LTE DIN Rail Analog Transmitters with Ethernet Communication and Analog Outputs for Process and Ratiometric Signal Applications

LTE DIN Rail Analog Transmitters with Ethernet Communication and Analog Outputs for Process and Ratiometric Signal Applications

Price: $558.00
  • P/NLTE20P
- +

Features

  • 200 mV, 2V, 20V, 200V, 300V & 600V DC voltage input ranges
  • 2, 20, 200 mA and 5A DC current input ranges
  • Accuracy ±0.01% of reading ± 2 counts
  • Absolute and ratiometric mode for bridges and potentiometers
  • Error less than 0.01%  of full scale for absolute ranges, less than 0.01% of reading for ratiometric measurements
  • All input ranges are user selectable and factory calibrated
  • Up to 60 conversions per second, Ideal for peak or valley capture
  • 4-20 mA, 0-20 mA, 0-10V or -10V to +10V transmitter output, (isolated)
  • Analog output resolution 0.0015%  of span, accuracy ±0.02%  of span
  • Ethernet data I/O, Modbus TCP
  • Dual 120 mA solid state relays for alarm or control (isolated)
  • 5V, 10V, 12V, or 24V dc transducer excitation output (isolated)
  • Power 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac (isolated)
  • DIN rail mount housing, 22.5 mm wide, detachable screw-clamp connectors
  • Operating temperature from -40°C to 70°C (-40°F to 158°F)
    Optional - Extended allows up to 180 data points for custom curve linearization and a rate derived from consecutive readings.

The Laureate™ LTE Series DIN rail analog transmitter with ethernet communication and analog outputs for versatile connectivity.

The digitally programmable transmitter features two relays for alarm or control. The series offers exceptional accuracy of 0.01% of reading ± 2 counts, with high read rates at up to 60 or 50 conversions per second. The LTE Series transmitters offer the same high performance, signal conditioning, and programmable features as Laureate digital panel meters, counters, and timers.

The Laureate 4-20 mA, 0-20 mA, 0-10V or -10V to +10V and ethernet output transmitter for process signal input provides zero and span adjustment for use with a wide range of industrial transducers. Six DC voltage and four DC current input ranges are jumper selectable. The two most sensitive voltage ranges, 200.00 mV and 2.0000V, provide a high input impedance of 1 GΩ to minimize the load on the voltage signal.

The transmitter can be set to a ratio (or potentiometer follower) mode by making selections at the connector and in software. In this mode, the transmitter output tracks a ratio of the applied excitation voltage and is unaffected by changes in the excitation voltage. Ratiometric measurements provide an exceptional accuracy of 0.01% of reading ± 2 counts. This capability is used with the transmitter's 5V or 10V excitation output for load cells and Wheatstone bridges, and with the transmitter's 5V excitation output for potentiometers which track wiper position.

All signal conditioner board ranges are factory-calibrated, with calibration factors for each range securely stored in an onboard EEPROM. These factors can be scaled via software to accommodate external shunts, enabling field replacement of signal conditioner boards without necessitating recalibration of the associated transmitter. For optimal accuracy, factory recalibration is recommended annually. All Laurel Electronics instruments undergo factory calibration using the industry-leading Fluke calibrators, which are recalibrated yearly and certified traceable to national standards, ensuring the highest level of precision and reliability.

The optional extended Laureate computer board enhances Laureate Transmitters by displaying rates derived from successive readings and enabling highly accurate custom curve linearization. For example, it can calculate liquid volume or flow rate in a horizontal cylindrical tank using levels from a 4-20 mA transmitter. Setup is straightforward: users input up to 180 data points into a spreadsheet or text file, and the computer calculates spline-fit segments, which are then downloaded to the transmitter for precise operation.

Laureate Transmitters are easily programmed with Laurel’s free Instrument Setup Software, downloadable from our website and compatible with Windows PCs, requiring a data interface board for setup.

High read rate of up to 50 or 60 conversions per second, the Laureate™ LTE Series transmitter uses Concurrent Slope (US Pat. 5,262,780) analog-to-digital conversion to integrate signals over a full power line cycle (50 Hz or 60 Hz). This read rate enables peak and valley capture, real-time computer interfacing, and control applications. Peak and valley values are automatically captured and can be viewed using Laurel’s free Instrument Setup Software (compatible with Windows PCs) or transmitted as serial data.

