Understanding the Laureate™ LTE Series DIN Rail Transmitter for Load Cell & Microvolt Input
The Laureate™ LTE Series DIN rail transmitter for load cell or microvolt input is designed for load cells, strain gauges, and microvolt input signals where exceptional sensitivity and stability are required. The most sensitive full-scale input range, ±20 mV, can be scaled internally to ±99,999 counts. The selected input range for the full 0-20 mA output span can be as wide as ±99,999 counts or as narrow as 150 counts, limited only by electrical noise and the time constants of the programmable moving average digital filter.
Ratiometric vs. Absolute Accuracy
Serial data is accurate to ±0.01% of reading ±2 counts in ratiometric load cell mode, and ±0.01% of full scale ±2 counts in absolute microvolt mode. Five full-scale ranges are available: ±20.000 mV, ±50.0000 mV, ±100.00 mV, ±250.00 mV, and ±500.00 mV, all with 1 GΩ input impedance. In microvolt mode, resolution scales with range from 1 µV at ±20.000 mV to 25 µV at ±500.00 mV. Maximum applied voltage is 100V. Update rate is up to 50/sec at 50 Hz or 60/sec at 60 Hz.
4-Wire and 6-Wire Load Cell Connections
In 4-wire connection, the excitation and sense lines are tied together; the transmitter makes ratiometric corrections for supply voltage variations but does not compensate for variations in lead resistance — often used with short cable runs. In 6-wire connection, sense lines are separate from excitation lines, eliminating effects due to lead resistance variation and allowing long cable runs in outdoor environments with temperature extremes. For large scales, up to four 350-ohm load cells can be powered by a single Laureate, whose excitation output is rated 120 mA at 10V, with excitation and sense points of the bridges connected in parallel; load cell outputs are averaged if the load cells share the same mV/V sensitivity.
Ethernet Data I/O
Standard Ethernet Data I/O is 10/100 Base-T per IEEE 802.3, isolated to 250V rms working / 2.3 kV rms per 1 minute test. The supported serial protocol is Modbus TCP at digital address 247, compliant with the Modbus over Serial Line Specification V1.0 (2002). Analog output levels are 4-20 mA, 0-20 mA, or 0-10 Vdc (jumper selectable), with 16-bit resolution and 0.02% of output span accuracy plus conversion accuracy. Power consumption is 2.5W at 24V, 4.0W at max excitation output — the transmitter is powered through its own standard AC/DC power input (85-264 Vac or low-voltage 10-48 Vdc/12-32 Vac options), separate from its Ethernet data connection.
Factory-Calibrated Accuracy
All signal conditioner board ranges are factory-calibrated, with calibration factors stored in EEPROM, enabling field replacement of signal conditioner boards without necessitating recalibration of the transmitter. Factory recalibration is recommended annually. The optional Extended computer board displays rate derived from successive readings and allows custom curve linearization using up to 180 data points.
Where LTE Load Cell & Microvolt Transmitters Are Used
- Networked Weighing Systems — direct Ethernet connection to SCADA/PLC for scale and hopper weight monitoring.
- Remote-Site Load Cell Monitoring — bridge signal conditioning at locations reached via existing Ethernet infrastructure.
- Structural Health Monitoring Networks — distributed strain gauge readings reported over a common network.
- Multi-Scale Networked Installations — several transmitters on one Modbus TCP network reporting to a central controller.
- Laboratory & Test Stand Force Measurement — networked microvolt-level force/strain data acquisition.
- OEM Networked Weighing Instrumentation — DIN rail integration into Ethernet-based control panels.
LTE Load Cell & Microvolt Transmitter Frequently Asked Questions
Is this LTE transmitter itself powered via Power over Ethernet (PoE), given "power over ethernet" appears among the page's listed keywords?
No — documented Power Input specification lists standard AC/DC power options (85-264 Vac or 90-300 Vdc standard, with 10-48 Vdc or 12-32 Vac as a low-power option), separate and distinct from the transmitter's Ethernet Data I/O connection; the transmitter's own power input is documented independently of its network cable, so PoE is not documented as this transmitter's actual power source despite the term's appearance among the page's general keyword list.
