Transmitters
DPM Input + Display Setup Screen
From the Main Menu, click on View > Setup, then on theInput+Display tab. You can now specify the meter hardware, signal type, display mode, and functions of control inputs A and B. Clicking on any item brings up a pull-down menu with the available choices.
more
Setup Screen 6 for Digital Panel Meters and Digital Transmitters
DPM Scaling Setup Screen
Click on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 7 for Digital Panel Meters and Digital Transmitters
DPM Filter Setup Screen
Click on the Filter tab, which allows you to specify the digital filter time constant (if any), the adaptive filter threshold, and whether Peak / Valley values are filtered or unfiltered. As for all setup screens, clicking on the F1 key while an item is highlighted brings up a Help screen for that item, as illustrated.
more
Setup Screen 8 for Digital Panel Meters and Digital Transmitters
DPM Relay Alarms Setup Screen
Click on the Relay Alarms tab, which allows you to set up Alarms 1 and 2 for the optional dual relay output board. Clicking on any of the four numeric fields changes these to green and brings up a special field to enter the desired numeric value, which is tied to the displayed reading.
more
Setup Screen 9 for Digital Panel Meters and Digital Transmitters
DPM Communications Setup Screen
Click on the Communications tab so set up serial communications. In particular, you can special the Serial Protocol and the meter address if multiple meters are to be addressed on the same serial data line.
more
Setup Screen 10 for Digital Panel Meters and Digital Transmitters
DPM Analog Output Setup Screen
Click on the Analog Out tab so set up the optional analog output board. Three output ranges are selectable, the endpoints of which can be tied to user-specified High and Low readings.
more
Setup Screen 11 for Digital Panel Meters and Digital Transmitters
DPM Lockouts Setup Screen
Click on the Lockouts tab to check off menu items which will no longer be accessible from the front panel of the meter. This will simplify meter operation and prevent unintended setup changes.
more

Meter Setup Utilities

Setup Screen 12 for Digital Panel Meters and Digital Transmitters
DPM Front Panel Setup Screen
As an aid to programming the meter from the front panel when a serial connection is not available, you can return to the Main Menu and click on View > Menu. The required sequence of front panel screens will then be displayed. Click on any step in the sequence for the meaning of each digit, as illustrated for the FILtEr step. For a hardcopy, simply press on Print.
more
Setup Screen 13 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 14 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screens
Click on any of the displayed plug-in boards, and you will be presented with the jumper positions and electrical connections for your selected board. This minimizes the need to refer to the printed manual.
more
Setup Screen 15 for Digital Panel Meters and Digital Transmitters
DPM Commands Screen
This page allows you set up external input, serial communications, an analog output proportional to the display (optional), and lockouts for Laureate digital counters. The grayed out area at the top right of the screen applies to Laureate remote displays.
more
Graphical Output Screens (not available with Ethernet)

From the Main Menu, click on Readings if your PC is connected to the meter. A pull-down menu then offers three choices: ListPlot and Graph.

  • List presents the latest readings in a 20-row by 10-column table. Press Pause at any time to freeze the display. This is one method to capture peak readings.   
  • Plot generates a plot of readings vs. time in seconds. It effectively turns the DPM-PC combination into a printing digital oscilloscope.
    more 
  • Graph generates a histogram where the horizontal axis is the reading and the vertical axis is the number of occurrences of readings. The display continually resizes itself as the number of readings increases.
    more
Setup Screen 18 for Digital Panel Meters and Digital Transmitters
DPM Calibration Screens
Click on the Scaling tab, which provides three scalClick on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 19 for Digital Panel Meters and Digital Transmitters
Frequency Meter Calibration Screen
Calibration of the quartz crystal of the Laureate frequency meter requires the input of a known frequency from a calibrator. Apply the frequency, then enter the frequency in Hertz. Calibration will be automatic, with storage of the calibration factor stored in non-volatile memory.
more

 

Dimensions

Laurel transmitter case

Dimensioned CAD assembly drawings in EPRT, STEP, x_t, .dwg, pdf file formats: Laureate-transmitter-case.zip (zipping prevents browser from opening CAD files as text files).