Standard Features of Laureate LTE Transmitters Include:

  • Ethernet I/O, (isolated). The supported protocols are Modbus RTU and ASCII, which are tunneled via Modbus TCP. Note that RS232 or RS485 data I/O is provided by Laurel's LT Series transmitters.
  • 4-20 mA, 0-20 mA or 0-10V analog transmitter output, (isolated), jumper-selectable and user scalable. All selections provide 16-bit (0.0015 ) resolution of output span and 0.02%  output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.
  • Dual solid state relays, (isolated). Available for local alarm or control. Rated 120 mA at 130 Vac or 180 Vdc.
  • Selectable transducer excitation output, (isolated), user selectable 5V@100 mA, 10V@120 mA, 12V@100mA, or 24V@50 mA.
  • Power 85-264 Vac, (isolated), low-voltage 10-48 Vdc or 12-32 Vac power is optional.

Digital signal filtering modes can be selected to ensure stable readings in electrically noisy environments.

  • An unfiltered selection provides true peak and valley readings and aids in control applications.
  • A batch average filter selection averages each 16 conversions.
  • An adaptive moving average filter selection provides a choice of 8 time constants from 80 ms to 9.6 seconds. When a significant change in signal level occurs, the filter adapts by briefly switching to the shortest time to follow the change, then reverts back to its selected time constant. An auto setting selects the time constant selection based on signal noise.

Two tare functions: auto-tare and manual tare. In auto-tare, an input line is grounded by an external pushbutton. This causes the current weight, which is normally the empty weight of the container to be stored in memory as an offset. In manual tare, the tare value can be entered manually via a control input pushbutton or using Laurel's free Instrument Setup Software.  

Peak and valley values are automatically captured. These may be displayed via  Laurel's free Instrument Setup Software,  which runs on a PC under MS Windows or can be transmitted as serial data.

An (isolated) 5, 10, 12, or 24 Vdc excitation output is standard to power transducers or two-wire transmitters. Ratiometric operation, which automatically compensates for changes in the applied excitation, is jumper selectable for applications, such as bridges, where the signal to be measured is proportional to the excitation level.

Removable screw terminal connections of Laurel transmitters

LTE series DIN rail transmitters & signal conditioners can be interfaced to a wide range of sensors and transducers using one of seven available plug-in signal conditioner boards. The transmitters duplicate the high performance (high accuracy, high read rate) and extensive programmable features of Laureate 1/8 DIN digital panel meters, counters and timers. They utilize the same signal conditioners boards, much of the same firmware, and Laurel's free Windows-based Instrument Setup Software. They come in a compact DIN rail mount package with detachable screw-clamp connectors for easy wiring.

The LTE series Transmitters accessible from this page include a 4-20 mA, 0-20 mA, 0-10V, or -10V to +10V analog output (isolated, user selectable), an ethernet serial data interface (isolated, user selectable), and dual 120 mA solid state AC/DC relays (isolated). An (isolated) 5, 10, 12, or 24 Vdc transducer excitation output is included with all models other than those with a temperature or AC RMS signal conditioner.

Connecting Laureate LTE Transmitters to a Local Area Network (LAN)

Laurel LTE series Ethernet transmitters can connect directly to a LAN via an Ethernet cable. Up to 30 Laureate LT Transmitters and/or Digital Panel Meters can be configured for RS485 and daisy-chained to an LT Transmitter for seamless LAN integration. Setup for both configurations is streamlined using Laurel’s free Instrument Setup Software, which simplifies node discovery and transmitter configuration. 

Flexible Communication Options for LTE Transmitters

Laureate Transmitters can be equipped with Laurel communication boards to support various interfaces and protocols. These include serial interfaces with ASCII or Modbus RTU protocols, and Ethernet interfaces with web access, ASCII, or Modbus TCP/IP protocols, ensuring versatile connectivity for your commercial applications.