Why does this LTE transmitter's documented analog output include 4-20 mA, unlike the DC Voltage/Current LTE variant's documented 0-20 mA/0-10V-only output set?
Documented analog output levels for this load cell/microvolt LTE transmitter specifically list "4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)" — a genuinely different, broader set than documented on some other LTE Series variants; this reflects that documented output level options can differ by specific transmitter model within the LTE family, so the exact available options should be confirmed against each individual product's own specification table.
Does choosing ratiometric load cell mode versus absolute microvolt mode change which accuracy specification applies?
Yes — documented specification lists two separate accuracy figures for these two modes: ±0.01% of reading ±2 counts in ratiometric load cell mode, versus ±0.01% of full scale ±2 counts in absolute microvolt mode; since "of reading" and "of full scale" accuracy calculations produce different absolute error magnitudes at partial-scale readings, the selected mode genuinely changes how the transmitter's real-world accuracy should be calculated for a given measurement.
Why does the 6-wire connection specifically enable longer cable runs in outdoor environments with temperature extremes, compared to the 4-wire connection?
Documented description specifically attributes this to the 6-wire connection's separate sense lines eliminating effects due to variations in lead resistance — since lead resistance itself changes with temperature and cable length, the documented 4-wire connection (where excitation and sense are tied together) accumulates this temperature- and length-dependent error, while the 6-wire connection's independent sense path is documented as specifically avoiding it, which is why 6-wire is the documented choice for longer, more thermally variable cable runs.
Does connecting up to four 350-ohm load cells in parallel to a single transmitter require the load cells to be identical models?
Not necessarily identical models, but they must share a specific characteristic — documented description specifically states load cell outputs "will be averaged if the load cells have the same sensitivity in mV/V," meaning the specific requirement documented is matched mV/V sensitivity across the paralleled load cells, rather than requiring identical model numbers; load cells from different sources with matching documented sensitivity specifications would be consistent with this stated averaging behavior.
Does this transmitter's documented Modbus TCP-only protocol support limit which control systems can poll it, compared to the RS232/RS485 LT Series variant's broader documented protocol set?
The LTE variant's documented Ethernet Data I/O supports Modbus TCP specifically at digital address 247, while the LT Series serial variant is documented elsewhere as separately supporting Modbus RTU/ASCII and Laurel Custom ASCII protocols — a control system needing a protocol other than Modbus TCP would need to reference the LT Series serial variant instead, since this specific LTE page documents Modbus TCP as the supported protocol for its Ethernet interface.
Does the documented maximum applied voltage of 100V represent a working measurement limit, or a survivable overvoltage limit before damage?
Documented specification lists "Max applied voltage: 100 V" as a single figure without separately distinguishing normal operating range from a documented overvoltage survival rating — given the transmitter's documented full-scale ranges top out at ±500.00 mV, a 100V figure sits far above the intended measurement span, consistent with this being documented as a protective maximum the input circuitry can tolerate without damage, rather than a range within which accurate measurement is expected.
Can the Extended board's custom curve linearization be applied to correct for known nonlinearity in a specific load cell's response?
Documented capability describes the Extended board's custom curve linearization generally as extending accuracy for applications like tank volume calculation from level readings, without restricting its use case to flow or level applications specifically — since custom curve linearization is documented as accepting up to 180 user-supplied data points to build a spline-fit correction, this general capability is consistent with also being applied to correct a load cell's known nonlinear response, provided the correcting data points are supplied during setup.
Does selecting the WM1 custom scaling option change the transmitter's documented core accuracy specifications from the standard WM option?
Documented WM1 option describes custom scaling (specifying min/max input and corresponding min/max displayed reading across a 20-500 mV span) as a configuration choice for how raw signal is mapped to a displayed reading, not as a change to the transmitter's underlying signal conditioning accuracy; the documented accuracy specifications in the main table are consistent with applying to both WM and WM1 configurations, since both use the same underlying load cell signal conditioner hardware.
