LTE DIN Rail Digital Transmitters with Ethernet Communication and Analog Outputs for Duty Cycle and Pulse Width Modulation Applications

LTE DIN Rail Digital Transmitters with Ethernet Communication and Analog Outputs for Duty Cycle and Pulse Width Modulation Applications

Price: $613.00
  • P/NLTE80FR
- +

Features

  • Transmits duty cycle with resolution of 1%, 0.1% or 0.01%.
  • Transmits pulse width modulated (PWM) signal inputs in engineering units
  • Frequencies from 0.005 Hz to 10 kHz
  • Inputs from NPN or PNP proximity switches, contact closures, digital logic, magnetic pickups down to 12 mV, or AC inputs up to 250 Vac.
  • Takes ratio of ON or OFF period and total period.
  • Triggers on positive or negative pulse edges.
  • 4-20 mA, 0-20 mA, 0-10V or -10V to +10V transmitter output, (isolated)
  • Analog output resolution 0.0015%  of span, accuracy ±0.02%  of span
  • Ethernet data I/O, Modbus TCP
  • Dual 120 mA solid state relays for alarm or control (isolated)
  • 5V, 10V, 12V, or 24V dc transducer excitation output (isolated)
  • Power 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac (isolated)
  • DIN rail mount housing, 22.5 mm wide, detachable screw-clamp connectors
  • Operating temperature from -40°C to 70°C (-40°F to 158°F)
  • Extended allows up to 180 data points for custom curve linearization and a rate derived from consecutive readings

The Laureate™ LTE Series DIN rail analog transmitter with ethernet communication and analog outputs for versatile connectivity.

The digitally programmable transmitter features two relays for alarm or control. The series offers exceptional accuracy with Input frequencies from 0.005 Hz to 1 MHz. The LTE Series transmitters offer the same high performance, signal conditioning, and programmable features as Laureate digital panel meters, counters, and timers.

Clock diagram, 4-20 mA duty cycle transmitter

The Laureate 4-20 mA, 0-20 mA, 0-10V or -10V to +10V and ethernet output transmitter for duty cycle is a measure of ON or OFF period as a percentage of total period. Duty cycle is determined by averaging an integral number of periods over a gate time which is selectable from 10 ms to 199.99 s. The same signal is applied to Channels A and B. The transmitter divides the average pulse width t by the period P between pulses and expresses the ratio t/P in percent. A resolution of 1%, 0.1% or 0.01% is selectable. By selecting leading or falling pulse edges, ON or OFF duty cycle can be transmitted.

Pulse Width Modulation (PWM) is a transducer output format where the measured information is provided as duty cycle applied to a constant frequency, such as 120 Hz. As for duty cycle, the transmitter divides the average pulse width by the period between pulses over a gate time which is selectable from 10 ms to 199.99 s. It then scales this ratio mathematically to transmit this ratio in engineering units, such as relative humidity (RH).

The Laureate duty cycle & pulse width modulation transmitter uses an Extended counter transmitter main board and the FR dual-channel signal conditioner board, which accepts signals from 12 mV to 250 Vac, inputs from proximity switches with an PNP or NPN output, TTL or CMOS logic, and contact closures. Jumper selections provide optimum operation for different sensor types and noise conditions. A built-in (isolated) 5, 10, or 24 Vdc excitation supply can power proximity switches and other sensors.

Exceptional Accuracy and Stability. Laureate transmitters determine frequency by taking the inverse of period as measured with a calibrated quartz crystal time base. This results in extremely accurate and stable 6-digit internal readings (±999,999 counts), which are then processed in software. The analog output is generated by an ultra-linear 16-bit (65,536 step) digital-to-analog converter (DAC) for 0.02% output accuracy. The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control.

The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control.

All signal conditioner board ranges are factory-calibrated, with calibration factors for each range securely stored in an onboard EEPROM. These factors can be scaled via software to accommodate external shunts, enabling field replacement of signal conditioner boards without necessitating recalibration of the associated transmitter. For optimal accuracy, factory recalibration is recommended annually. All Laurel Electronics instruments undergo factory calibration using the industry-leading Fluke calibrators, which are recalibrated yearly and certified traceable to national standards, ensuring the highest level of precision and reliability.