Laureate Ethernet network by Laurel Electronics

Laureate™ Ethernet & 4-20 mA Output Transmitter for Process & Ratio Signals

tr>
Analog Input Range Resolution Reading Accuracy Input Ohms
DC Voltage ±200.00 mV 10 µV 0.01% FS ± 2 cts 1 GΩ
±2.0000 V 100 µV 0.01% FS ± 2 cts 1 GΩ
±20.000 V 1 mV 0.01% FS ± 2 cts 10 MΩ
±200.00 V 10 mV 0.01% FS ± 2 cts 10 MΩ
±600.0 V* 100 mV ± 0.4 V 10 MΩ
DC Current ±2.0000 mA 0.1 µA 0.01% FS ± 2 cts 100 Ω
±20.000 mA 1 µA 0.01% FS ± 2 cts 10 Ω
±200.00 mA 10 µA 0.01% FS ± 2 cts 1 Ω
±5.000 A 1 mA ±10 mA 0.01 Ω
* Range not ETL certified.
Reading Resolution 16 bits (65,536 steps)
Reading Accuracy 0.01% of full scale ± 2 counts (except 5A range) for absolute measurements.
0.01% of reading ± 2 counts for ratiometric measurements.
Update Rate, Max 50/sec at 50 Hz, 60/sec at 60 Hz
Max applied voltage 600 Vac for 20, 200 & 600 V ranges, 125 Vac other ranges
Over-current protection 25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, 1x for 5 A
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.
Analog Output (standard)
Output Levels 0-20 mA or 0-10 Vdc (selectable)
Compliance, 4-20 mA 10V (0-500Ω load)
Compliance, 0-10V 2 mA (5 kΩ load)
Output Resolution 16 bits (65,536 steps)
Output Accuracy 0.02% of output span plus conversion accuracy
Output Isolation 250V rms working, 2.3 kV rms per 1 minute test
Ethernet Data I/O (standard)
Type 10/100 Base-T Ethernet per IEEE 802.3
Data Rates 300, 600, 1200, 2400, 4800, 9600, 19200 baud
Output Isolation 250V rms working, 2.3 kV rms per 1 min test
Serial Protocol Modbus TCP
Modbus Compliance Modbus over Serial Line Specification V1.0 (2002)
Digital Addresses 247
Dual Relay Output (standard)
Relay Type Two solid state relays, SPST, normally open, Form A
Load Rating 120 mA at 140 Vac or 180 Vdc
Excitation Output (standard)
5 Vdc 5 Vdc ± 5%, 100 mA (jumper selectable)
10 Vdc 10 Vdc ± 5%, 120 mA (jumper selectable)
12 Vdc 12 Vdc ± 5%, 100 mA (jumper selectable)
24 Vdc 24 Vdc ± 5%, 50 mA (jumper selectable)
Output Isolation 50 Vdc from signal ground
Ratiometric operation 5 Vdc or 10 Vdc for bridge circuits, 5 Vdc for potentiometers
Power Input
Standard Power 85-264 Vac or 90-300 Vdc
Low Power Option 10-48 Vdc or 12-32 Vac
Power Frequency DC or 47-63 Hz
Power Isolation 250V rms working, 2.3 kV rms per 1 min test
Power Consumption 2.5W typical at 34V, 4.0W with max excitation output
Mechanical
Dimensions 129 x 104 x 22.5 mm case
Mounting 35 mm rail per DIN EN 50022
Connectors Detachable screw-clamp connectors for signal and power RJ45 jack for Ethernet
Signal Connections
process meter electrical connections
Environmental
Operating Temperature -40°C to 70°C (-40°F to 158°F)
Storage Temperature -40°C to 85°C (-40°F to 185°F)
Relative Humidity 95% at 40°C, non-condensing
Cooling Required Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan.
Mechanical
Enclosure Rugged black polycarbonate housing material
Mounting 35 mm rail per DIN EN 50022
Dimensions 129 x 104 x 22.5 mm case
Connectors Detachable screw clamp connectors meet VDE / IEC / UL / CSA standards. RJ45 jack for Ethernet
Tightening Torque Screw terminal connectors: 5 lb-in (0.56 Nm)
Weight Complete transmitter: 183 g (6.5 oz)
Replacement Case Screws
Size 6
Thread Pitch 6-19
Length 1/2"
Head Style Pan Head
Drive Style Phillips
Head Diameter 0.256-0.270
Head Height 0.087-0.097
Full/Partial Thread Full
Drive Size 2
Material Steel
Finished Black Oxide
General
Programming Utilize Laurel's free Instrument Setup Software, which runs on a PC under MS Windows. 
Security Lockout options available using Laurel's free Instrument Setup Software.
Warranty 3 years parts & labor
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.

