Understanding the Laureate™ LTE Series DIN Rail Transmitter for Thermocouple Temperature Input
The Laureate™ LTE Series DIN rail transmitter for thermocouple input delivers a linearized, highly accurate, stable, and repeatable output for thermocouple types J, K, T, E, N, R, or S. The thermocouple type and temperature range, specified in °C or °F, are user-selectable. The temperature range can be as wide as the entire span of the thermocouple type, or as narrow as 150 counts (such as 15.0°), limited only by considerations of electrical noise and digital filtering time constants.
Per-Type Conformity Error
Each thermocouple type carries its own documented conformity error across its full range: Type J, ±0.09°C; Type K, ±0.1°C; Type T (0°C to 400°C), ±0.03°C, and (below 0°C), ±0.2°C; Type E, ±0.18°C; Type N, ±0.10°C; Type R, ±0.17°C; Type S, ±0.12°C. Calibration is per NIST Monograph 125 (IPTS-68). Overall error at 25°C is ±0.01 of full scale ±2 counts.
Cold Junction Compensation
For cold junction compensation (CJC), an external transistor is mounted adjacent to the thermocouple input to measure ambient temperature. That transistor is calibrated as a system with the signal conditioner board. Reference junction tempco is ±0.02 deg/deg.
Signal Specifications
Input resistance is 1 GΩ, input current is 100 pA. Maximum lead resistance is 1 kΩ for rated accuracy. Span tempco is ±0.003% of reading/°C. Overvoltage protection is 125 Vac. NMR at 50/60 Hz is 80 dB plus a selectable filter from 80 ms to 9.6 s time constant. CMR, DC-60 Hz is 120 dB with 500Ω imbalance; CMV, DC-60 Hz is 250 Vac from power and earth grounds. Open sensor indication is selectable as 0 mA or greater than 20 mA output. Analog output step response time is 50 ms.
Fast ON/OFF Control & Ethernet I/O
With the optional dual solid state relay output, rated with a typical response time of only 17 ms, Laureate temperature transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control, or as supervisory process monitors providing alarms when processes exceed normal limits. Relay modes must be non-latching, since 4-20 mA temperature transmitters do not offer external reset. Standard Ethernet Data I/O is 10/100 Base-T per IEEE 802.3, isolated to 250V rms working / 2.3 kV rms per 1 minute test, with Modbus TCP at digital address 247.
Where LTE Thermocouple Transmitters Are Used
- Networked Furnace & Kiln Monitoring — Ethernet-connected high-temperature thermocouple readout.
- Fast Closed-Loop Temperature Control — 17 ms relay response for tight ON/OFF control loops.
- Multi-Zone Process Heating — networked thermocouple monitoring across distributed heating zones.
- Supervisory Temperature Alarming — shutoff/alarm relay action on out-of-range process temperature.
- Multi-Point Networked Temperature Monitoring — several transmitters on one Modbus TCP network.
- OEM Networked Temperature Instrumentation — DIN rail integration into Ethernet-based control panels.
LTE Thermocouple Transmitter Frequently Asked Questions
Why does Type T thermocouple conformity error split into two separate figures (±0.03°C above 0°C, ±0.2°C below 0°C) while other types list one figure across their entire range?
Documented specification specifically lists this split only for Type T, without a comparable split for the other six documented types — this reflects that Type T's own thermoelectric characteristic curve is documented as having a genuinely different, more variable conformity error below 0°C compared to its 0-400°C range, whereas the other thermocouple types are documented with one conformity error figure applicable across their full listed span.
Why does relay latching mode specifically have to be non-latching on this thermocouple transmitter?
Documented explanation specifically ties this requirement to the transmitter's 4-20 mA output format lacking any external reset input — since a latching relay mode requires some mechanism to reset it after tripping, and documented description specifically states temperature transmitters in this 4-20 mA format don't offer that external reset capability, non-latching is documented as the only relay mode that remains usable without a reset path.
Does the documented external CJC transistor need to be separately calibrated by the user, or is it factory-handled?
Factory-handled — documented description specifically states the CJC transistor "is calibrated as a system with the signal conditioner board," indicating the transistor's calibration is bundled into the factory calibration process for that specific board rather than requiring separate user calibration; this is consistent with the broader documented practice of factory-calibrated ranges with calibration factors stored in EEPROM.
Why does maximum lead resistance (1 kΩ) matter specifically "for rated accuracy" rather than being an absolute hard limit?
Documented phrasing specifically qualifies the 1 kΩ figure as the threshold "for rated accuracy," rather than describing it as an absolute operational limit beyond which the transmitter stops functioning — this is consistent with lead resistance beyond 1 kΓ potentially still producing a reading, but one that may fall outside the transmitter's documented accuracy specifications, since additional lead resistance affects the tiny thermocouple voltage signal proportionally more as resistance increases.
Does selecting the "0 mA" open sensor indication option change the documented overall accuracy specification of the transmitter under normal operating conditions?
No — documented open sensor indication (selectable as 0 mA or greater than 20 mA output) is specifically a fault-condition behavior, describing what the transmitter outputs when the thermocouple circuit itself is broken; the documented ±0.01 of full scale ±2 counts overall accuracy figure applies during normal operation with an intact thermocouple, and is a separate specification from this fault-indication behavior.
Why is documented CMV (common mode voltage) at DC-60 Hz specified as 250 Vac from power and earth grounds, separate from the 125 Vac overvoltage protection figure?
These are documented as addressing two different scenarios — the 250 Vac CMV figure specifically describes a common mode voltage the input can tolerate relative to power and earth grounds during normal operation, while the 125 Vac overvoltage protection figure specifically describes a separate protective threshold; both are genuine, distinct documented input specifications rather than the same figure expressed two different ways.