 

 

CAL-Analog

Certificate of Calibration

$65.00

CBL02

USB-to-RS232 Adapter Cable

$47.00

CBL04

RS232 Cable for LT Transmitters

$47.00

CBL12

12-foot Power Cable

$47.00

CBL6

6-foot Power Cable

$41.00
Ordering Guide
Part Number as Configured: LTE20P385C
Price as Configured: $558.00

Click on the Option Board Links for More Product Information

Base Item
$388.00
Main Board
$0.00
Power (Isolated)
$89.00
$89.00
Signal Input (Isolated)
$81.00
$81.00
$81.00
$81.00
$81.00
$81.00
$81.00
Note: The same signal conditioner board can be user configured for all RTD types listed and °C or °F, as well as for resistance measurement
Note: All ranges are factory calibrated and user selectable
$81.00
Part Number as Configured:
LTE20P385C
Price as Configured:
$558.00
Quantity:
- +
Extended Price:
$558.00

Understanding the Laureate™ LTE Series DIN Rail Transmitter for RTD Temperature Input

The Laureate™ LTE Series DIN rail transmitter for RTD temperature provides a linearized, highly accurate, stable and repeatable output for 100 ohm platinum, 10 ohm copper, and 120 ohm nickel RTDs. Pt100 platinum RTDs can have a DIN alpha of 0.003850 or ANSI alpha of 0.003902. The RTD type and temperature range, specified in °C or °F, are user-selectable, as narrow as 150 counts (such as 15.0°), limited only by electrical noise and digital filtering time constants.

Per-Type Accuracy

Platinum Pt100 DIN (alpha 0.003850): -202°C to +850°C, ±0.03°C ±0.01% of reading, calibrated per IEC 751 (IPTS-68). Platinum Pt100 ANSI (alpha 0.003902): -202°C to +850°C, ±0.04°C ±0.01% of reading, calibrated per NIST Monograph 126. Nickel Ni120: -80°C to +260°C, ±0.05°C ±0.01% of reading. Copper Cu10: -100°C to +260°C, ±0.05°C ±0.01% of reading. Excitation current is 196 µA for Pt100 and Ni120, and 5.0 mA for Cu10.

2-, 3-, and 4-Wire Lead Compensation

In 4-wire hookup, different pairs of leads apply the excitation current and sense the voltage drop across the RTD, so the IR drop across the excitation leads is not a factor. In 3-wire hookup, the transmitter senses the combined voltage drop across the RTD plus two excitation leads, also senses the voltage drop across one excitation lead, and subtracts twice this voltage from the combined total — this technique effectively subtracts all lead resistance and compensates for ambient temperature changes if the two excitation leads are identical. In 2-wire hookup, the transmitter senses the combined voltage drop across the RTD and both lead wires; lead wire voltage drop can be measured by shorting out the RTD during setup and automatically subtracted, but changing lead wire resistance due to ambient temperature will not be compensated. Sensor lead resistance tempco is 10 mdeg/Ω/deg for 2-wire (up to 10Ω), and 10 µdeg/Ω/deg for 3- and 4-wire (up to 100Ω).

Additional Signal Specifications

Zero tempco is ±0.03 deg/deg. Span tempco is ±0.003% of reading/°C. Overvoltage protection is 125 Vac. Open sensor indication is standard, selectable as 0 mA or greater than 20 mA output. Instrument Setup Software provides for user calibration (multiplier of RTD resistance plus offset in degrees) for RTDs whose resistance differs from nominal at 0°C. The same signal conditioner board can be user configured for all RTD types listed, in °C or °F, as well as for resistance measurement.

Ethernet Data I/O

Standard Ethernet Data I/O is 10/100 Base-T per IEEE 802.3, isolated to 250V rms working / 2.3 kV rms per 1 minute test, with Modbus TCP at digital address 247. Analog output levels are 4-20 mA and 0-10 Vdc (selectable), 16-bit resolution, ±0.02% of output span accuracy, and 50 ms step response time.

Where LTE RTD Transmitters Are Used

  • Networked Process Temperature Monitoring — Ethernet-connected Pt100/Ni120/Cu10 readout.
  • Long-Run RTD Installations — 3- and 4-wire lead resistance compensation over distance.
  • High-Precision Laboratory & Calibration Systems — 4-wire configuration for lead-resistance-immune readings.
  • Multi-Point Networked Temperature Monitoring — several transmitters on one Modbus TCP network.
  • OEM Networked Temperature Instrumentation — DIN rail integration into Ethernet-based control panels.

LTE RTD Temperature Transmitter Frequently Asked Questions

Why does Pt100 DIN (alpha 0.003850) carry a documented ±0.03°C accuracy figure while Pt100 ANSI (alpha 0.003902) is documented at ±0.04°C, despite both being 100Ω platinum RTDs?