Transmitter Pinout

LTE Ethernet Transmitter Pinout

Custom curve linearization

Using a linearizing digital panel meter or transmitter

A Laureate process meter or transmitter with the Extended main board option allows exceptionally accurate custom curve linearization. For setup, up to 180 data points can be entered into a spreadsheet. The system then creates multiple non-linear spline-fit segments, which provide much better accuracy than linear segments. One application, as illustrated, is the readout of volume of irregularly shaped tanks based on measured liquid level or pressure. Altimeters and thermistors are further applications.

 

Free Instrument Setup Software for Series 2 Laureates

Digital Panel Meter Laurel Electronics Digital Transmitters
1/8 DIN Digital Panel Meters DIN Rail Transmitters

Free Downloadable Windows-based Instrument Setup (IS) software (Data Interface Board Required) for use with our programmable Digital Panel Meters, Scale Meters, Counters, Timers, Remote Displays, and Transmitters, are an easy method to set up Laureate 1/8 DIN digital panel meters, counters, timers, remote displays, and DIN-rail transmitters, as explained in the Instrument Setup Software Manual. Laureate 1/8 DIN instruments can also be set up from the front panel, as explained in their respective Owners Manuals. Instrument Setup software is of benefit whether or not the PC is connected to the instrument.

  • When the PC is connected to the instrument, Instrument Setup software can retrieve the setup file from the instrument or open a default setup file or previously saved setup file from disk View Setup, then provides graphical user interface (GUI) screens with pull-down menus applicable to input, display, scaling, filtering, alarms, communications, analog output, and front panel lockouts. Fields that are not applicable to the instrument as configured are either left out or grayed out. Clicking on any item will bring up a detailed Help screen for that item. After editing, the setup file can be downloaded, uploaded to the instrument, or saved to a disk. The same setup file can then be downloaded into multiple instruments.
  • When the PC is not connected to the instrument, the above GUI screens can be used to set up a virtual instrument. The setup file can then be saved to disk. Switching toView Menu then brings up a screen with the required front panel programming steps. This view can be printed out for use at the instrument site and to serve as a hard copy record.

    Download Free Instrument Setup Software


Installation

Set User Account Control (UAC) of MS Windows to "Never notifiy me" so that Instrument Setup Software can create directories. The UAC change screen can be reached as follows:

  • Under Windows 7, click on the Windows Start button in the lower left of the desktop and enter "UAC" in the search field.
  • Under Windows 8, navigate to Control Panel, then to the "User Accounts and Family Safety" section, and click on "Change User Account Control Settings."
  • Under Windows 10, click on the Windows Start button in the lower left of the desktop, then on "Settings", and enter "UAC" in the search field.
  • Reboot your computer for the changed UAC setting to take effect.
Meter board with USB Type-B connector

RJ11-to-DB9 cable with rear view of DB9 connector to PC

Laurel USB cable, P/N CBL05

RS232 cable, meter to PC, P/N CBL01

Laureate 1/8 DIN Laureate instruments must be equipped with a serial communications board and be connected to the computer via a serial communications cable. The connection can be via RS232, RS485, USB or Ethernet. Following setup, the serial communications board may be removed from the instrument if desired. The wiring of the RS232 cable is illustrated above with end views of the two connectors.

Laureate LT Series transmitters come standard with a 3-wire serial interface, which can be jumpered for RS232 or RS485.
Laureate LTE Series transmitters come standard with an Ethernet interface.

Meter Setup Screens

Click on any of the reduced screens below for a full-size screen view, then click on the Back button of your browser to return to this page. The screens examples below are for a fully-loaded Series 2 Digital Panel Meter (DPM), which is connected to the PC via RS232. If the meter is a Series 1 meter (pre-2007), this is sensed by the software, and somewhat different screens are brought up. Please see Series 1 setup screens.