Does this LTE Thermocouple transmitter's documented Modbus TCP-only protocol limit compatibility compared to the RS232/RS485 LT Series thermocouple variant?
Yes — this page documents Modbus TCP specifically as the supported Ethernet Data I/O protocol at digital address 247, while the LT Series serial variant is documented elsewhere as separately supporting Modbus RTU/ASCII and Laurel Custom ASCII; a control system needing a protocol other than Modbus TCP would need to reference the LT Series serial variant rather than this LTE Ethernet variant.
Does the documented 17 ms relay response time apply to the standard relay board, or specifically to the optional dual solid state relay board?
Specifically the dual solid state relay board — documented phrasing directly ties the 17 ms typical response time to "the optional dual solid state relay output option," distinguishing this fast solid-state figure from magnetic relay options, which are documented elsewhere across the LT/LTE family as having different (typically slower) mechanical switching characteristics.
Can the same physical LTE thermocouple transmitter be field-reconfigured between different thermocouple types, or does each type require separate hardware?
Documented ordering guide lists each specific thermocouple type/range combination (JC, JF, KC, KF, etc.) as a separate signal input selection at order time, while a separate documented note states "the same signal conditioner board can be user configured for all thermocouple types listed and °C or °F" — this indicates the underlying board hardware supports reconfiguration across types, even though ordering specifies one particular type/scale combination initially.
Does span tempco (±0.003% of reading/°C) and reference junction tempco (±0.02 deg/deg) represent the same underlying error source?
No — these are documented as two separate error sources with different units and mechanisms: span tempco describes how the transmitter's overall measurement scaling itself drifts with ambient temperature change, while reference junction tempco specifically describes drift in the cold junction compensation's own temperature-tracking accuracy; both contribute to total measurement drift with ambient temperature, but through documented, physically distinct mechanisms.
Cold Junction Compensation Questions From the Field
What specifically is the cold junction, and why does it need to be compensated for at all?
Documented explanation specifically identifies the cold junction (or reference junction) as the point where the two dissimilar thermocouple wires terminate and connect to the measuring instrument — since thermocouple calibration tables are documented as always assuming this reference junction is held at exactly 0°C, and in practice it instead sits at whatever the local ambient temperature happens to be, compensation is documented as necessary specifically to correct for that difference between the assumed 0°C reference and the junction's actual real-world temperature.
What specifically is an isothermal block, and why does its physical design matter for CJC accuracy?
Documented explanation specifically describes an isothermal block as a thermally conductive material to which both the thermocouple's terminal wires and the CJC temperature sensor are attached, specifically to ensure both are held at the exact same temperature; documented analysis identifies the temperature gradient between the actual cold junction and the CJC sensor as one of the two primary sources of CJC error, so an effective isothermal design is what keeps this specific gradient-driven error small.
Is there a documented typical magnitude of measurement error if cold junction compensation is entirely omitted?
Yes — documented analysis specifically cites a typical error of 20-30°C at room temperature if CJC is not implemented at all, illustrating that this isn't a minor correction but a genuinely large source of error; without it, documented explanation notes the derived temperature value would be corrupted directly by whatever the local ambient temperature happens to be.
Does a single CJC temperature sensor provide adequate compensation across multiple, physically spread-out thermocouple input channels?
Not necessarily, according to documented analysis — documented product comparison specifically notes that many competing multi-channel products use only a single temperature sensor to compensate several input channels together, while a more advanced documented approach uses a dedicated CJC sensor integrally mounted with each individual terminal block group, specifically because temperature gradients across a spread-out terminal block (from convective heating, transient air currents, or nearby heat sources) can otherwise introduce error that a single shared sensor wouldn't capture.
Can using mismatched thermocouple extension wire introduce an additional, unintended cold junction into a measurement circuit?
Yes — documented explanation specifically warns that using an incorrect type of wire to extend a thermocouple can create an additional, unintended thermocouple junction at that splice point, since any junction of dissimilar metals is documented as forming its own thermocouple effect; using extension wire that correctly matches the original thermocouple type is documented as necessary to avoid introducing this extra, uncompensated junction into the circuit.
Are there documented alternative CJC sensor technologies beyond a simple diode or transistor-based approach, and do they differ meaningfully in performance?
Yes — documented technology comparison specifically identifies resistive temperature detectors (RTDs) and thermistors as commonly used CJC sensor technologies alongside diode/transistor-based integrated circuit approaches, noting RTDs specifically offer high accuracy and linearity over a wide range but require their own excitation current and additional signal processing, representing a genuine documented performance and complexity tradeoff between these different CJC sensor technology choices.
Is there a documented reference temperature range over which typical onboard CJC circuitry compensates most effectively?
Yes — documented analysis specifically notes that a common onboard CJC compensation approach "works extremely well" for circuit ambient temperatures in the 20-50°C range, implying documented CJC performance can be more effective within this typical room-temperature-adjacent band than at more extreme ambient conditions, which is a genuine, specifically documented performance characteristic rather than uniform accuracy across all possible ambient temperatures.
Is an ice-point (0°C) reference bath still considered a documented viable CJC method for modern industrial use, or is it purely historical?
It's documented as still valid, though less commonly practical for routine industrial use — documented explanation specifically notes an ice-point reference (or its electronic equivalent using thermoelectric Peltier cooling to hold junctions continuously near 0°C) is still preferable on accuracy and stability grounds, since reference tables themselves are built on a 0°C assumption, with one documented electronic ice-point equivalent specifically citing typical errors of less than 0.1°C.




With the optional dual solid state relay output option, which has a typical response time of only 17 ms, Laureate temperature meters and transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. They can also serve as supervisory process monitors and provide alarms or shutoffs when processes exceed normal limits.