Laureate Transmitters are easily programmed with Laurel’s free Instrument Setup Software, downloadable from our website and compatible with Windows PCs, requiring a data interface board for setup.

Standard Features of Laureate LTE Transmitters Include:

  • Ethernet I/O, (isolated). The supported protocols are Modbus RTU and ASCII, which are tunneled via Modbus TCP. Note that RS232 or RS485 data I/O is provided by Laurel's LT Series transmitters.
  • 4-20 mA, 0-20 mA or 0-10V analog transmitter output, (isolated), jumper-selectable and user scalable. All selections provide 16-bit (0.0015 ) resolution of output span and 0.02%  output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.
  • Dual-channel pulse inputs for voltage signals, NPN or PNP proximity switches, contact closures, magnetic pickups or flow meters.
  • Dual solid state relays, (isolated). Available for local alarm or control. Rated 120 mA at 130 Vac or 180 Vdc.
  • Selectable transducer excitation output, (isolated), user selectable 5V@100 mA, 10V@120 mA, 12V@100 mA or 24V@50 mA.
  • Power 85-264 Vac, (isolated), low-voltage 10-48 Vdc or 12-32 Vac power is optional.

Digital signal filtering modes can be selected to ensure stable readings in electrically noisy environments.

  • An unfiltered selection provides true peak and valley readings and aids in control applications.
  • A batch average filter selection averages each 16 conversions.
  • An adaptive moving average filter selection provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, the filter adapts by briefly switching to the shortest time to follow the change, then reverts back to its selected time constant. An Auto setting selects the time constant selection based on signal noise.

Peak and valley values are automatically captured. These may be displayed via Laurel's free Instrument Setup Software,  which runs on a PC under MS Windows or can be transmitted as serial data.

Two control inputs (CMOS/TTL levels, logic 0 = tied to digital ground, logic 1 = open) or dry contacts that can be set to control / activate 14 transmitter commands.

An (isolated) 5, 10, 12, or 24 Vdc excitation output is standard to power transducers or two-wire transmitters. Ratiometric operation, which automatically compensates for changes in the applied excitation, is jumper selectable for applications, such as bridges, where the signal to be measured is proportional to the excitation level.

Removable screw terminal connections of Laurel transmitters

LTE series DIN rail transmitters & signal conditioners can be interfaced to a wide range of sensors and transducers using one of seven available plug-in signal conditioner boards. The transmitters duplicate the high performance (high accuracy, high read rate) and extensive programmable features of Laureate 1/8 DIN digital panel meters, counters and timers. They utilize the same signal conditioners boards, much of the same firmware, and Laurel's free Windows-based Instrument Setup Software. They come in a compact DIN rail mount package with detachable screw-clamp connectors for easy wiring.

The LTE series Transmitters accessible from this page include a 4-20 mA, 0-20 mA, 0-10V, or -10V to +10V analog output (isolated, user selectable), an ethernet serial data interface (isolated, user selectable), and dual 120 mA solid state AC/DC relays (isolated). An (isolated) 5, 10, 12, or 24 Vdc transducer excitation output is included with all models other than those with a temperature or AC RMS signal conditioner.

Connecting Laureate LTE Transmitters to a Local Area Network (LAN)

Laurel LTE series Ethernet transmitters can connect directly to a LAN via an Ethernet cable. Up to 30 Laureate LT Transmitters and/or Digital Panel Meters can be configured for RS485 and daisy-chained to an LT Transmitter for seamless LAN integration. Setup for both configurations is streamlined using Laurel’s free Instrument Setup Software, which simplifies node discovery and transmitter configuration. 

Flexible Communication Options for LTE Transmitters

Laureate Transmitters can be equipped with Laurel communication boards to support various interfaces and protocols. These include serial interfaces with ASCII or Modbus RTU protocols, and Ethernet interfaces with web access, ASCII, or Modbus TCP/IP protocols, ensuring versatile connectivity for your commercial applications.