Laurel Dual Channel Pulse Input Rate Meter
Welcome Screen
From the computer desktop, click on Start > Programs > IS2 > IS2. Or click on the IS icon on your desktop. This splash screen will be displayed for three seconds. The software revision number is in the lower right.
more
Setup Screen 02s for Digital Panel Meters and Digital Transmitters
Communications Selection Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 3 for Digital Panel Meters and Digital Transmitters
Establish Communications Screen
If you selected RS-232, you will be asked to specify the PC Com Port and Baud Rate, which should match the jumper setup of the instrument. Click on Establish. With the right settings, the Communications Established field will light up in green, and the Meter Type will be recognized. If so, click onMain Menu.
more
Setup Screen 4 for Digital Panel Meters and Digital Transmitters
Main Menu Screen
Click on File > Default Setup to retrieve the default setup file from disk for your type of meter. Click on File > Open Setupto retrieve a previously saved setup file from disk or on File > Save Setup to save your edited setup file to disk. Click onDPM > Get Setup to retrieve the setup file from your meter or on DPM > Put Setup to download your edited setup file into the meter.
more
Setup Screen 5 for Digital Panel Meters and Digital Transmitters
DPM Input + Display Setup Screen
From the Main Menu, click on View > Setup, then on theInput+Display tab. You can now specify the meter hardware, signal type, display mode, and functions of control inputs A and B. Clicking on any item brings up a pull-down menu with the available choices.
more
Setup Screen 6 for Digital Panel Meters and Digital Transmitters
DPM Scaling Setup Screen
Click on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 7 for Digital Panel Meters and Digital Transmitters
DPM Filter Setup Screen
Click on the Filter tab, which allows you to specify the digital filter time constant (if any), the adaptive filter threshold, and whether Peak / Valley values are filtered or unfiltered. As for all setup screens, clicking on the F1 key while an item is highlighted brings up a Help screen for that item, as illustrated.
more
Setup Screen 8 for Digital Panel Meters and Digital Transmitters
DPM Relay Alarms Setup Screen
Click on the Relay Alarms tab, which allows you to set up Alarms 1 and 2 for the optional dual relay output board. Clicking on any of the four numeric fields changes these to green and brings up a special field to enter the desired numeric value, which is tied to the displayed reading.
more
Setup Screen 9 for Digital Panel Meters and Digital Transmitters
DPM Communications Setup Screen
Click on the Communications tab so set up serial communications. In particular, you can special the Serial Protocol and the meter address if multiple meters are to be addressed on the same serial data line.
more
Setup Screen 10 for Digital Panel Meters and Digital Transmitters
DPM Analog Output Setup Screen
Click on the Analog Out tab so set up the optional analog output board. Three output ranges are selectable, the endpoints of which can be tied to user-specified High and Low readings.
more
Setup Screen 11 for Digital Panel Meters and Digital Transmitters
DPM Lockouts Setup Screen
Click on the Lockouts tab to check off menu items which will no longer be accessible from the front panel of the meter. This will simplify meter operation and prevent unintended setup changes.
more

Meter Setup Utilities

Setup Screen 12 for Digital Panel Meters and Digital Transmitters
DPM Front Panel Setup Screen
As an aid to programming the meter from the front panel when a serial connection is not available, you can return to the Main Menu and click on View > Menu. The required sequence of front panel screens will then be displayed. Click on any step in the sequence for the meaning of each digit, as illustrated for the FILtEr step. For a hardcopy, simply press on Print.
more
Setup Screen 13 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 14 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screens
Click on any of the displayed plug-in boards, and you will be presented with the jumper positions and electrical connections for your selected board. This minimizes the need to refer to the printed manual.
more
Setup Screen 15 for Digital Panel Meters and Digital Transmitters
DPM Commands Screen
This page allows you set up external input, serial communications, an analog output proportional to the display (optional), and lockouts for Laureate digital counters. The grayed out area at the top right of the screen applies to Laureate remote displays.
more
Graphical Output Screens (not available with Ethernet)

From the Main Menu, click on Readings if your PC is connected to the meter. A pull-down menu then offers three choices: ListPlot and Graph.

  • List presents the latest readings in a 20-row by 10-column table. Press Pause at any time to freeze the display. This is one method to capture peak readings.   
  • Plot generates a plot of readings vs. time in seconds. It effectively turns the DPM-PC combination into a printing digital oscilloscope.
    more 
  • Graph generates a histogram where the horizontal axis is the reading and the vertical axis is the number of occurrences of readings. The display continually resizes itself as the number of readings increases.
    more
Setup Screen 18 for Digital Panel Meters and Digital Transmitters
DPM Calibration Screens
Click on the Scaling tab, which provides three scalClick on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 19 for Digital Panel Meters and Digital Transmitters
Frequency Meter Calibration Screen
Calibration of the quartz crystal of the Laureate frequency meter requires the input of a known frequency from a calibrator. Apply the frequency, then enter the frequency in Hertz. Calibration will be automatic, with storage of the calibration factor stored in non-volatile memory.
more

 

Dimensions

Laurel transmitter case

Dimensioned CAD assembly drawings in EPRT, STEP, x_t, .dwg, pdf file formats: Laureate-transmitter-case.zip (zipping prevents browser from opening CAD files as text files).