Documented specification lists these as genuinely separate accuracy figures tied to two different calibration standards — IEC 751 (IPTS-68) for the DIN alpha curve versus NIST Monograph 126 for the ANSI alpha curve — since these are documented as distinct calibration references with their own characterization data, the resulting achievable accuracy figures for each curve are documented separately rather than being identical simply because both use 100Ω platinum elements.

Why does sensor lead resistance tempco improve by roughly three orders of magnitude between 2-wire (10 mdeg/Ω/deg) and 3-/4-wire (10 µdeg/Ω/deg) configurations?

Documented figures specifically quantify this difference in lead-resistance-driven temperature error per ohm per degree — since 3- and 4-wire configurations are documented as actively compensating for or eliminating lead resistance effects (through excitation/sense lead separation), while 2-wire configuration is documented as only compensating for the initial resistance value measured at setup (not its later temperature-driven drift), the residual documented tempco for 2-wire is substantially larger, reflecting the lead wire's own resistance change with ambient temperature going uncompensated.

Does the documented 3-wire compensation technique work correctly if the two excitation leads have genuinely different lengths or gauges?

No — documented description specifically qualifies the 3-wire compensation technique as effective "if the two excitation leads are identical," meaning the method's accuracy depends on this stated assumption; if the two excitation leads genuinely differ in resistance (due to length, gauge, splices, or connection quality), the documented subtraction of "twice one excitation lead's voltage drop" would not perfectly cancel the actual combined lead resistance, since the calculation assumes both leads' resistance is the same as the one it's actually measuring.

Why does the 2-wire hookup method require "shorting out the RTD during transmitter setup" rather than compensating for lead resistance automatically like the 3-wire method?

Documented description specifically explains that 2-wire hookup senses the combined voltage drop across the RTD and both lead wires together, with no separate, independent way to isolate just the lead wire contribution during normal operation; shorting the RTD during setup is documented as the specific method used to capture just the lead wire resistance in isolation at that moment, which is then subtracted — but since this is a one-time setup measurement, documented limitation notes any later lead resistance change from ambient temperature won't be automatically compensated the way it is in 3- and 4-wire configurations.

Does the documented user calibration feature (multiplier plus offset) allow correcting for an RTD with a genuinely different alpha curve than the transmitter is configured for?

The page documents user calibration specifically as addressing RTDs "whose resistance is different than nominal at 0°C," which is consistent with correcting a manufacturing tolerance or small resistance offset at the reference point — this is documented as a distinct concern from selecting the correct underlying RTD type/alpha curve at time of order (P385 for DIN alpha, P392 for ANSI alpha), so a genuinely mismatched alpha curve would need the correct P385/P392 signal input selected, rather than being correctable solely through the documented user calibration multiplier/offset.

Why does copper (Cu10) RTD excitation current (5.0 mA) differ so substantially from the 196 µA used for Pt100 and Ni120?

Documented specification lists these substantially different excitation currents without detailing the underlying circuit reasoning — this is consistent with Cu10's documented much lower base resistance (9.035Ω at 0°C, versus 100Ω for Pt100 and 120Ω for Ni120) requiring proportionally more excitation current to develop a comparably measurable voltage signal across the sensor for the same signal conditioning circuitry to process accurately.

Does this LTE RTD transmitter's documented Modbus TCP-only protocol limit compatibility compared to the RS232/RS485 LT Series RTD variant?

Yes — this page documents Modbus TCP specifically as the supported Ethernet Data I/O protocol at digital address 247, while the LT Series serial variant is documented elsewhere as separately supporting Modbus RTU/ASCII and Laurel Custom ASCII; a control system needing a protocol other than Modbus TCP would need to reference the LT Series serial variant rather than this LTE Ethernet variant.

Does the documented note that the same signal conditioner board supports both RTD types and resistance measurement mean an RTD transmitter can be reconfigured for general resistance measurement without new hardware?

Documented note specifically states the board "can be user configured for all RTD types listed... as well as for resistance measurement," which is consistent with resistance measurement being an available configuration option on the same underlying board hardware — though the page itself doesn't detail whether this reconfiguration is purely a software/setup change or also involves jumper settings, similar to how DC voltmeter versus ammeter operation is documented as jumper-selected on other LT/LTE transmitters.

Does zero tempco (±0.03 deg/deg) and span tempco (±0.003% of reading/°C) represent the same underlying drift mechanism?