Laureate Ethernet network by Laurel Electronics

Laureate™ Ethernet & 4-20 mA Transmitter for Duty Cycle Input

Duty Cycle Measurement
Item Transmitted ON or OFF duty cycle of periodic pulse waveshape
Displayed Units 1%, 0.1%, 0.01%
Frequency Range 0.005 Hz to 10 kHz
Accuracy 0.01%, 0.005 Hz to 500 Hz, 0.1% at 5 kHz, 1% at 10 kHz
Maximum Timing Interval 199.99 s
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.
Pulse Width Modulation (PWM) Measurement
Item Transmitted Measurement based on Pulse Width Modulation (PWM) input
Displayed Units Scaled reading in engineering units
Frequency Range 0.005 Hz to 10 kHz
Accuracy 0.01%, 0.005 Hz to 500 Hz, 0.1% at 5 kHz, 1% at 10 kHz
Maximum Timing Interval 199.99 s
Update Rate
Conversion Interval Gate time + 30 ms + 0-2 signal periods
Gate Time Selectable 10 ms to 199.99 s
Time Before Zero Output Selectable 10 ms to 199.99 s
Pulse Input
Types AC, pulses from NPN, PNP transistors, contact closures, magnetic pickups
Grounding Common ground for channels A & B.
Minimum Signal Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V)
Maximum Signal 250 Vac
Noise Filter 1 MHz, 30 kHz, 250 Hz (selectable)
Contact Debounce 0, 3, 50 ms (selectable)
Analog Output (standard)
Output Levels 0-20 mA or 0-10 Vdc (selectable)
Compliance, 0-10V 2 mA ( 5 kΩ load )
Output Resolution 16 bits (65,536 steps)
Output Accuracy 0.02% of output span plus conversion accuracy
Output Isolation 250V rms working, 2.3 kV rms per 1 minute test
Ethernet I/O (standard)
Type 10/100 Base-T Ethernet per IEEE 802.3
Data Rates 300, 600, 1200, 2400, 4800, 9600, 19200 baud
Output Isolation 250V rms working, 2.3 kV rms per 1 min test
Serial Protocol Modbus TCP
Modbus Compliance Modbus over Serial Line Specification V1.0 (2002)
Digital Addresses 247
Dual Relay Output (standard)
Relay Type Two solid state relays, SPST, normally open, Form A
Load Rating 120 mA at 140 Vac or 180 Vdc
Excitation Output (standard)
5 Vdc 5 Vdc ± 5%, 100 mA (jumper selectable)
10 Vdc 10 Vdc ± 5%, 120 mA (jumper selectable)
12 Vdc 12 Vdc ± 5%, 100 mA (jumper selectable)
24 Vdc 24 Vdc ± 5%, 50 mA (jumper selectable)
Output Isolation 50 Vdc from signal ground
Power Input
Standard Power 85-264 Vac or 90-300 Vdc
Low Power Option 10-48 Vdc or 12-32 Vac
Power Frequency DC or 47-63 Hz
Power Isolation 250V rms working, 2.3 kV rms per 1 min test
Power Consumption 2.4W typical at 24V, 4W with max excitation output
Environmental
Operating Temperature -40°C to 70°C (-40°F to 158°F)
Storage Temperature -40°C to 85°C (-40°F to 185°F)
Relative Humidity 95% at 40°C, non-condensing
Cooling Required Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan.
Mechanical
Enclosure Rugged black polycarbonate housing material
Mounting 35 mm rail per DIN EN 50022
Dimensions 129 x 104 x 22.5 mm case
Connectors Detachable screw clamp connectors meet VDE / IEC / UL / CSA standards. RJ45 jack for Ethernet
Tightening Torque Screw terminal connectors: 5 lb-in (0.56 Nm)
Weight Complete transmitter: 183 g (6.5 oz)
Replacement Case Screws
Size 6
Thread Pitch 6-19
Length 1/2"
Head Style Pan Head
Drive Style Phillips
Head Diameter 0.256-0.270
Head Height 0.087-0.097
Full/Partial Thread Full
Drive Size 2
Material Steel
Finished Black Oxide
General
Programming Utilize Laurel's free Instrument Setup Software, which runs on a PC under MS Windows. 
Security Lockout options available using Laurel's free Instrument Setup Software.
Warranty 3 years parts & labor
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended every 12 months.