 

 

CAL-Analog

Certificate of Calibration

$65.00

CBL02

USB-to-RS232 Adapter Cable

$47.00

CBL04

RS232 Cable for LT Transmitters

$47.00

CBL12

12-foot Power Cable

$47.00

CBL6

6-foot Power Cable

$41.00
Ordering Guide
Part Number as Configured: LTE20P
Price as Configured: $558.00

Click on the Option Board Links for More Product Information

Base Item
$388.00
Main Board
$0.00
Extended allows up to 180 data points for custom curve linearization and a rate derived from consecutive readings.
$33.00
Power (Isolated)
$89.00
$89.00
Signal Input (Isolated)
$81.00
$156.00
$81.00
Note: The same DC signal conditioner can be user configured for DC, process, bridge, and potentiometer signals. It is precalibrated in EEPROM for all DC Volt and DC Amp ranges listed for DC transmitters.
$156.00
Part Number as Configured:
LTE20P
Price as Configured:
$558.00
Quantity:
- +
Extended Price:
$558.00

Understanding the Laureate™ LTE Series DIN Rail Transmitter for Process & Ratiometric Signals

The Laureate™ LTE Series DIN rail transmitter for process signal input provides zero and span adjustment for use with a wide range of industrial transducers. Six DC voltage and four DC current input ranges are jumper selectable. The two most sensitive voltage ranges, 200.00 mV and 2.0000V, provide a high input impedance of 1 GΩ to minimize the load on the voltage signal.

Ratiometric / Potentiometer Follower Mode

The transmitter can be set to a ratio (or potentiometer follower) mode by making selections at the connector and in software. In this mode, the transmitter output tracks a ratio of the applied excitation voltage and is unaffected by changes in the excitation voltage. Ratiometric measurements provide an exceptional accuracy of 0.01% of reading ±2 counts, compared to 0.01% of full scale ±2 counts (except the 5A range) for absolute measurements. This capability is used with the transmitter's 5V or 10V excitation output for load cells and Wheatstone bridges, and with the 5V excitation output for potentiometers tracking wiper position.

Signal Specifications

Input resistance is 1 GΩ on the 200.00 mV and 2.0000V ranges, 10 MΩ on the 20.000V, 200.00V, and 600.0V ranges (the 600.0V range is not ETL certified). Maximum applied voltage is 600 Vac for the 20V/200V/600V ranges, 125 Vac for other ranges. Overcurrent protection is 25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, and 1x for 5A. Update rate is up to 50/sec at 50 Hz or 60/sec at 60 Hz. The same DC signal conditioner board can be user-configured for DC, process, bridge, and potentiometer signals, precalibrated in EEPROM for all DC volt and DC amp ranges.

Custom Curve Linearization

A Laureate process transmitter with the Extended main board option allows exceptionally accurate custom curve linearization. Up to 180 data points can be entered into a spreadsheet; the system then creates multiple non-linear spline-fit segments, which provide much better accuracy than linear segments. One application is the readout of volume in irregularly shaped tanks based on measured liquid level or pressure. Altimeters and thermistors are further applications.

Ethernet Data I/O

Standard Ethernet Data I/O is 10/100 Base-T per IEEE 802.3, isolated to 250V rms working / 2.3 kV rms per 1 minute test. The supported serial protocol is Modbus TCP at digital address 247. Analog output levels are 0-20 mA or 0-10 Vdc (selectable), with 16-bit resolution and 0.02% of output span accuracy plus conversion accuracy.