Does the transmitter's documented 1 GΩ input impedance on the load cell ranges serve the same purpose as the 1 GΩ impedance documented on the most sensitive LT Series DC voltage ranges?
Yes, in principle — both are documented as minimizing loading on a sensitive, typically low-power source signal; for load cells specifically, documented high input impedance helps ensure the transmitter draws negligible current from the bridge output, similarly to how the same high impedance figure on sensitive DC voltage ranges is documented as minimizing load on the measured voltage signal, reflecting a shared design principle across the LT/LTE family's most sensitive input ranges.
Power over Ethernet (PoE) Deployment Questions From the Field
What is the documented maximum cable distance for standard Power over Ethernet, and what specifically limits it?
Documented standard specifically limits PoE transmission to 100 meters (about 328 feet) per standard twisted-pair Ethernet cabling specifications — documented explanation notes that beyond this distance, wire resistance, heat generation, and electromagnetic interference begin degrading the data signal, leading to attenuation and eventual packet loss, which is why this figure represents a hard, physics-based ceiling rather than an arbitrary standards choice.
Does voltage drop over a PoE cable run increase in direct proportion to cable distance?
Yes — documented explanation specifically states that as PoE transmission distance increases, voltage drop increases proportionally, which is a genuinely different and compounding problem on top of the general data-signal attenuation that also worsens with distance; both effects are documented as growing together as cable length approaches the standard's maximum.
Are there documented solutions for extending PoE-powered device deployments beyond the standard 100-meter cable limit?
Yes — documented industrial solutions specifically include PoE injectors and extenders designed to deliver power and data over a single Ethernet cable to remote sites, with one documented example specifically citing a Gigabit-rated, IP30-rated, DIN-rail-mountable injector unit backward-compatible with earlier PoE standards, specifically engineered to address long cable runs in remote industrial deployments.
Does heat generation from PoE current specifically require ambient temperature-based safeguards in real deployments?
Yes — documented technical description specifically identifies current passing through PoE cable conductors as a genuine source of heat generation, with documented safeguards designed to lower the current limit if ambient temperature exceeds a specified threshold (one documented example cites 45°C) to prevent the system from reaching an unsafe operating temperature (documented as 60°C in that same example).
Do PoE systems have built-in protections against overload conditions that could damage connected equipment?
Yes — documented guidance specifically states that PoE switches and devices have built-in safeguards monitoring power usage, which can shut down or limit power delivery if an overload is detected; this documented protection specifically aims to reduce the risk of overheating or fire in both the power sourcing equipment and the powered device.
Can a remote monitoring system automatically detect and recover a nonresponsive PoE-powered device without a site visit?
Yes — documented system design specifically describes a monitoring device detecting nonresponsive PoE devices connected through a network switch, and automatically instructing the switch's API to power-cycle either the specific nonresponsive port or the entire switch, depending on how many devices are found nonresponsive; this documented remote power-cycling capability is specifically aimed at reducing the need for in-person site visits to recover a stalled device.
Is proper network design and cabling planning specifically documented as necessary before large-scale industrial PoE rollout, or can it generally be added ad hoc?
Documented industry guidance specifically recommends organizations properly plan PoE deployment in advance — considering appropriate power sources, proper cabling, and overall network design — rather than treating it as an incremental, ad hoc addition; this documented planning emphasis reflects that power delivery, not just data connectivity, becomes a genuine design constraint once PoE is deployed at scale.
Beyond powering cameras and lighting, is PoE documented as enabling broader industrial data collection strategies at remote or unmanned sites?
Yes — documented field description specifically frames PoE-enabled remote connectivity as an "operational intelligence layer," citing real-time visibility from IoT sensors streaming process performance, machine health, energy consumption, and environmental data back to centralized systems; this is documented as particularly relevant at remote sites that run with minimal or zero onsite personnel, where a reliable networked power-and-data backbone becomes mission-critical infrastructure.




