Transmitter Pinout

LTE Ethernet Transmitter Pinout

 

Free Instrument Setup Software for Series 2 Laureates

Digital Panel Meter Laurel Electronics Digital Transmitters
1/8 DIN Digital Panel Meters DIN Rail Transmitters

Free Downloadable Windows-based Instrument Setup (IS) software (Data Interface Board Required) for use with our programmable Digital Panel Meters, Scale Meters, Counters, Timers, Remote Displays, and Transmitters, are an easy method to set up Laureate 1/8 DIN digital panel meters, counters, timers, remote displays, and DIN-rail transmitters, as explained in the Instrument Setup Software Manual. Laureate 1/8 DIN instruments can also be set up from the front panel, as explained in their respective Owners Manuals. Instrument Setup software is of benefit whether or not the PC is connected to the instrument.

  • When the PC is connected to the instrument, Instrument Setup software can retrieve the setup file from the instrument or open a default setup file or previously saved setup file from disk View Setup, then provides graphical user interface (GUI) screens with pull-down menus applicable to input, display, scaling, filtering, alarms, communications, analog output, and front panel lockouts. Fields that are not applicable to the instrument as configured are either left out or grayed out. Clicking on any item will bring up a detailed Help screen for that item. After editing, the setup file can be downloaded, uploaded to the instrument, or saved to a disk. The same setup file can then be downloaded into multiple instruments.
  • When the PC is not connected to the instrument, the above GUI screens can be used to set up a virtual instrument. The setup file can then be saved to disk. Switching toView Menu then brings up a screen with the required front panel programming steps. This view can be printed out for use at the instrument site and to serve as a hard copy record.

    Download Free Instrument Setup Software


Installation

Set User Account Control (UAC) of MS Windows to "Never notifiy me" so that Instrument Setup Software can create directories. The UAC change screen can be reached as follows:

  • Under Windows 7, click on the Windows Start button in the lower left of the desktop and enter "UAC" in the search field.
  • Under Windows 8, navigate to Control Panel, then to the "User Accounts and Family Safety" section, and click on "Change User Account Control Settings."
  • Under Windows 10, click on the Windows Start button in the lower left of the desktop, then on "Settings", and enter "UAC" in the search field.
  • Reboot your computer for the changed UAC setting to take effect.
Meter board with USB Type-B connector

RJ11-to-DB9 cable with rear view of DB9 connector to PC

Laurel USB cable, P/N CBL05

RS232 cable, meter to PC, P/N CBL01

Laureate 1/8 DIN Laureate instruments must be equipped with a serial communications board and be connected to the computer via a serial communications cable. The connection can be via RS232, RS485, USB or Ethernet. Following setup, the serial communications board may be removed from the instrument if desired. The wiring of the RS232 cable is illustrated above with end views of the two connectors.

Laureate LT Series transmitters come standard with a 3-wire serial interface, which can be jumpered for RS232 or RS485.
Laureate LTE Series transmitters come standard with an Ethernet interface.

Meter Setup Screens

Click on any of the reduced screens below for a full-size screen view, then click on the Back button of your browser to return to this page. The screens examples below are for a fully-loaded Series 2 Digital Panel Meter (DPM), which is connected to the PC via RS232. If the meter is a Series 1 meter (pre-2007), this is sensed by the software, and somewhat different screens are brought up. Please see Series 1 setup screens.