Where LTE Process & Ratiometric Transmitters Are Used

  • Networked Tank Level & Volume Monitoring — custom curve linearization with Ethernet-connected level output.
  • Bridge & Wheatstone Circuit Signal Conditioning — ratiometric measurement immune to excitation drift.
  • Potentiometer Position Feedback — networked wiper-position tracking for valve or actuator position.
  • Nonlinear Sensor Linearization — altimeters, thermistors, and irregular-vessel level sensors.
  • Multi-Point Networked Process Monitoring — several transmitters on one Modbus TCP network.
  • OEM Networked Process Instrumentation — DIN rail integration into Ethernet-based control panels.

LTE Process & Ratiometric Transmitter Frequently Asked Questions

Why does ratiometric mode specifically use "0.01% of reading" accuracy while absolute mode uses "0.01% of full scale" accuracy?

Documented specification lists these as two separate accuracy formulas tied to how each mode processes the signal — ratiometric mode's documented immunity to excitation voltage changes means its accuracy tracks the actual reading itself, while absolute mode's documented accuracy is instead pegged to the fixed full-scale range regardless of where the actual reading falls; this reflects a genuine difference in what each mode's accuracy figure is mathematically referenced against.

Why does potentiometer follower mode specifically use only 5V excitation, while bridge/load cell ratiometric mode can use either 5V or 10V?

The page documents 5V or 10V excitation as available for bridges and load cells, but specifically lists only 5V for potentiometers, without detailing the underlying reason for this narrower option — this is consistent with the documented excitation options simply differing by application type as specified, so a potentiometer follower application should be configured with the documented 5V excitation rather than assuming the 10V option is also available for that specific use case.

Does the documented note that "the same DC signal conditioner can be user configured for DC, process, bridge, and potentiometer signals" mean all four modes are active simultaneously?

No — documented phrasing specifically describes the single physical signal conditioner board as being configurable across these different signal types, which is consistent with one mode being selected via jumper and software settings at a time, not multiple modes operating concurrently; this reflects hardware flexibility (one board serving several distinct application types) rather than simultaneous multi-mode operation.

Why is the ±600.0V range specifically documented as "not ETL certified," while the other five voltage ranges are not flagged this way?

Documented footnote specifically marks only the ±600.0V range with this qualifier, distinct from the LTE DC Voltage/Current transmitter's separate footnote phrasing ("certified to ±300.0V") for its own ±600.0V range — this indicates the two pages document this same top voltage range's certification status somewhat differently, so the precise certification scope for the 600V range should be confirmed against whichever specific transmitter model is actually being specified.

Does selecting the SG1 custom scaling option change this transmitter's documented core measurement accuracy from the standard SG option?

No — documented SG1 option describes custom scaling (specifying min/max input and corresponding min/max reading) as a configuration choice for how raw signal maps to a displayed value, not as a change to the underlying signal conditioning accuracy; both SG and SG1 use the same documented DC/process signal conditioner hardware and share the same documented accuracy specifications.

Can custom curve linearization correct for a nonlinearity that exists in the sensor itself, or only for nonlinearity in the physical vessel being measured?

Documented examples specifically include altimeters and thermistors alongside irregular tank volume as applications for custom curve linearization — since altimeters and thermistors are sensors with their own documented nonlinear response characteristics (distinct from a tank's physical shape), this indicates the documented linearization capability is general-purpose, applicable to correcting nonlinearity from the sensor itself just as much as from the physical geometry of a measured vessel.

Does this LTE Process transmitter's documented Modbus TCP-only protocol limit compatibility compared to the RS232/RS485 LT Series process variant's documented broader protocol set?

Yes — this page documents Modbus TCP specifically as the supported Ethernet Data I/O protocol at digital address 247, while the LT Series serial variant is documented elsewhere as separately supporting Modbus RTU/ASCII and Laurel Custom ASCII; a control system needing a protocol other than Modbus TCP would need to reference the LT Series serial variant rather than this LTE Ethernet variant.

Does the transmitter's documented 1 GΩ input impedance on the two most sensitive voltage ranges serve a specific purpose in ratiometric bridge applications?

Yes, in principle — documented description specifically ties this high input impedance to minimizing load on the voltage signal being measured; in a ratiometric bridge application, drawing minimal current from the bridge output is consistent with preserving the bridge's own balance and the accuracy of the ratiometric reading, similar to how high input impedance is documented as beneficial for other sensitive DC voltage measurements across the LT/LTE family.

Does choosing the Extended main board for custom curve linearization change the transmitter's documented Ethernet or analog output specifications?