No — these are documented as two separate specifications describing different aspects of temperature-driven measurement drift: zero tempco describes drift in the reading at the zero/reference point, while span tempco describes drift in the overall scaling of readings across the measurement range as ambient temperature changes; both contribute to total measurement drift but through documented, physically distinct mechanisms.

Does selecting a wider RTD range (such as the full -202°C to +850°C Pt100 DIN span) change the transmitter's documented ±0.01% of reading accuracy component?

No — documented accuracy is expressed as a fixed error figure (such as ±0.03°C for Pt100 DIN) plus a separate ±0.01% of reading component; the percentage-of-reading portion is documented as applying proportionally regardless of the specific span selected, while the fixed error figure remains constant, meaning total accuracy at any given actual temperature reading follows the same documented formula whether a wide or narrow input span is configured.

3-Wire RTD Lead Wire Matching Questions From the Field

Why does even a small amount of lead resistance cause a disproportionately large temperature reading error in a Pt100 RTD?

Documented explanation specifically notes a 100-ohm platinum RTD changes resistance by only about 0.385 ohms per degree Celsius — since this per-degree resistance change is so small, documented calculation shows a lead resistance of just 2 ohms can translate into roughly a 5°C measurement error, illustrating how the RTD's inherently small resistance-per-degree sensitivity makes it disproportionately vulnerable to any uncompensated lead resistance.

What real-world conditions commonly break the "identical lead resistance" assumption that 3-wire compensation depends on?

Documented field examples specifically cite a splice or repair performed on one conductor but not the other, a field repair using mismatched wire gauge because it was what was available on hand, and a corroded or loose terminal adding resistance on just one side of the pair — these are documented as genuine, common real-world causes of the two "identical" excitation leads becoming measurably mismatched over an installation's service life.

Is there a documented quick field test to verify whether a 3-wire RTD installation is correctly wired?

Yes — documented field test specifically involves swapping any two of the three lead wires at the controller terminals; if the temperature reading changes significantly after the swap, documented guidance identifies this as indicating a wiring fault, since a properly wired and matched 3-wire RTD installation is documented as showing the same reading regardless of which two wires are swapped.

Why is a 4-wire RTD configuration documented as being immune to lead resistance mismatch in a way 3-wire configurations are not?

Documented explanation specifically attributes this to the 4-wire configuration's completely separate voltage-sensing wire pair carrying essentially zero current, due to the high-impedance nature of a voltage measurement input — since negligible current flows through those sensing wires, their resistance has essentially zero effect on the reading regardless of length or mismatch, which documented analysis contrasts directly with 3-wire's dependence on the "leads are identical" assumption.

Does accidentally jumpering or shorting the two excitation leads together at the transmitter terminals of a properly matched 3-wire RTD actually introduce new error, or does it simply reduce accuracy back toward 2-wire levels?

It genuinely introduces new error, documented as worse than simply reverting to 2-wire performance — one documented worked example specifically shows a normal, well-matched 3-wire installation producing 0.00°F of lead-related error, while jumpering the two excitation leads at the transmitter produces a documented +0.94°F error purely from that jumper, illustrating the jumper doesn't just remove the 3-wire compensation benefit but actively creates a new, uncompensated resistance path.

Does using the same wire gauge and type throughout a 3-wire RTD installation genuinely improve real-world accuracy, or is this mainly a theoretical best practice?

It's documented as a genuine, practical best practice with a measurable accuracy benefit — documented guidance specifically states using the same type of wire on all three RTD lead wires makes a 3-wire installation "as accurate as possible," directly tying the practical wire-selection decision to the underlying mathematical assumption (identical lead resistance) that the entire 3-wire compensation technique depends on.

Is there a documented typical real-world accuracy difference between 2-wire and 3-wire RTD configurations, expressed as a concrete number rather than just "more or less accurate"?

Yes — one documented comparison specifically cites 3-wire RTDs as typically achieving ±0.5 to 1°C accuracy compared to ±1 to 5°C for 2-wire configurations, assuming lead wires up to 100 feet in length; this documented range gives a concrete sense of the real accuracy gap between the two configurations under a common practical installation length.

Does grounding the cable shield at both the sensor end and the controller end of a 3-wire RTD installation improve noise rejection?

No — documented guidance specifically warns against grounding both ends of a shielded RTD cable, since doing so creates a ground loop that introduces noise rather than rejecting it; documented best practice specifically recommends grounding the shield only at the controller or cabinet side, leaving the sensor end of the shield unconnected.