Laurel Dual Channel Pulse Input Rate Meter
Welcome Screen
From the computer desktop, click on Start > Programs > IS2 > IS2. Or click on the IS icon on your desktop. This splash screen will be displayed for three seconds. The software revision number is in the lower right.
more
Setup Screen 02s for Digital Panel Meters and Digital Transmitters
Communications Selection Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 3 for Digital Panel Meters and Digital Transmitters
Establish Communications Screen
If you selected RS-232, you will be asked to specify the PC Com Port and Baud Rate, which should match the jumper setup of the instrument. Click on Establish. With the right settings, the Communications Established field will light up in green, and the Meter Type will be recognized. If so, click onMain Menu.
more
Setup Screen 4 for Digital Panel Meters and Digital Transmitters
Main Menu Screen
Click on File > Default Setup to retrieve the default setup file from disk for your type of meter. Click on File > Open Setupto retrieve a previously saved setup file from disk or on File > Save Setup to save your edited setup file to disk. Click onDPM > Get Setup to retrieve the setup file from your meter or on DPM > Put Setup to download your edited setup file into the meter.
more
Setup Screen 5 for Digital Panel Meters and Digital Transmitters
DPM Input + Display Setup Screen
From the Main Menu, click on View > Setup, then on theInput+Display tab. You can now specify the meter hardware, signal type, display mode, and functions of control inputs A and B. Clicking on any item brings up a pull-down menu with the available choices.
more
Setup Screen 6 for Digital Panel Meters and Digital Transmitters
DPM Scaling Setup Screen
Click on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 7 for Digital Panel Meters and Digital Transmitters
DPM Filter Setup Screen
Click on the Filter tab, which allows you to specify the digital filter time constant (if any), the adaptive filter threshold, and whether Peak / Valley values are filtered or unfiltered. As for all setup screens, clicking on the F1 key while an item is highlighted brings up a Help screen for that item, as illustrated.
more
Setup Screen 8 for Digital Panel Meters and Digital Transmitters
DPM Relay Alarms Setup Screen
Click on the Relay Alarms tab, which allows you to set up Alarms 1 and 2 for the optional dual relay output board. Clicking on any of the four numeric fields changes these to green and brings up a special field to enter the desired numeric value, which is tied to the displayed reading.
more
Setup Screen 9 for Digital Panel Meters and Digital Transmitters
DPM Communications Setup Screen
Click on the Communications tab so set up serial communications. In particular, you can special the Serial Protocol and the meter address if multiple meters are to be addressed on the same serial data line.
more
Setup Screen 10 for Digital Panel Meters and Digital Transmitters
DPM Analog Output Setup Screen
Click on the Analog Out tab so set up the optional analog output board. Three output ranges are selectable, the endpoints of which can be tied to user-specified High and Low readings.
more
Setup Screen 11 for Digital Panel Meters and Digital Transmitters
DPM Lockouts Setup Screen
Click on the Lockouts tab to check off menu items which will no longer be accessible from the front panel of the meter. This will simplify meter operation and prevent unintended setup changes.
more

Meter Setup Utilities

Setup Screen 12 for Digital Panel Meters and Digital Transmitters
DPM Front Panel Setup Screen
As an aid to programming the meter from the front panel when a serial connection is not available, you can return to the Main Menu and click on View > Menu. The required sequence of front panel screens will then be displayed. Click on any step in the sequence for the meaning of each digit, as illustrated for the FILtEr step. For a hardcopy, simply press on Print.
more
Setup Screen 13 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screen
Specify your desired communication protocol and the serial communications bus type, which should match the jumper setup of the instrument. Select None if the PC is not connected to the instrument.
more
Setup Screen 14 for Digital Panel Meters and Digital Transmitters
DPM Jumper Setup Screens
Click on any of the displayed plug-in boards, and you will be presented with the jumper positions and electrical connections for your selected board. This minimizes the need to refer to the printed manual.
more
Setup Screen 15 for Digital Panel Meters and Digital Transmitters
DPM Commands Screen
This page allows you set up external input, serial communications, an analog output proportional to the display (optional), and lockouts for Laureate digital counters. The grayed out area at the top right of the screen applies to Laureate remote displays.
more
Graphical Output Screens (not available with Ethernet)

From the Main Menu, click on Readings if your PC is connected to the meter. A pull-down menu then offers three choices: ListPlot and Graph.

  • List presents the latest readings in a 20-row by 10-column table. Press Pause at any time to freeze the display. This is one method to capture peak readings.   
  • Plot generates a plot of readings vs. time in seconds. It effectively turns the DPM-PC combination into a printing digital oscilloscope.
    more 
  • Graph generates a histogram where the horizontal axis is the reading and the vertical axis is the number of occurrences of readings. The display continually resizes itself as the number of readings increases.
    more
Setup Screen 18 for Digital Panel Meters and Digital Transmitters
DPM Calibration Screens
Click on the Scaling tab, which provides three scalClick on the Scaling tab, which provides three scaling methods to relate the signal to the displayed reading: 1) Scale and Offset method, 2) Coordinates of two points method, and 3) Reading Coordinates of Two Points method. The last method uses actual high and low signals, and the computer will prompt you.
more
Setup Screen 19 for Digital Panel Meters and Digital Transmitters
Frequency Meter Calibration Screen
Calibration of the quartz crystal of the Laureate frequency meter requires the input of a known frequency from a calibrator. Apply the frequency, then enter the frequency in Hertz. Calibration will be automatic, with storage of the calibration factor stored in non-volatile memory.
more

 

Dimensions

Laurel transmitter case

Dimensioned CAD assembly drawings in EPRT, STEP, x_t, .dwg, pdf file formats: Laureate-transmitter-case.zip (zipping prevents browser from opening CAD files as text files).