No — documented Extended board capability (custom curve linearization with up to 180 data points, plus rate derived from consecutive readings) is described as an additive processing feature layered on top of the underlying measurement and output path; the documented Ethernet Data I/O and analog output specifications (16-bit resolution, 0.02% output accuracy, Modbus TCP at address 247) apply the same way regardless of whether the Standard or Extended main board is selected.

Can the P1 and SG1 custom scaling options both be used to scale a 4-20 mA input, or is P1 specifically required for that signal type?

Documented default scaling for the P option is specifically "4-20 mA in = 4-20 mA out," while the SG option's documented default is "0-200 mV = 0-100.00" — this indicates P (and its custom-scaling counterpart P1) is the documented option specifically intended for a 4-20 mA process signal, while SG/SG1 is documented as oriented toward millivolt-level bridge/strain gauge signals, so P1 is the more directly applicable documented choice for scaling a 4-20 mA input specifically.

Tank Strapping Table & Nonlinear Level Calibration Questions From the Field

What specifically is a tank strapping table, and why do non-linear tanks require one?

Documented definition specifically describes a strapping table (also called a tank calibration chart, tank gauge chart, or dip chart) as a lookup converting a measured level into a corresponding volume — documented explanation specifically notes non-linear tanks can't have their volume calculated from level using simple mathematical equations, since volume doesn't change proportionally with level in a non-cylindrical or irregularly shaped vessel, which is specifically why a table-based conversion is documented as necessary.

Does simple linear interpolation between adjacent strapping table points provide the same accuracy as more sophisticated interpolation methods?

Not necessarily — documented patent-level description specifically contrasts basic linear interpolation between two adjacent table entries with higher-order polynomial interpolation methods (citing third, fourth, and fifth order polynomial interpolations, specifically referencing Neville's algorithm), noting that documented testing shows these higher-order methods can provide a more accurate strap volume than simple linear interpolation between just two points.

Does the accuracy of a tank's volume readout improve simply by adding more data points to the strapping table?

Yes, generally — documented explanation specifically states that within each "strap" (interval between table points), volume is linearly interpolated with level, so a greater number of straps in the table is documented as directly producing more accurate volume indication; more closely spaced data points reduce the error introduced by interpolating across each individual gap.

Is there a documented best practice for how strapping table data points should be distributed along a tank's height, rather than spacing them evenly?

Yes — documented field experience specifically describes most real-world dip tables as having more data points clustered specifically in regions of greatest non-linearity (such as a tank's rounded ends or dished heads), with relatively few data points needed for the straight cylindrical bulk of the vessel where volume changes linearly with level; this uneven, non-linearity-driven spacing is documented as standard practice rather than using uniform spacing throughout.

Can a strapping table generated for one specific physical tank be reused for a different tank of the same nominal size and shape?

Not reliably, according to documented guidance — documented explanation specifically notes that variations in tank manufacturing make a custom strap chart developed for one particular tank necessary, since manufacturing variation between individually built tanks means even nominally identical tanks can have real dimensional differences that a shared generic strapping table wouldn't capture.

Does the chemical composition or type of liquid stored in a tank affect the validity of its strapping table?

No — documented explanation specifically states that tank calibration via a strap chart is performed independent of the type of liquid in the tank, since the strapping table maps physical level to physical volume based on the tank's geometry alone; the same strap chart is documented as reusable across different liquids, since chemical composition doesn't affect the level-to-volume geometric relationship the table describes.

How were strapping tables traditionally generated before modern electronic level sensors and linearization capability existed?

Documented history specifically traces the term "strapping" itself to the traditional method of wrapping a steel measuring tape (a "strap") around the outside of a storage tank at different heights to physically measure and calibrate the vessel; documented modern practice has largely replaced this manual method with laser levels and ultrasonic thickness gauges for generating the same underlying table.

Once a strapping table has been generated for a tank, is there a documented method to load it directly into a transmitter or level sensor rather than maintaining it as a separate paper or PLC reference?

Yes — documented product examples specifically describe modern level sensors accepting a strapping chart programmed directly into the sensor itself, commonly via a communication protocol such as Modbus; documented setup for this approach involves assigning a volume value to a series of known level measurements, after which the sensor uses those stored points to linearize its own continuous volume output going forward.