 

Duty Cycle & Pulse Width Modulation (PWM) Modes
Duty cycle graph In duty cycle mode, the transmitter displays ON or OFF time in percent from 0% to 100% of period for repetitive pulse trains. In the illustration, duty cycle in percent is 100 x t/P.

In pulse width modulation (PWM) mode, the meter also determines the duty cycle ratio, but then scales this ratio for display in engineering units.

 

 

CAL-Digital

Certificate of Calibration

$65.00

CBL02

USB-to-RS232 Adapter Cable

$47.00

CBL04

RS232 Cable for LT Transmitters

$47.00

CBL12

12-foot Power Cable

$47.00

CBL6

6-foot Power Cable

$41.00
Ordering Guide
Part Number as Configured: LTE80FR
Price as Configured: $613.00

Click on the Option Board Links for More Product Information

Base Item
$388.00
Main Board
$55.00
Power (Isolated)
$89.00
$89.00
Signal Input (Isolated)
$81.00
Part Number as Configured:
LTE80FR
Price as Configured:
$613.00
Quantity:
- +
Extended Price:
$613.00

Understanding the Laureate™ LTE Series DIN Rail Transmitter for Duty Cycle & Pulse Width Modulation

The Laureate™ LTE Series DIN rail transmitter for duty cycle is a measure of ON or OFF period as a percentage of total period. Duty cycle is determined by averaging an integral number of periods over a gate time selectable from 10 ms to 199.99 s. The same signal is applied to Channels A and B. The transmitter divides the average pulse width t by the period P between pulses and expresses the ratio t/P in percent. A resolution of 1%, 0.1%, or 0.01% is selectable. By selecting leading or falling pulse edges, ON or OFF duty cycle can be transmitted.

Pulse Width Modulation (PWM) Mode

PWM is a transducer output format where measured information is provided as duty cycle applied to a constant frequency, such as 120 Hz. As for duty cycle mode, the transmitter divides the average pulse width by the period between pulses over the selectable gate time, then scales this ratio mathematically to transmit it in engineering units, such as relative humidity (RH).

Signal Specifications

Frequency range is 0.005 Hz to 10 kHz for both duty cycle and PWM modes. Accuracy is 0.01% from 0.005 Hz to 500 Hz, 0.1% at 5 kHz, and 1% at 10 kHz. Maximum timing interval is 199.99 s. The Laureate duty cycle and PWM transmitter uses an Extended counter main board and the FR dual-channel signal conditioner, accepting signals from 12 mV to 250 Vac from proximity switches with PNP or NPN output, TTL or CMOS logic, and contact closures. Noise filter is selectable at 1 MHz, 30 kHz, or 250 Hz; contact debounce is selectable at 0, 3, or 50 ms.

Ethernet Data I/O

Standard Ethernet Data I/O is 10/100 Base-T per IEEE 802.3, isolated to 250V rms working / 2.3 kV rms per 1 minute test, with Modbus TCP at digital address 247. Analog output levels are 0-20 mA or 0-10 Vdc (selectable), 16-bit resolution, 0.02% of output span accuracy plus conversion accuracy.

Where LTE Duty Cycle & PWM Transmitters Are Used

  • Networked PWM Sensor Signal Conversion — engineering-unit scaling (e.g., relative humidity) from constant-frequency PWM sensor outputs over Ethernet.
  • Motor Drive Duty Cycle Monitoring — ON/OFF duty cycle tracking with Modbus TCP reporting.
  • HVAC & Environmental PWM Sensor Integration — networked duty-cycle-to-engineering-unit conversion for RH or pressure sensors.
  • Multi-Point Networked Duty Cycle Monitoring — several transmitters on one Modbus TCP network.
  • OEM Networked PWM Instrumentation — DIN rail integration into Ethernet-based control panels.

LTE Duty Cycle & PWM Transmitter Frequently Asked Questions

Why does documented accuracy degrade from 0.01% at frequencies up to 500 Hz to a full 1% at 10 kHz?

Documented specification specifically ties accuracy tiers to frequency, with the finest 0.01% figure documented across 0.005 Hz to 500 Hz, degrading to 0.1% at 5 kHz and 1% at 10 kHz — since duty cycle is computed by timing pulse width against total period using gate-time-based counting, higher-frequency signals leave proportionally less absolute time within each cycle to resolve fine timing differences, which is documented as the reason accuracy coarsens as frequency increases.

Why does the transmitter apply "the same signal" to both Channel A and Channel B for duty cycle measurement, rather than using two independent signal sources?

Documented description specifically states duty cycle measurement applies the same signal to both channels — this is consistent with the transmitter needing to independently detect both the pulse width (t) and the total period (P) from that single waveform, using the shared A/B channel architecture to extract both measurements from one signal rather than comparing two genuinely different, independent inputs the way some other LTE Series dual-channel modes do.

Does PWM mode's documented scaling to "engineering units" change the underlying accuracy of the duty cycle measurement itself?

No — documented description specifically frames PWM mode as determining the same duty cycle ratio as duty cycle mode, then mathematically scaling that ratio for display in engineering units; this scaling is a downstream mathematical conversion applied after the duty cycle ratio itself has already been measured, so the documented accuracy figures for the underlying duty cycle/PWM measurement apply the same way regardless of whether the final display is in percent or a scaled engineering unit.

Why does the documented PWM example specifically use a 120 Hz constant carrier frequency rather than an arbitrary frequency?

The page documents 120 Hz specifically as "such as" one example of a constant carrier frequency used in PWM transducer output format, without stating this as a fixed requirement — this is consistent with PWM transducers in general being documented as using some fixed carrier frequency (of which 120 Hz is one common real-world example) upon which the duty cycle is modulated to encode the measured value, rather than the transmitter itself requiring exactly 120 Hz to function.

Does selecting leading versus falling edge triggering change which physical portion of the waveform (ON time or OFF time) is measured as "duty cycle"?

Yes — documented description specifically states that by selecting leading or falling pulse edges, either ON or OFF duty cycle can be transmitted; this indicates the edge selection determines which specific portion of the periodic waveform (the ON time or the OFF time) is being measured and expressed as the duty cycle ratio, rather than edge selection being unrelated to which duty cycle value is reported.

Does this LTE Duty Cycle/PWM transmitter's documented Modbus TCP-only protocol limit compatibility compared to the RS232/RS485 LT Series duty cycle variant?

Yes — this page documents Modbus TCP specifically as the supported Ethernet Data I/O protocol at digital address 247, while the LT Series serial variant is documented elsewhere as separately supporting Modbus RTU/ASCII and Laurel Custom ASCII; a control system needing a protocol other than Modbus TCP would need to reference the LT Series serial variant rather than this LTE Ethernet variant.

Does the documented power consumption figure (2.4W typical) differ from the 2.5W typical figure documented on several other LTE Series transmitters?

Yes — this page documents 2.4W typical at 24V (4W with max excitation output), a slightly different figure from the 2.5W typical / 4.0W max figures documented on several other LTE Series pages; this genuine difference reflects that documented power consumption varies by specific transmitter model and its particular signal conditioner board, so this duty cycle/PWM transmitter's own figures shouldn't be assumed to match other LTE Series product pages.

Can the same physical transmitter be reconfigured between duty cycle mode and PWM mode, or does each require separate hardware?

Documented description presents duty cycle mode and PWM mode as two configuration options built on the same underlying Extended main board and FR signal conditioner, distinguished by whether the ratio is displayed directly as a percentage (duty cycle mode) or mathematically scaled into engineering units (PWM mode) — this is consistent with a setup/configuration choice on shared hardware rather than a distinction requiring different transmitter models.

Does the documented resolution selection (1%, 0.1%, or 0.01%) trade off against the transmitter's documented update rate?

The page documents both resolution and update rate as tied to the selectable gate time (10 ms to 199.99 s) without stating resolution and update rate are directly linked to each other independently of gate time — since finer resolution generally benefits from longer gate times to average more integral periods together, and the documented output update rate is also directly governed by gate time, selecting a longer gate time for finer resolution is consistent with correspondingly slowing the update rate, the same general gate-time tradeoff documented across the LTE Series.

Does the Extended main board requirement for this duty cycle/PWM transmitter also enable the custom curve linearization documented elsewhere for other LTE Series Extended-board transmitters?

Yes — documented features section specifically lists "Extended allows up to 180 data points for custom curve linearization and a rate derived from consecutive readings" as part of this transmitter's own feature set, consistent with the same Extended main board capability documented across other LTE Series FR-based transmitters, applicable here to further correcting or scaling the duty cycle/PWM-derived reading.

PWM Sensor Signal Conditioning Questions From the Field

Why do some humidity sensor designs specifically encode relative humidity as a duty cycle ratio rather than a simple analog voltage?

Documented sensor design examples specifically use a capacitive humidity-sensitive element as part of a timing circuit (such as connected to the threshold and trigger pins of a 555-style timer), where the sensor's own changing capacitance directly determines the charge/discharge timing and therefore the resulting duty cycle — this documented approach makes the duty cycle itself inherently proportional to humidity, and documented analysis notes this method can also make the resulting frequency independent of supply voltage when duty cycle is set near 50 percent.

Is there a documented typical accuracy figure achievable with a duty-cycle-based humidity sensing circuit?

Yes — one documented circuit design specifically cites an accuracy of less than ±3.9 percent RH using a duty-cycle-timing approach based on a variable-capacitance humidity sensor; this documented figure gives a concrete sense of the accuracy range achievable with this type of PWM/duty-cycle-encoded humidity sensing method.

Why does PWM output specifically offer better noise immunity and lower power consumption compared to a current-loop transducer output, according to documented technical analysis?

Documented technical comparison specifically notes PWM output requires less than 1mW when connected to a high-impedance node, versus 20mW to 100mW documented for a comparable current-loop transducer in a 5V system — documented analysis attributes PWM's favorable noise immunity and lower power characteristics specifically to its pulse-timing encoding method, which the source describes as suitable for transmission over longer distances similarly to current-loop signals, but with documented efficiency advantages particularly relevant for battery-powered applications.

Is there a documented standard mapping between a transducer's ratiometric analog output range and the resulting PWM duty cycle range?

Yes — one documented PWM transducer circuit specifically maps a 0.5V to 4.5V ratiometric sensor output range to a corresponding 10% to 90% duty cycle range, with the documented "offset" corresponding to 10% duty cycle and "span" corresponding to 80% duty cycle; this documented mapping illustrates a standard, defined relationship some PWM sensor circuits use between the underlying analog measurement and the resulting duty cycle output.

Does documented guidance recommend using a dedicated frequency counter with pulse-width measurement capability to properly interpret a PWM sensor's compensated output?

Yes — documented technical guidance specifically identifies a frequency counter with a pulse-width-measurement option as one appropriate instrument for measuring a PWM sensor output's pulse width during sensor compensation, alongside the alternative documented approach of interfacing the PWM output to a microcontroller and using its internal timer to calculate the interval between low-to-high and high-to-low transitions.

Does a PWM humidity or process sensor output always require conversion to a standard 0-10V or 4-20mA signal before it can drive typical industrial control equipment?

Often yes for standard industrial actuators — documented field guidance specifically notes that standard humidifier valve or damper actuators typically expect 0-10V or 4-20mA modulating signals, and specifically recommends using a PWM converter or binary output stage where connected equipment (such as some industrial ultrasonic humidifiers requiring 24V on/off staging) cannot directly accept a PWM signal, indicating PWM-to-standard-signal conversion is a genuine, documented practical requirement in many real installations.

Is there a documented distinction between the accuracy expectations for process-control humidity applications versus general comfort-control applications?

Yes — documented field guidance specifically recommends ±2% RH accuracy for process control applications, contrasted with ±5% RH accuracy documented as acceptable for general comfort applications; this documented accuracy distinction reflects that the required precision for a PWM/duty-cycle-derived humidity reading genuinely depends on the specific end-use application's tolerance requirements.

Does sensor drift affect a PWM/duty-cycle-based humidity sensor differently than it affects other sensor output types, according to documented guidance?

Documented guidance doesn't specifically single out PWM/duty-cycle sensors as uniquely prone to drift, but does specifically recommend annual recalibration per manufacturer specifications to account for sensor drift over time in humidity sensing generally; this documented recalibration practice applies to the underlying sensing element's own drift characteristics, which would similarly affect the duty cycle output regardless of whether it's ultimately read by a dedicated PWM-capable transmitter or another signal conditioning method.